47
OPERATING PROCEDURE
PHOTOS
5. Removing outdoor fan motor
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN931, CN932 (Fan motor)
(3) Remove the propeller nut.
(4) Remove the propeller.
(5) Remove the screws fixing the fan motor.
(6) Remove the fan motor.
Photo 6
Photo 7
Photo 8
6. Removing the compressor and 4-way valve
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Remove the inverter assembly. (Refer to 2.)
(3) Recover gas from the refrigerant circuit.
NOTE:
Recover gas from the pipes until the pressure gauge
shows 0 kg/cm
2
(0 MPa).
(4) Detach the brazed part of the suction and the discharge pipe
connected with compressor.
(5) Remove the nuts of compressor legs.
(6) Remove the compressor.
(7) Detach the brazed part of pipes connected with 4-way valve.
Defrost thermistor
Outdoor heat
exchanger tempera-
ture thermistor
Propeller nut
Screws of the outdoor fan motor
Propeller
Brazed parts of 4-way valve
Ambient temperature
thermistor
OBH629A
Содержание MUZ-SF25VE
Страница 9: ...9 WIRING DIAGRAM 6 MUZ SF25VE MUZ SF35VE MUZ SF25VEH MUZ SF35VEH OBH629A ...
Страница 10: ...10 MUZ SF42VE MUZ SF50VE MUZ SF42VEH MUZ SF50VEH OBH629A ...
Страница 51: ...51 OBH629A ...