39
G Check of outdoor thermistors
MUZ-FH06/09/12
Thermistor
Symbol
Connector, Pin No.
Board
Defrost
RT61
Between CN641 pin1 and pin2
Inverter P.C. board
Discharge temperature
RT62
Between CN641 pin3 and pin4
Fin temperature
RT64
Between CN642 pin1 and pin2
Ambient temperature
RT65
Between CN643 pin1 and pin2
Outdoor heat exchanger temperature RT68
Between CN644 pin1 and pin3
Replace the thermistor except RT64.
When RT64 is abnormal, replace the inverter P.C.
board.
Replace the inverter P.C. board.
No
No
Is the resistance of thermistor normal?
(Refer to 10-6.1.)
Reconnect the connector of thermistor.
Turn ON the power supply and press EMERGENCY OPERATION switch.
Does the unit operate for 10 minutes or more
without showing thermistor abnormality?
OK
(Cause is poor contact.)
Yes
Yes
Disconnect the connector of thermistor in the inverter P.C. board (see
below table), and measure the resistance of thermistor.
MUZ-FH15/18
Thermistor
Symbol
Connector, Pin No.
Board
Defrost
RT61
Between CN671 pin1 and pin2
Inverter P.C. board
Discharge temperature
RT62
Between CN671 pin3 and pin4
Fin temperature
RT64
Between CN673 pin1 and pin2
Ambient temperature
RT65
Between CN672 pin1 and pin2
Outdoor heat exchanger temperature RT68
Between CN671 pin5 and pin6
OBH684C