1-2. SELECTING THE INSTALLATION LOCATION
1-3. SPECIFICATIONS
Model
Power supply *1
Wire speci
¿
cations
Pipe size
(thickness *3, *4)
Maximum amount of
refrigerant charge *7
Indoor unit
Outdoor unit
Rated Voltage
Frequency
%
reaker
capacity
Power supply *2
Indoor/outdoor
connecting wire *2
Gas / Liquid
MSZ
LN25VG
MSZ
LN35VG
MUZ
LN25VG(
+
Z)
MUZ
LN35VG
230 V
50
+
z
10 A
3
core
1
0 mm
ð
4
core
1
0 mm
ð
ø9
52 / 6
35 mm
(0
8 mm)
1260 g
MSZ
LN35VG
MUZ
LN35VG
+
Z
12 A
3
core
1
5 mm
ð
MSZ
LN50VG
MUZ
LN50VG
16 A
3
core
2
0 mm
ð
1510 g
MUZ
LN50VG
+
Z
1910 g
MSZ
LN60VG
MUZ
LN60VG
ø12
7 / 6
35 mm
(0
8 mm)
Note:
When operating the air conditioner in low outside temperature,
E
e sure to follow the
instructions descri
E
ed
E
elow
Never install the outdoor unit in a place where its air inlet/outlet side may
E
e exposed
directly to wind
To prevent exposure to wind, install the outdoor unit with its air inlet side facing the
wall
To prevent exposure to wind, it is recommended to install a
E
af
À
e
E
oard on the air outlet
side of the outdoor unit
Avoid the following places for installation where air conditioner trou
E
le is lia
E
le to occur
Where
À
amma
E
le gas could leak
Where there is much machine oil
Where oil is splashed or where the area is
¿
lled with oily smoke (such as cooking areas
and factories, in which the properties of plastic could
E
e changed and damaged)
Salty places such as the seaside
Where
sul
¿
de gas is generated such as hot spring, sewage, waste water
Where there is high
frequency or wireless equipment
Where there is emission of high levels of VOCs, including phthalate compounds,
formaldehyde, etc
, which may cause chemical cracking
The appliance shall
E
e stored so as to prevent mechanical damage from occurring
Where
air
À
ow is not
E
locked
Where cool (or warm) air spreads over the entire room
Rigid wall without vi
E
ration
Where it is not exposed to direct sunshine
'
o not expose to direct sunshine also during
the period following unpacking to
E
efore use
Where easily drained
At a distance 1 m or more away from your TV and radio
Operation of the air conditioner
may interfere with radio or TV reception
An ampli
¿
er may
E
e required for the affected
device
In a place as far away as possi
E
le from
À
uorescent and incandescent lights
In order to
make the infrared remote control operate the air conditioner normally
The heat from the
lights may cause deformation or the ultraviolet may cause deterioration
Where the air
¿
lter can
E
e removed and replaced easily
Where it is away from the other heat or steam source
Please ensure that the Router supports the WPA2
AES encryption setting
E
efore com
mencement of the installation of this indoor unit equipped with the Wi
Fi interface
The End user should read and accept the terms and conditions of the Wi
Fi service
E
efore
commencement of the installation of this indoor unit equipped with the Wi
Fi interface
This indoor unit equipped with the Wi
Fi interface should not
E
e installed and connected to
any Mitsu
E
ishi Electric system which is to provide application critical cooling or heating
REMOTE CONTROLLER
Where it is easy to operate and easily visi
E
le
Where children cannot touch it
Select a position a
E
out 1
2 m a
E
ove the
À
oor and check that signals from the remote
controller are surely received
E
y the indoor unit from that position (
µE
eep
¶
or
µE
eep
E
eep
¶
receiving tone sounds)
After that, attach remote controller holder to a pillar or wall and
install wireless remote controller
Note:
In rooms where inverter type
À
uorescent lamps are used, the signal from the wireless
remote controller may not
E
e received
OUTDOOR UNIT
Where it is not exposed to strong wind
If the outdoor unit is exposed to a wind during
defrosting, the defrosting time will
E
e longer
Where
air
À
ow is good and dustless
Where rain or direct sunlight can
E
e avoided as much as possi
E
le
Where
neigh
E
ours are not annoyed
E
y operation sound or hot (or cool) air
Where rigid wall or support is availa
E
le to prevent the increase of operation sound or
vi
E
ration
Where there is no risk of com
E
usti
E
le gas leakage
When installing the unit at a high level,
E
e sure to secure the unit legs
Where it is at least 3 m away from the antenna of TV set or radio
Operation of the air
conditioner may interfere with radio or TV reception in areas where reception is weak
An ampli
¿
er may
E
e required for the affected device
Install the unit horizontally
Please install it in an area not affected
E
y snowfall or
E
lowing snow
In areas with heavy
snow, please install a canopy, a pedestal and/or some
E
af
À
e
E
oards
Note:
It is advisa
E
le to make a piping loop near outdoor unit so as to reduce vi
E
ration transmit
ted from there
(LN25, 35, 50/50
+
Z, 60)
Pipe length and height difference
Max
pipe length
20/30 m
Max
height difference
12/15 m
Max
num
E
er of
E
ends *5, *6
10
Refrigerant adjustment A *7
20 g/m
Insulation thickness *8, *9
8 mm
INDOOR UNIT
*1 Connect to the power switch which has a gap of 3 mm or more when open to interrupt the source power phase
(When the
power switch is shut off, it must interrupt all phases
)
*2 Use wires in conformity with design 60245 IEC 57
*3 Never use pipes with thickness less than speci
¿
ed
The pressure resistance will
E
e insuf
¿
cient
*4 Use a copper pipe or a copper
alloy seamless pipe
*5
%
e careful not to crush or
E
end the pipe during pipe
E
ending
*6 Refrigerant pipe
E
ending radius must
E
e 100 mm or more
*7 If pipe length exceeds 7 m, additional refrigerant (R32) charge is required
(No additional charge is required for pipe length less
than 7 m
)
Additional refrigerant = A × (pipe length (m) – 7)
*8 Insulation material
+
eat resisting foam plastic 0
045 speci
¿
c gravity
*9
%
e sure to use the insulation of speci
¿
ed thickness
Excessive thickness may cause incorrect installation of the indoor unit and
insuf
¿
cient thickness may cause dew drippage
WARNING
The unit should be installed in rooms which have the
À
oor space speci
¿
ed below.
MSZ-LN25/35VG: 1.7 m²
MSZ-LN50VG: 2.5 m²
MSZ-LN50VGHZ/60VG: 3.9 m²
CAUTION
(Could lead to serious injury in particular environments when operated incorrectly
)
■
Install an earth leakage breaker depending on the
installation place.
If an earth leakage
E
reaker is not installed, it could cause
electric shock
■
Perform the drainage/piping work securely according
to the installation manual.
If there is defect in the drainage/piping work, water could
drop from the unit, soaking and damaging household
goods
■
Do not touch the air inlet or the aluminum
¿
ns of the
outdoor unit.
This could cause injury
■
Do not install the outdoor unit where small animals
may live.
If small animals enter and touch the electric parts inside
the unit, it could cause a malfunction, smoke emission,
or
¿
re
Also, advise user to keep the area around the unit
clean
■
Do not operate the air conditioner during interior
construction and
¿
nishing work, or while waxing the
À
oor.
%
efore operating the air conditioner, ventilate the room
well after such work is performed
Otherwise, it may cause
volatile elements to adhere inside the air conditioner,
resulting in water leakage or scattering of dew
■
To prevent damage from static electricity, touch a
nearby metal body to discharge static electricity from
yourself before touching the indoor unit equipped with
the Wi-Fi interface.
Static electricity from the human
E
ody may damage the
Wi
Fi interface unit
■
Do not use the indoor unit equipped with the Wi-Fi
interface nearby other wireless devices, microwaves,
cordless phones, or facsimiles.
It can cause malfunctions