No. Symptom
Indication
Abnormal point / Condition
Condition
Remedy
LED1
(Red)
LED2
(Yellow)
20
Outdoor
unit oper-
ates.
Once Lighting
Primary current protection
The input current exceeds 15 A.
These symptoms do not mean any abnormality of
the product, but check the following points.
Check if indoor
fi
lters are clogged.
Check if refrigerant is short.
Check if indoor/outdoor unit air circulation is short
cycled.
•
•
•
•
Secondary current protection The current of the compressor exceeds 15 A.
21
Twice Lighting
High-pressure protection
(MUZ)
The indoor gas pipe temperature exceeds 113°F (45°C) dur-
ing heating.
Defrosting in cooling
The indoor gas pipe temperature falls 37°F (3°C) or below
during cooling.
22
3 times
Lighting
Discharge temperature protec-
tion
The discharge temperature exceeds 212°F (100°C) during
operation.
Check refrigerant circuit and refrigerant amount.
Refer to 10-5. "Check of LEV".
Refer to 10-5. "Check of outdoor thermistors".
•
•
•
23
4 times
Lighting
Low discharge temperature
protection
The frequency of the compressor is kept 80 Hz or more and
the discharge temperature is kept under 102°F (39°C) for
more than 20 minutes.
Refer to 10-5. "Check of LEV".
Check refrigerant circuit and refrigerant amount.
•
•
24
5 times
Lighting
Cooling high-pressure protec-
tion
The outdoor heat exchanger temperature exceeds 136°F (58
°C) during operation.
This symptom does not mean any abnormality of
the product, but check the following points.
Check if indoor
fi
lters are clogged.
Check if refrigerant is short.
Check if indoor/outdoor unit air circulation is short
cycled.
•
•
•
•
25
Outdoor
unit oper-
ates
9 times
Lighting Inverter check mode
The unit is operated with emergency operation switch.
–
26
Lighting Lighting Normal
–
–