27
SERVICE FUNCTIONS
10
TROUBLESHOOTING
11
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the OPERATION INDICATOR lamp is flashing on and off before starting serv-
ice work.
2) Before servicing, check that the connector and terminal are connected properly.
3) When the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection
and the components for bursting and discoloration.
4) When troubleshooting, refer to 11-2, 11-3 and 11-4.
11-1. CAUTIONS ON TROUBLESHOOTING
1. Before troubleshooting, check the following
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and after
confirming the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the
electronic control P.C. board.
3) When removing the electrical parts, be careful to the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
MUZ-GA50VA
MUZ-GA60VA
MUZ-GA71VA
Contents of “SERVICE FUNCTIONS” have been removed.
Lead wiring
Housing point
Incorrect
Correct
Содержание MUZ-GA50VA-E1
Страница 10: ...10 MUZ GA60VA E3 ...