32
H
H
Check of HPS
Infinity
0
"
Yes
No
Start
1. Disconnect the connector CN722 in the electronic control P. C. board.
2. Check the resistance of HPS after 1 minute has passed since the outdoor unit power supply was turned off.
Check the resistance between
each terminal.
Reconnect CN722.
Turn on power supply to the indoor and outdoor unit.
3 minutes later, EMERGENCY OPERATION starts.
Is HPS protection displayed
immediately after compressor
starts?
Replace HPS (63H1).
Replace the electronic control P. C. board.
Normal
I
I
The other cases
In the case that the indoor fan and outdoor fan operate but the compressor does not operate, it causes that the
high pressure switch can be operated once.
First of all, check the high pressure switch can be shorted, turn OFF the power and turn ON again 1 minute later.
Indoor unit dose not operate. (difference modes)
• When you try to run two indoor unit simultaneously, one for cooling and the other for heating, the unit which
transmits signal to the outdoor units earlier decides the operation mode. The other unit indicates as shown in
the figure below.
• When the above situation occurs, set all the indoor units to the same mode, turn OFF the indoor units, and
then turn them back ON.
• Though the top of the indoor unit sometimes gets warm, this does not mean malfunction. The reason is that
the refrigerant gas continuously flows into the indoor unit even while it is not operating.
OPERATION INDICATOR
Lighting
Flashing
• When the operation frequency does not go up from lowest frequency.
OB287B--2.qxp 06.6.7 11:15 AM Page 32