background image

4-1. PURGING PROCEDURES AND LEAK TEST

1) Remove service port cap of stop valve on the side of the outdoor unit gas pipe. (The 

stop valves are fully closed and covered in caps in initial state.)

2) Connect gauge manifold valve and vacuum pump to service port of stop valve on the 

gas pipe side of the outdoor unit.

4-2. TEST RUN

1) Insert power supply plug into the power outlet and/or 

turn on the breaker. Check that all LED lamps are not lit. 
If they are blinking, check that the horizontal vane is in-
stalled correctly. Refer to operating instructions for details.

2) Press the E.O. SW once for COOL, and twice for HEAT 

operation. Test run will be performed for 30 minutes. If 
the upper lamp of the operation indicator blinks every 0.5 
seconds, inspect the indoor/outdoor unit connecting wire 
(A) for mis-wiring.  After the test run, emergency mode (set 
temperature 24ºC) will start.

3) To stop operation, press the E.O. SW several times until 

all LED lamps turn off. Refer to operating instructions for 
details. 

Checking the remote (infrared) signal reception

Press the ON/OFF button on the remote controller (6) and check that an electronic sound 
is heard from the indoor unit. Press the ON/OFF button again to turn the air conditioner 
off.
•  Once the compressor stops, the restart preventive device operates so the compressor 

will not operate for 3 minutes to protect the air conditioner.

4-3. AUTO RESTART FUNCTION

This product is equipped with an auto restart function. When the power supply is stopped 
during operation, such as during blackouts, the function automatically starts operation in 
the previous setting once the power supply is resumed. (Refer to the operating instruc-
tions for details.) 

4-4. EXPLANATION TO THE USER

•  Using the OPERATING INSTRUCTIONS, explain to the user how to use the air condi-

tioner (how to use the remote controller, how to remove the air filters, how to remove 
or put the remote controller in the remote controller holder, how to clean, precautions 
for operation, etc.)

•  Recommend the user to read the OPERATING INSTRUCTIONS carefully.

5-1. REMOVING AND INSTALLING THE PANEL ASSEMBLY

5-3. PUMPING DOWN

When relocating or disposing of the air conditioner, pump down the system following the 
procedure below so that no refrigerant is released into the atmosphere.
1) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe 

side of the outdoor unit.

2) Fully close the stop valve on the liquid pipe side of the outdoor unit.
3) Close the stop valve on the gas pipe side of the outdoor unit almost completely so that 

it can be easily closed fully when the pressure gauge shows 0 MPa [Gauge] (0 kgf/
cm

2

).

4) Start the emergency COOL operation.
  To start the emergency operation in COOL mode, disconnect the power supply plug 

and/or turn off the breaker. After 15 seconds, connect the power supply plug and/or 
turn on the breaker, and then press the E.O. SW once. (The emergency COOL 
operation can be performed continuously for up to 30 minutes.)

5) Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure 

gauge shows 0.05 to 0 MPa [Gauge] (approx. 0.5 to 0 kgf/cm

2

).

6) Stop the emergency COOL operation.
  Press the E.O. SW several times until all LED lamps turn off. Refer to operating in-

structions for details.

5-2. REMOVING THE INDOOR UNIT

Remove the bottom of the indoor unit from the installation 
plate.
When releasing the corner part, release both left and right 
bottom corner part of indoor unit and pull it downward and 
forward as shown in the figure on the right.

If the above method cannot be used

Remove the panel. Then, insert hexagonal wrenches into the square holes on the left and 
right sides of the unit and push them up as shown in the following figure. The bottom of 
the indoor unit lowers and releases the hooks.

Removal procedure

1) Remove the 2 screws which fix the panel assem-

bly.

2) Remove the panel assembly. Be sure to remove 

its bottom end first.

Installation procedure

1) Install the panel assembly following the removal 

procedure in reverse. 

2) Be sure to press the positions as indicated by the 

arrows in order to attach the assembly completely 
to the unit.

Stop valve for 
GAS

Stop valve cap
(Torque 19.6 to 
29.4 N•m, 200  
to 300 kgf▪cm)

Vacuum pump (or the vacuum 
pump with the function to 
prevent the back flow)

Gauge manifold valve 
(for R410A)

Compound pressure gauge 
(for R410A)

0.101 MPa  

(

760 mmHg)

Handle 
Low

Handle High

Adapter for pre-
venting the back 
flow

Charge hose 
(for R410A)

*Close

*Open

Hexagonal wrench

Precautions when using the control valve When attaching the control valve 

to the service port, valve core may 
deform or loosen if excess pressure 
is applied. This may cause gas leak.

Service port

Charge hose 

Body

Close

Open

Control valve

A

When attaching the control valve to 
the service port, make sure that the 
valve core is in closed position, and 
then tighten part A. Do not tighten 
part A or turn the body when valve 
core is in open position.

Service port cap
(Torque 13.7 to 
17.7 N•m, 140 to 
180 kgf•cm)

*4 to 5 turns

3) Run the vacuum pump. (Vacuumize for more than 15 minutes.)
4) Check the vacuum with gauge manifold valve, then close gauge manifold valve, and 

stop the vacuum pump.

5) Leave as it is for one or two minutes. Make sure pointer gauge manifold valve remains 

in the same position. Confirm that pressure gauge shows –0.101 MPa [Gauge] (–760 
mmHg).

6) Remove gauge manifold valve quickly from service port of stop valve.
7) After refrigerant pipes are connected and evacuated, fully open all stop valves on both 

sides of gas pipe and liquid pipe. Operating without fully opening lowers the perform-
ance and this causes trouble.

8) Refer to 1-3., and charge the prescribed amount of refrigerant if needed. Be sure to 

charge slowly with liquid refrigerant. Otherwise, composition of the refrigerant in the 
system may be changed and affect performance of the air conditioner.

9) Tighten cap of service port to obtain the initial status.
10) Leak test

Stop valve 
for LIQUID

Caution:

•  After test run or remote signal reception check, turn off the unit with the E.O. SW or 

the remote controller before turning off the power supply. Not doing so will cause the 
unit to start operation automatically when power supply is resumed.

To the user

•  After installing the unit, make sure to explain the user about auto restart function. 
•  If auto restart function is unnecessary, it can be deactivated. Consult the service 

representative to deactivate the function. Refer to the service manual for details.

Push

Lower

Square hole

4.  PURGING PROCEDURES, LEAK TEST, AND TEST RUN

Pressure gauge
(for R410A)

5. RELOCATION AND MAINTENANCE

Emergency  
operation switch
(E.O. SW)

When pumping down the refrigerant, stop the compressor before disconnecting 
the refrigerant pipes. The compressor may burst if air etc. get into it.

 WARNING

HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 
100-8310, JAPAN

Содержание MSZ-GE22VAD

Страница 1: ...e refrigerant leakage N The unit shall be installed in accordance with na tional wiring regulations N Install an earth leakage breaker depending on the installation place If an earth leakage breaker is not installed it could cause electric shock N Perform the drainage piping work securely accord ing to the installation manual If there is defect in the drainage piping work water could drop from the...

Страница 2: ...ccording to the dimension for new refrigerant Appearance of the outdoor unit may differ from some models Wall Outdoor side ø 65 mm 5 7 mm 4 Loosen terminal screw and connect first the earth wire then indoor outdoor unit con necting wire A to the terminal block Be careful not to make mis wiring Fix the wire to the terminal block securely so that no part of its core is appeared and no external force ...

Страница 3: ...n hose to the hard vinyl chloride pipe be sure to insert it securely into the pipe Fig 3 Do not make drain piping as shown below Do not raise Accumulated drain water Air Waving Water leakage Water leakage Water leakage Tip of drain hose dipped in water Ditch At least 50 mm gap Cut off in case of right piping Cut off in case of downward piping Copper pipe Good Tilted Uneven Burred No good Fig 1 Fig...

Страница 4: ...or unit from the installation plate When releasing the corner part release both left and right bottom corner part of indoor unit and pull it downward and forward as shown in the figure on the right If the above method cannot be used Remove the panel Then insert hexagonal wrenches into the square holes on the left and right sides of the unit and push them up as shown in the following figure The botto...

Отзывы: