11
Max. Length
A
Max. Height
difference
B
Indoor
unit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Model
Refrigerant piping: ft.
Piping size O.D: in.
Max. Length
A
Max. Height difference
B
Gas
Liquid
MUZ-FS06NA
MUZ-FS06NAH
MUZ-FS09NA
MUZ-FS09NAH
MUZ-FS12NA
MUZ-FS12NAH
65
40
3/8
1/4
MUZ-FS15NA
MUZ-FS15NAH
MUZ-FS18NA
MUZ-FS18NAH
100
50
1/2
1/4
ADDITIONAL REFRIGERANT CHARGE (R410A: oz.)
NOTE
: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Model
Outdoor unit
precharged
Refrigerant piping length (one way): ft.
25
30
40
50
60
65
MUZ-FS06NA
MUZ-FS06NAH
MUZ-FS09NA
MUZ-FS09NAH
MUZ-FS12NA
MUZ-FS12NAH
2 lb. 9 oz.
0
1.08
3.24
5.40
7.56
8.64
Calculation: X oz. = 1.08/5 oz./ft. × (Refrigerant piping length (ft.) - 25)
NOTE
: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Model
Outdoor unit
precharged
Refrigerant piping length (one way): ft.
25
30
40
50
60
70
80
90
100
MUZ-FS15NA
MUZ-FS15NAH
MUZ-FS18NA
MUZ-FS18NAH
3 lb. 7 oz.
0
1.08
3.24
5.40
7.56
9.72
11.88
14.04
16.20
Calculation: X oz. = 1.08/5 oz./ft. × (Refrigerant piping length (ft.) - 25)