59
Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the
tables
below.
When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe, see 16-1.
Unit : inch
Piping length each indoor unit (a, b)
82 ft. MAX.
Total piping length (a+b)
164 ft. MAX.
Bending point for each unit
25 MAX.
Total bending point
60 MAX.
It does not matter which unit is higher.
MAX. REFRIGERANT PIPING LENGTH & PIPE SIZE SELECTION
MXZ-2A20NA MXZ-2A20NA -
1
MXZ-2A20NA -
2
Operating Range
MXZ-2A20NA MXZ-2A20NA -
1
MXZ-2A20NA -
2
Cooling
Heating
Maximum
Minimum
Maximum
Minimum
Indoor intake air temperature
95°FDB, 71°FWB
67°FDB, 57°FWB
80°FDB, 67°FWB
70°FDB, 60°FWB
Outdoor intake air temperature
115°FDB
14°FDB
75°FDB, 65°FWB
14°FDB, 12°FWB
a
b
Outdoor
unit
Indoor
units
49 ft.
33 ft.
49 ft.
Indoor unit class
Extension pipe diameter
09
Liquid
1/4
Gas
3/8
12
Liquid
1/4
Gas
3/8
15
Liquid
1/4
Gas
1/2
Outdoor unit union diameter
For
Indoor unit A
Liquid
1/4
Gas
3/8
Indoor unit B
Liquid
1/4
Gas
3/8