13
Unit: mm
MUZ-EF50VG
Outdoor
heat
exchanger
Flared connection
Defrost
thermistor
RT61
Discharge
temperature
thermistor
RT62
Flared connection
Stop valve
(With strainer)
Stop valve
(with service port)
Capillary tube
ø4.0×ø2.4×240
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe ø9.52
(with heat insulator)
Refrigerant pipe ø6.35
(with heat insulator)
LEV
R.V. coil
heating ON
cooling OFF
Muffler
Outdoor heat
exchanger
temperature
thermistor
RT68
Ambient
temperature
thermistor
RT65
Strainer
#100
Muffler
Capillary tube
ø3.0×ø2.0×210(×2)
Max. Length
A
Max. Height
difference
B
Indoor
unit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Model
Refrigerant piping: m
Piping size O.D: mm
Max. Length A
Max. Height difference B
Gas
Liquid
MUZ-EF25/35VG(H)
MUZ-EF42VG
20
12
9.52
6.35
MUZ-EF50VG
30
15
ADDITIONAL REFRIGERANT CHARGE (R32: g)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
7 m
8 m
9 m
10 m
11 m
12 m
13 m
14 m
15 m
20 m
30 m
MUZ-EF25VG(H)
620
0
20
40
60
80
100
120
140
160
260
-
MUZ-EF35VG(H)
740
MUZ-EF42VG
MUZ-EF50VG
1,050
460
Calculation: X g = 20 g/m × (Refrigerant piping length (m) – 7)
NOTE:
Refrigerant piping exceeding 7 m requires additional refrigerant charge according to the calculation.
OBH832