29
OPERATION INDICATOR
(POWER)
(AIR PURIFYING)
No.
Abnormal
point
Operation indicator lamp
Symptom
Condition
Remedy
1
MXZ type
Operation
mode
setting
• AIR PURIFYING lamp fl ash.
2.5-second OFF
• POWER lamp is lit.
Outdoor unit
operates but
indoor unit does
not operate.
The operation mode of the each indoor unit is
differently set to COOL (includes DRY, FAN)
and HEAT at the same time, the operation
mode of the indoor unit that has operated at
fi rst has the priority.
• Unify the operation mode.
Refer to outdoor unit service
manual.
10-5. TROUBLE CRITERION OF MAIN PARTS
MSZ-LN18VGW
MSZ-LN25VGW
MSZ-LN35VGW
MSZ-LN50VGW
MSZ-LN60VGW
MSZ-LN18VGV
MSZ-LN25VGV
MSZ-LN35VGV
MSZ-LN50VGV
MSZ-LN60VGV
MSZ-LN18VGB
MSZ-LN25VGB
MSZ-LN35VGB
MSZ-LN50VGB
MSZ-LN60VGB
MSZ-LN18VGR
MSZ-LN25VGR
MSZ-LN35VGR
MSZ-LN50VGR
MSZ-LN60VGR
Part name
Check method and criterion
Figure
Room temperature
thermistor (RT11)
Indoor coil thermistor
(RT12, RT13)
Measure the resistance with a tester.
Refer to 10-7. "Test point diagram and voltage", "Indoor electronic control
P.C. board", for the chart of thermistor.
Indoor fan motor (MF)
Check 10-6. "Check of indoor fan motor".
Vane motor (MV1)
(HORIZONTAL)
Measure the resistance between the terminals with a tester.
(Temperature: 10 - 30°C)
Color of the lead wire
Normal
RED - SKY
262 - 328
Ω
Vane motor (MV2)
(VERTICAL)
Measure the resistance between the terminals with a tester.
(Temperature: 10 - 30°C)
Color of the lead wire
Normal
RED - SKY
219 - 273
Ω
i-see SENSOR MOTOR
(MT)
Measure the resistance between the terminals with a tester.
(Temperature: 10 - 30°C)
Color of the lead wire
Normal
RED - BLK
262 - 328
Ω
AIR PURIFYING power
Check 10-6. .
SKY
SKY
RED
SKY
SKY
ROTOR
OPERATION INDICATOR
(POWER)
(AIR PURIFYING)
No.
Abnormal
point
Operation indicator lamp
Symptom
Condition
Remedy
1
AIR
PURIFYING
power
control
AIR PURIFYING lamp fl ashes.
2.5-second OFF
Indoor unit and
outdoor unit do
not operate.
When AIR PURIFYING power cannot be
turned OFF even if the AIR PURIFYING
operation is turned OFF by remote controller.
• Refer to 10-6.
"Check of AIR
PURIFYING power".
Lit
Blinking
Not lit
Lit
Blinking
Not lit
SKY
SKY
RED
SKY
SKY
ROTOR
BLK
BLK
RED
BLK
BLK
ROTOR
OBH766B