12
MUZ-SF50VE MUZ-SF50VEH
Unit: mm
Outdoor
heat
exchanger
Flared connection
Defrost
thermistor
RT61
Discharge
temperature
thermistor
RT62
Flared connection
Stop valve
Stop valve
(with service port)
Capillary tube
ø4.0×ø2.4×100
Capillary tube
ø4.0×ø2.4×200
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe
ø
12.7
(with heat insulator)
Refrigerant pipe
ø
6.35
(with heat insulator)
LEV
R.V. coil
heating ON
cooling OFF
Muffler
#100
Strainer
#100
Outdoor heat
exchanger
temperature
thermistor
RT68
Amb
tem
ther
RT6
Strainer
#100
Muffler
Capillary tube
ø3.0×ø2.0×200(×4)
Max. Length
A
Max. Height
difference
B
Indoor
unit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFEFRENCE
Refrigerant piping: m
Piping size O.D: mm
Max. Length A
Max. Height difference B
Gas
Liquid
MUZ-SF25/35/42
20
12
9.52
6.35
MUZ-SF50
30
15
12.7
ADDITIONAL REFRIGERANT CHARGE (R410A: g)
Model
Outdoor unit
precharged
7 m
8 m
9 m
10 m
11 m
12 m
13 m
14 m
15 m
20 m
MUZ-SF25
700
0
30
60
90
120
150
180
210
240
390
MUZ-SF35
800
MUZ-SF42
1,150
Calculation: X g = 30 g/m × (Refrigerant piping length (m) - 7)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
7 m
10 m
15 m
20 m
25 m
30 m
MUZ-SF50
1,550
0
60
160
260
360
460
Calculation: X g = 20 g/m × (Refrigerant piping length (m) – 7)
NOTE
: Refrigerant piping exceeding 7 m requires additional refrigerant charge according to the calculation.
OBH629