6
1 Measured under rated operating frequency.
Outdoor model
MUZ-AP20VG
Power supply
Single phase, 230 V, 50 Hz
Capacity
Rated (Min.-Max.)
Cooling
kW
2.0 (0.6 - 2.7)
Heating
2.5 (0.5 - 3.5)
Breaker Capacity
A
10
Electrical data
Power input 1 (Set)
Cooling
W
460
Heating
600
Running current 1 (Set)
Cooling
A
2.6
Heating
3.2
Power factor 1 (Set)
Cooling
%
76
Heating
81
Starting current 1 (Set)
A
3.2
Coefficient of performance
(COP) 1 (Set)
Cooling
4.35
Heating
4.17
Compressor
Model
KVB073FYXMC
Output
W
470
Current 1
Cooling
A
2.19
Heating
2.81
Refrigeration oil (Model)
L
0.27 (FW68S)
Fan motor
Model
RC0J50-NC
Current 1
Cooling
A
0.22
Heating
0.20
Dimensions W × H × D
mm
800 × 550 × 285
Weight
kg
31
Special remarks
Dehumidification
Cooling
L/h
0.6
Airflow 1
Cooling
High
m
3
/h
2,178
Med
2,178
Low
1,038
Heating
High
2,076
Med.
1,788
Low
1,452
Sound level 1
Cooling
dB(A)
47
Heating
48
Fan speed
Cooling
High
rpm
940
Med
940
Low
470
Heating
High
900
Med.
780
Low
640
Fan speed regulator
3
Refrigerant filling capacity (R32)
kg
0.55
NOTE
: Test conditions are based on ISO 5151.
Cooling: Indoor Dry-bulb temperature 27°C
Wet-bulb temperature 19°C
Outdoor Dry-bulb temperature 35°C
Wet-bulb temperature 24°C
Heating: Indoor Dry-bulb temperature 20°C
Outdoor Dry-bulb temperature 7°C
Wet-bulb temperature 6°C
Refrigerant piping length (one way): 5 m
SPECIFICATION
4
OBH839A
Содержание MUZ-AP20VG
Страница 8: ...8 Unit mm MUZ AP20VG OUTLINES AND DIMENSIONS 6 OBH839A ...
Страница 9: ...9 WIRING DIAGRAM 7 MUZ AP20VG E1 ET1 ER1 OBH839A ...