83
Check of LEV
No
Yes
Yes
No
Turn ON the breaker to the outdoor unit after checking LEV
coil is mounted to the LEV body securely.
Is "click - click" sound heard?
Or, do you feel vibration of LEV coil with your hand?
Disconnect the connectors.
MXZ-2D
CN724: LEV A, CN725: LEV B
Other models
CN791: LEV A, CN792: LEV B,
CN793: LEV C, CN794: LEV D,
CN795: LEV E, CN796: LEV F
Normal
Is the resistance of the LEV coil normal?
(Refer to 11-5.)
Replace the inverter P.C. board or
the outdoor control P.C. board.
Replace LEV coil.
• In cooling, the heat exchanger of non-operating indoor unit has frosted.
• In heating, non-operating indoor unit gets warm.
CN724
CN725
CN793
CN794
CN795
CN796
Outdoor
control
P.C. board
MXZ-3D/4D/5D
MXZ-2D
Inverter
P.C. board
OBH626B