23
A Check of indoor fan motor
10-6. TROUBLESHOOTING FLOW
The indoor fan motor error has occurred, and the indoor fan does not operate.
Turn OFF the power supply.
Is there any foreign matter that interferes
the rotation of the line flow fan?
Yes
Yes
Yes
No
Remove the foreign matter and
adjust the line flow fan.
Pay enough attention to the high voltage on the fan motor connector CN211.
Turn ON the power supply, wait 5 seconds or more, and then press
EMERGENCY OPERATION switch.
Measure the supply voltage as follows within 12 seconds after EMER-
GENCY OPERATION switch is pressed.
If more than 12 seconds passes, turn OFF the power supply and turn it
ON again, then measure the voltage.
<Indoor electronic control P.C. board>
1. Measure the voltage between CN211 (+) and (–).
2. Measure the voltage between CN211 (+) and (–).
If more than 12 seconds
passes after EMERGENCY
OPERATION switch is
pressed, the voltage meas-
ured at 2. above goes 0 V
DC although the indoor P.C.
board is normal.
Does the voltage between CN211
(+) and (–) on the indoor electronic
control P.C. board rise to the range of
3 to 6 V DC within 12 seconds after
EMERGENCY OPERATION switch is
pressed?
Replace the indoor fan motor.
No
The indoor fan motor error has occurred, and the indoor fan repeats "12-second ON and 30-second OFF" 3 times, and then stops.
Measure the voltage between CN211
(+) and (–) while the fan motor is
rotating.
Is it unchanged holding 0
or 15 V DC?
No
(Changed)
Yes
(Unchanged)
Replace the indoor fan motor.
Is there 325 V DC
between CN211 (+)
and (–) ?
Replace the indoor electronic
control P.C. board.
Replace the indoor electronic
control P.C. board.
Replace the indoor electronic
control P.C. board.
No
<HR25/35/42/50VF>
OBH822B