80
SERVICE FUNCTIONS
11
ACTUATOR CONTROL
10
Relation between main sensor and actuator
MXZ-2A20NA MXZ-2A20NA -
1
MXZ-2A20NA -
2
MXZ-3A30NA MXZ-3A30NA -
1
MXZ-4A36NA
Discharge temperature thermistor
Indoor coil thermistor
Defrost thermistor
Gas pipe temperature thermistor
(MXZ-2A20NA, MXZ-3A30NA)
Fin temperature thermistor
Ambient temperature thermistor
Outdoor heat exchanger temperature
Capacity code
Purpose
Protection
Defrosting Protection
Defrosting
Control
Protection
Control
Protection
Control
Compressor
LEV
Outdoor
fan motor
4-way
valve
Sensor
Actuator
11-1. PRE-HEAT CONTROL <MXZ-2A20NA -
1
, MXZ-2A20NA -
2
, MXZ-3A30NA -
1
, MXZ-4A36NA
>
If moisture gets into the refrigerant cycle, or when refrigerant is liquefied and collected in the compressor, it may interfere
the start-up of the compressor.
To improve start-up condition, the compressor is energized even while it is not operating.
This is to generate heat at the winding.
The compressor uses about 50 W when pre-heat control is turned ON.
Pre-heat control is ON at initial setting.
[How to deactivate pre-heat control]
Turn OFF the power supply for the air conditioner before making the setting.
Set the 4th Dip Switch of SW1 on the outdoor electronic control P.C. board to ON to deactivate pre-heat control func-
tion (MXZ-2A20NA -
1
, MXZ-2A20NA -
2
).
Set the 4th Dip Switch of SW2 on the outdoor electronic control P.C. board to ON to deactivate pre-heat control func-
tion (MXZ-3A30NA -
1
, MXZ-4A36NA).
Turn ON the power supply for the air conditioner.
NOTE
: Pre-heat control will be turned OFF when the breaker is turned OFF.
ON
SW2
1 2 3 4 5 6
ON
SW2
1 2 3 4 5 6
MXZ-3A30NA -
MXZ-4A36NA
SW2
SW1
SW871
ON
SW1
1 2 3 4
MXZ-2A20NA -
ON
1 2 3 4
SW1
1
MXZ-2A20NA -
2
1