4

FLARED CONNECTIONS

• This unit has flared connections on both indoor and outdoor sides.
• Refrigerant pipes are used to connect the indoor and outdoor units as shown in the figure below.
• Insulate both refrigerant and drain piping completely to prevent condensation.

Limits

Pipe length

15 m max.

Height difference

5 m max.

No. of bends

10 max.

• Refrigerant adjustment … If pipe length exceeds 7 m, additional refrigerant (R-22) charge is required.

(The outdoor unit is charged with refrigerant for 7 m pipe length.)

Up to 7 m

No additional charge required

Pipe length

Exceeding 7 m

Additional charge required

Refrigerant

MCF TYPE

: 15 g/m

to be added

MCFH TYPE : 50 g/m

PIPING PREPARATION

• Refrigerant pipes of 3, 5, 7, 10 and 15 m are available as optional items.

1

Table below shows the specifications of pipes commercially available.

Model

Pipe

Outside diameter

Insulation thickness

Insulation material

mm

mm

MCF(H)-13NV

For liquid

6.35

8

For gas

12.7

MCF(H)-18NV

For liquid

6.35

8

Heat resisting foam plastic

For gas

15.88

0.045 specific gravity

MCF-24NV

For liquid

9.52

8

For gas

15.88

2

Ensure that the 2 refrigerant pipes are well insulated to prevent condensation.

3

Refrigerant pipe bending radius must be 100 mm or more.

 Caution:

Using careful insulation of specified thickness. Excessive thickness prevents storage behind the in-
door unit and lack of thickness causes dew drippage.

4-1

A CASE OF SUSPENDING INDOOR UNIT FROM THE CEILING

4-1-(1)

MOUNTING INSTALLATION PLATE FIXING BOLTS

4. INDOOR UNIT INSTALLATION

1. Determine the locations of installation plate fixing bolts.

• Use installation pattern to determine the locations of instal-

lation plate fixing bolts 

J

.

a

Installation pattern

Details are printed on pattern.
Attention:

Surrounding temperature and humidity conditions
may cause paper pattern to shrink or expand.
(Measure dimensions before drilling holes.)

2. Suspension structure (Give site of suspension strong struc-

ture).

Wood structure

• Select tie beam (one-story houses) or second-floor

girder (two story houses) as reinforcement member.

• Use sturdy beams of at least 60 mm square for beam

pitch of 900 mm or less or of at least 90 mm square for
beam pitch of 900-1800 mm.

a

Pitch

b

Ceiling

c

Rafter

d

Bracket

e

Roof beam

Ferroconcrete Structures

• Secure installation plate fixing bolts 

J

 as shown at the

right or use angle-stock bracework to install installa-
tion plate fixing bolts 

J

.

f

Use inserts rated at 100-150 kg each

g

Steel reinforcing rod

J

Installation plate fixing bolts

3. Installation plate fixing bolts pitch.

• Use the installation plate fixing bolts 

J

 M10 (

×

 4 procure

locally).

a

Indoor unit

b

Air outlet

1

Installation plate

• Projecting dimension of installation fixing bolts 

J

 from hori-

zontal base line against which you fix installation plate 

1

as within at the right.

c

Horizontal base line

1

Installation plate

J

Installation fixing bolts

a

*Remove installation pattern after installation.

b

c

d

e

a

a

b

a

1

300 mm

150 mm

1065 mm

f

J

g

c

J

1

max. 40 mm

REFRIGERANT AND DRAINAGE PIPE SIZES

Model

MCF(H)-13NV

MCF(H)-18NV

MCF-24NV

Refrigerant pipe

Liquid

OD ø6.35 (1/4”)

OD ø9.52 (3/8”)

Gas

OD ø12.7 (1/2”)

OD ø15.88 (5/8”)

Drainage pipe

Hard PVC pipe : OD ø26 (1”)

OPTIONAL PARTS

Model

MCF(H)-13NV

MCF(H)-18NV

MCF-24NV

Air cleaning filter

MAC-1200FT

Deodorizing filter

MAC-1700DF

Содержание MUCF-13NV

Страница 1: ...SORIES 3 4 INDOOR UNIT INSTALLATION 4 5 OUTDOOR UNIT INSTALLATION 9 6 INDOOR OUTDOOR UNIT CONNECTION FINISHING AND TEST RUN 10 7 FOR MOVEMENT AND MAINTENANCE 12 Floor and CeilingType Air Conditioner MCF 13NV 18NV 24NV Series MCFH 13NV 18NV Series FLARE CONNECTION TYPE English Deutsch Français Nederlands Español Italiano ÏÏËÓÈÎ Português Dansk Svenska Türkçe Русский ...

Страница 2: ...p from the unit and household goods could be wet and damaged Please provide an exclusive circuit for the air conditioner and do not connect other electrical appliances to it Please report to your supply authority or obtain their consent before connecting this equipment to the power supply system Be sure to read THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY before installing the air conditione...

Страница 3: ...unit MUCFH type A Drain socket 1 B Drain cap ø33 2 C Drain cap ø16 only MUCFH 18NV 1 PARTS TO BE PROVIDED AT YOUR SIDE Item Q ty A Refrigerant pipe 1 set B Indoor outdoor connecting wire 1 C Piping tape 1 D Drain pipe PVC pipe OD ø26 1 E Pipe fixing band for refrigerant pipe The quantity depends on the pipe length 2 to 5 F Fixing screw for E The quantity depends on the pipe length 2 to 5 G Drain j...

Страница 4: ...llation plate fixing bolts Use installation pattern to determine the locations of instal lation plate fixing bolts J a Installation pattern Details are printed on pattern Attention Surrounding temperature and humidity conditions may cause paper pattern to shrink or expand Measure dimensions before drilling holes 2 Suspension structure Give site of suspension strong struc ture Wood structure Select...

Страница 5: ...wn in Fig 2 Be sure to confirm letters FRONT in installation plates 1 set FRONT side to air outlet side of indoor unit a FRONT 1 Installation plate 2 In case of fixing installation plates 1 above the ceiling put installation plates fixing bolt through a nut a spring washer the installation plate a spring washer and double nut Fig 3 In case of fixing installation plates 1 forward the ceiling direct...

Страница 6: ...irm the dimensions as below 4 2 4 FRONT GRILLE REMOVAL See to 4 1 4 Page 5 4 2 5 OPENING KNOCKOUT HOLE See to 4 1 5 Page 5 Installation pattern Remove installation pattern after installing Horizontal base line Hole for refrigerant and drain pipe in the case of downward piping Hole for refrigerant and drain pipe in the case of rear piping Installation plate 1 FRONT 4 2 6 FIXING UNIT TO INSTALLATION...

Страница 7: ...ward 2 Be sure to fix the cable by cable clamp 3 Replace the terminal cover securely Warning Attach the electrical part cover securely If it is attached incorrectly it could result in a fire an elec tric shock due to dust water etc Use the specified indoor outdoor unit connecting wire to connect the indoor and outdoor units and fix the wire to the terminal block securely so that no stress is appli...

Страница 8: ...nward inclination of 1 100 or more d Air bleeder e Do not raise f Odor trap g The end of drain hose is immersed in water h Gap from the ground level is 50 mm or less i Sewage ditch b c a 0 75 m 1 5 m i g h f e d Be sure to connect drain pipe D to drain joint bush se curely as shown in the right Be sure to pass drain pipe D with drain pipe cover through knockout hole on bottom surface so as to keep...

Страница 9: ...g 45 mm 15 mm Loosen terminal screw Terminal block Lead wire Connection details Caution Be careful not to make mis wiring Firmly tighten the terminal screws to prevent them from loosening After tightening pull the wires lightly to confirm that they do not move If the connecting wire is incorrectly connected to the terminal block the unit does not operate nor mally Warning Be sure to attach the ser...

Страница 10: ...b a 6 INDOOR OUTDOOR UNIT CONNECTION FINISHING AND TEST RUN 6 2 PIPE CONNECTION 1 Indoor unit connection Connect both liquid and gas piping to the indoor unit Apply a thin coat of refrigerant oil on the seat surface of pipe For connection first align the center then hand tighten the first 3 to 4 turns of flare nut Use tightening torque table below as a guideline for the indoor unit side union join...

Страница 11: ...sed by commands from the remote control Once the compressor stops the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner EMERGENCY OPERATION switch 6 3 PURGING PROCEDURES LEAK TEST PURGING PROCEDURES Connect the refrigerant pipes both the liquid pipe and the gas pipe between the indoor and the outdoor unit Remove the service port cap ...

Страница 12: ...on mode set temperature and the fan speed are memorized by the indoor electronic control P C board The auto restart function sets to work the moment the power has restored after power failure then the unit will restart automatically If the unit is operated in I FEEL CONTROL mode before power failure the operation is not memorized In I FEEL CONTROL mode the operation is decided by the initial room ...

Страница 13: ... J24532 CABLE MELCO TOKYO This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC ...