background image

3

2.  Installation diagram & parts

1. Safety precautions

1.3.  Before electric work

 Caution:

•  Be sure to install circuit breakers. If not installed, electric shock may result.

IMPORTANT
Make sure that the current leakage breaker is one compatible with higher 
harmonics.
Always use a current leakage breaker that is compatible with higher harmon-
ics as this unit is equipped with an inverter.
The use of an inadequate breaker can cause the incorrect operation of 
inverter.

•  For the power lines, use standard cables of sufficient capacity. Otherwise, a 

short circuit, overheating, or fire may result.

1.4.  Before starting the test run

 Caution:

•  Turn on the main power switch more than 12 hours before starting operation. 

Starting operation just after turning on the power switch can severely damage 
the internal parts. Keep the main power switch turned on during the operation 
season.

•  Before starting operation, check that all panels, guards and other protective 

parts are correctly installed. Rotating, hot, or high voltage parts can cause 
injuries.

•  When installing the power lines, do not apply tension to the cables. If the 

connections are loosened, the cables can snap or break and overheating or 
fire may result.

•  Be sure to ground the unit. Do not connect the ground wire to gas or water 

pipes, lighting rods, or telephone grounding lines. If the unit is not properly 
grounded, electric shock may result.

•  Use circuit breakers (ground fault interrupter, isolating switch (+B fuse), and 

molded case circuit breaker) with the specified capacity. If the circuit breaker 
capacity is larger than the specified capacity, breakdown or fire may result.

•  Do not touch any switch with wet hands. Electric shock may result.
•  Do not touch the refrigerant pipes with bare hands during operation. The 

refrigerant pipes are hot or cold depending on the condition of the flowing 
refrigerant. If you touch the pipes, burns or frostbite may result.

•  After stopping operation, be sure to wait at least five minutes before turning off 

the main power switch. Otherwise, water leakage or breakdown may result.

1.5.  Using R410A refrigerant air conditioners

 Caution:

•  Use C1220 copper phosphorus, for copper and copper alloy seamless pipes, 

to connect the refrigerant pipes. Make sure the insides of the pipes are clean 
and do not contain any harmful contaminants such as sulfuric compounds, 
oxidants, debris, or dust. Use pipes with the specified thickness. (Refer to 
page 6) Note the following if reusing existing pipes that carried R22 refriger-
ant.

-  Replace the existing flare nuts and flare the flared sections again.
-  Do not use thin pipes. (Refer to page 6)

•  Store the pipes to be used during installation indoors and keep both ends of 

the pipes sealed until just before brazing. (Leave elbow joints, etc. in their 
packaging.) If dust, debris, or moisture enters the refrigerant lines, oil dete-
rioration or compressor breakdown may result.

•  Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration 

oil applied to the flared sections. If mineral oil is mixed in the refrigeration 
oil, oil deterioration may result.

•  Do not use refrigerant other than R410A refrigerant. If another refrigerant is 

used, the chlorine will cause the oil to deteriorate.

•  Use the following tools specifically designed for use with R410A refrigerant. 

The following tools are necessary to use R410A refrigerant. Contact your 
nearest dealer for any questions.

Tools (for R410A)

Gauge manifold

Flare tool

Charge hose

Size adjustment gauge

Gas leak detector

Vacuum pump adapter

Torque wrench

Electronic refrigerant charging scale

•  Be sure to use the correct tools. If dust, debris, or moisture enters the refriger-

ant lines, refrigeration oil deterioration may result.

•  Do not use a charging cylinder. If a charging cylinder is used, the composition 

of the refrigerant will change and the efficiency will be lowered.

2.1.  Before installation (Fig. 2-1)

This installation manual is only for the outdoor unit installation. In installing 
the indoor units and branch box, refer to the installation manual attached 
to each unit.

Any structural alterations necessary for the installation must comply with the local 
building code requirements.

This diagram is intended to show the configuration of accessories.
For actual installation, the outdoor unit is to be turned 180°.

Units should be installed by licensed contractor according to local code require-
ment.

Note:
The dimensions given along the arrows above are required to guarantee the 
air conditioner’s performance. Install the unit in as wide a place as possible 
for later service or repairs.

Parts to be locally procured

[A]

Branch box/outdoor unit connecting wire 
(3-core, Refer to 7.3. External wiring procedure)

1

[B]

Extension pipe

1

[C]

Wall hole sleeve

1

[D]

Wall hole cover

1

[E]

Pipe fixing band 
(The quantity depends on the pipe length.)

2 to 7

[F]

Fixing screw for [E] 4 × 20 mm
(The quantity depends on the pipe length.)

2 to 7

[G]

Piping tape

1

[H]

Putty

1

[I]

Drain hose (hard PVC pipe VP16)

1

[J]

Refrigeration oil

1

[K]

Power supply cord
(2-core, Refer to 7.3. External wiring procedure)

1

Fig. 2-1

[K]

[A]

[H]

[I]

[B]

[C]

[D]

[E]

[F]

[G]

Branch box

5-branches type

Outdoor unit

3-branches type

Содержание MXZ-160VA-A

Страница 1: ...TALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit Air Conditioners OUTDOOR UNIT MXZ 8B140 160VA A FOR INSTALLER HFC utilized R410A ...

Страница 2: ...ock or fire may result When installing or relocating or servicing the air conditioner use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pressure in the refrigerant line and may result in an explosion and other hazar...

Страница 3: ...s that carried R22 refriger ant Replace the existing flare nuts and flare the flared sections again Do not use thin pipes Refer to page 6 Store the pipes to be used during installation indoors and keep both ends of the pipes sealed until just before brazing Leave elbow joints etc in their packaging If dust debris or moisture enters the refrigerant lines oil dete rioration or compressor breakdown may ...

Страница 4: ...serving the table below The unit s quantities are limited in 2 to 8 units For the next step make sure that the total rated capacity selected will stay in a range as shown below MXZ 8B140 3 0 18 5kw MXZ 8B160 3 0 20 2kw Example MXZ 8B140 MSZ 60 6 0 SEZ 35 3 5 SLZ 35 3 5 SEZ 25 2 5 SLZ 25 2 5 Indoor unit type 15 20 22 25 35 42 50 60 71 80 100 1 Rated capacity Cooling kW 1 5 2 0 2 2 2 5 3 5 4 2 5 0 6...

Страница 5: ... more than three units must be installed side by side In addition leave space as shown Do not install the optional air outlet guides for upward airflow Obstacles at front only Fig 3 13 When using an optional air outlet guide the clearance is 1000 mm or more Obstacles at front and rear only Fig 3 14 When using an optional air outlet guide the clearance is 1000 mm or more Single parallel unit arrange...

Страница 6: ...ervicing the air conditioner use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pres sure in the refrigerant line and may result in an explosion and other hazards The use of any refrigerant other than that specified ...

Страница 7: ... of using 1 branch box Flare connection employed No brazing N In case of using 2 branch boxes Branch box 1 2 branches pipe joint optional parts Branch box 2 Conversion formula 1 4 F ø6 35 3 8 F ø9 52 1 2 F ø12 7 5 8 F ø15 88 3 4 F ø19 05 5 3 Addition of refrigerant Additional charging is not necessary for this unit if the total pipe length b1 b2 a1 a2 a3 a4 a5 a6 a7 a8 does not exceed 40 m If the ...

Страница 8: ...ry If it is used a gas leakage or even a pipe extraction may occur 2 For details about connecting the pipes for the P100 indoor unit refer to the installation manual of the Y shape connection pipe PAC AK52YP E When bending the pipes be careful not to break them Bend radii of 100 mm to 150 mm are sufficient Make sure the pipes do not contact the compressor Abnormal noise or vibration may result Pipe...

Страница 9: ... in Cap Wrench hole Completely closed Operation section LO HI A C D B K E F G H I Fig 5 11 5 8 Airtight test and evacuation Airtight test Fig 5 11 Airtight test should be made by pressurizing nitrogen gas For the test method refer to the following figure 1 Connecting the testing tool Make a test with the stop valve closed Be also sure to pressurize both liquid or high pressure pipe and gas or low p...

Страница 10: ... pipe and gas or low pressure pipe with the stop valve closed Remember Never carry out air purge by refrigerant Warning When installing or moving a unit to another place do not mix anything other than specified refrigerant into the refrigeration cycle If air is mixed the refrigeration cycle may obtain abnormally high pressure resulting in a burst pipe A high precision gravimeter measurable up to 0 ...

Страница 11: ...not be operated by a single remote controller 3 2 Different refrigerant systems cannot be connected together 3 3 A M NET adapter cannot be connected to an outdoor unit 3 1 Group operation by single remote controller 3 2 Group operation between different refrigerant systems 3 3 Connection of M NET adapter to outdoor unit Master controller G 50 etc Power supply unit 2 1 Only 3 branch type 2 2 Only 5...

Страница 12: ...ower supply work can be carried out at just one spot of the outdoor unit It will contribute to simplify the work and save costs Power supply Model Power supply 140 160V N 220 230 240V 50Hz N 220V 60Hz Max Permissive System Impedance 0 22 Ω Note Power supply input Outdoor unit only Connect the lines C D in accordance with the terminal block names to ensure correct polarity Model Wire diameter Break...

Страница 13: ...ermediate connections can lead to communication errors if water enters the cables and causes insufficient insulation to ground or a poor electrical contact at the inter mediate connection point If an intermediate connection is necessary be sure to take measures to prevent water from entering the cables 1 Power supply cords of appliances shall not be lighter than design 60245 IEC or 227 IEC 2 In cas...

Страница 14: ...t run may not start 8 Test run 8 1 Before test run After completing installation and the wiring and piping of the indoor and outdoor units check for refrigerant leakage looseness in the power supply or control wiring wrong polarity and no disconnection of one phase in the supply Use a 500 volt M ohm tester to check that the resistance between the power supply terminals and ground is at least 1 MΩ ...

Страница 15: ...ration mode locking func tion by external signal CN3S Remote control panel Relay circuit External input adapter PAC SC36NA Outdoor unit control board Relay power supply Procure locally Max 10m ON OFF SW1 Heating Cooling SW2 Validity of SW1 Invalidity of SW1 Any indoor unit that is operating in a mode different from the one specified by the external signal will enter the standby mode The setting bec...

Страница 16: ...ase be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U438L01 ...

Отзывы: