background image

25

 D  How to check miswiring and serial signal error

A

• Reinstall ei-

ther the unit 

or the light  

away from 

each other.

• Attach a 

fi

 lter 

on remote 

control 

receiving 

section of 

the indoor 

unit.

• Turn OFF inverter-controlled lighting 

equipment.

• Turn OFF the power supply and then 

turn ON again.

• Press the emergency operation switch.

After the relay 

52C is turned on 

3 minutes later, is 

miswiring or the 

serial signal error 

indicated?

No

B

Yes

1 Make sure that the wiring is correct. If the pro-

cedure is performed without correcting miswir-
ing, it may lead to damage to the P.C. board. 

3 Be sure to release the failure-mode recall function after checking.

Turn OFF the power supply.

Is there rated voltage in the 
power supply?

Yes

No

1. Turn ON the power supply.
2. Press the emergency operation switch.

Check the power supply.

Has the relay 52C been turned on 3 minuets later ?
[The relay will be turned on in 3 to 7 seconds by 
bridging the timer short mode point (Refer to 10-7.).]

Is there any miswiring, poor 
contact, or wire disconnec-
tion of the indoor/outdoor 
connecting wire?

Yes

No

Correct them.

No

Yes

Aim the remote controller at the indoor unit, and press 
STOP/OPERATE/ (OFF/ON) button. The relay 52C will 
be turned on, and the outdoor unit will be energized.

Is the rated supply voltage applied 
between the S1 and S2 on the 
outdoor terminal block? (Check of 
supply voltage) 

No

Is there any problem in the 

indoor/outdoor connecting wire, 

such as the damage of the wire, 

intermediate connection, poor 

contact with the terminal block?

Yes

Replace 

the indoor/

outdoor con-

necting wire.

No

Replace the indoor electronic control 
P.C. board.   3

Is there approximately 250 VDC – 370 
VDC between DB61 (+) and DB61 
(–) on the inverter P.C. board in the 
outdoor unit? (Voltage check of the 
inverter P.C. board in the outdoor unit) 

No

Replace the 

inverter P.C. 

board in the 

outdoor unit.  2

Yes

Yes

Does the LED on the inverter P.C. 

board in the outdoor unit repeat 

"3.6-second-OFF and 0.8-second-

ON quick blinking" for 3 minutes 

after the outdoor unit is energized? 

(Check the blinking pattern within 3 

minutes after LED is turned on. Af-

ter 3 minutes, LED will blink 6 times 

whether the inverter P.C. board in 

the outdoor unit is normal or not.)

No

Replace the 

inverter P.C. 

board in the 

outdoor unit.  2

Yes

A

2 Be careful of 140 

VDC – 280 VDC 
residual charge in 
the capacitor on the 
main inverter circuit.

B

Turn OFF the power supply. Make sure again that the 

indoor/outdoor connecting wire is correctly connected. 

With the indoor/outdoor connecting wire connected, bridge 

between S2 and S3 on the outdoor terminal block.  1

<Preparation of the remote controller>

 While pressing both OPERATION SELECT button and 

TOO COOL button on the remote controller at the same 

time, press RESET button.

 First, release RESET button. 

  Hold down the other 2 buttons for another 3 seconds. 

Make sure that the indicators on the LCD screen shown in 

the right 

fi

 gure are all displayed. Then release the buttons.

  (Setting up the failure mode recall function)

Indication of miswiring

Indication of serial signal error

OPERATION 
INDICATOR lamp

Continuous blinks

Initializing the determination of the power 
receiving system

The microprocessor may have mistaken the 
unit as a model receiving power from the 
outdoor unit. Follow the procedure below to 
start the determination of the power receiv-
ing system all over again.
1. Hold down the emergency operation 

switch for 30 seconds. (Do not release the 
switch even though a buzzer beeps once 
in about 5 seconds. Keep holding down 
the switch until a buzzer beeps again for 
1 second after 30 seconds. Figure 1) 

2. Turn off the power supply.
3. Wait for about 30 seconds.
4. Turn on the power supply.
5. Press the emergency operation switch.
6. The relay 52C will be turned on in 3 min-

utes.

Has the miswiring or the serial error 
been indicated?

Yes

No

ON

OFF

Buzzer

0.5-second

1-second

ON

OFF

Emergency 
operation switch

30-second

ON

OFF

5-second

Beeps

Beeps

Beeps

Figure 1

OBH750

Содержание MSZ-DM25VA

Страница 1: ...IAGRAM 9 8 SERVICE FUNCTIONS 10 9 MICROPROCESSOR CONTROL 12 10 TROUBLESHOOTING 16 11 DISASSEMBLY INSTRUCTIONS 28 Outdoor unit service manual MUZ DM VA Series OBH751 MXZ DM VA Series OBH739 MSZ DM25VA MSZ DM35VA INDOOR UNIT Models MSZ DM25VA E1 ER1 MSZ DM35VA E1 ER1 SERVICE MANUAL NOTE RoHS compliant products have G mark on the spec name plate No OBH750 PARTS CATALOG OBB750 ...

Страница 2: ...h the refrigerant Do not touch the hot or cold areas in the refrigeration cycle When the repair or the inspection of the circuit needs to be done without turning off the power exercise great caution not to touch the live parts Use the specified refrigerant only Never use any refrigerant other than that specified Doing so may cause a burst an explosion or fire when the unit is being used serviced o...

Страница 3: ...3 1 TECHNICAL CHANGES MSZ DM25VA E1 ER1 MSZ DM35VA E1 ER1 1 New model OBH750 ...

Страница 4: ...Battery AAA for remote controller 2 Air cleaning filter Silver ionized air purifer filter 1 2 PART NAMES AND FUNCTIONS Operation indicator lamp Remote control receiving section Horizontal vane Air inlet Air lter Front panel Air outlet Heat exchanger Emergency operation switch Remote controller Air cleaning lter Silver ionized air purifier filter Display section OBH750 ...

Страница 5: ...Med 330 Low 210 Sound level Cooling Super High dB A 43 45 High 37 38 Med 30 31 Low 22 Heating Super High dB A 43 44 High 37 Med 30 Low 23 Fan speed Cooling Super High rpm 1 080 1 200 High 880 930 Med 710 730 Low 550 Heating Super High rpm 1 120 1 150 High 900 Med 710 Low 520 Fan speed regulator 4 Remote controller model RH16A NOTE Test conditions are based on ISO 5151 Cooling Indoor Dry bulb tempe...

Страница 6: ...10 MSZ DM25VA INDOOR UNIT WALL MICROPHONE 0 8m 1m 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 NC 60 NC 50 NC 40 NC 30 NC 20 NC 70 OCTAVE BAND SOUND PRESSURE LEVEL dB re 0 0002 MICRO BAR BAND CENTER FREQUENCIES Hz COOLING FUNCTION SPL dB A LINE Super High FAN SPEED HEATING Test conditions Cooling Dry bulb temperature 27 C Wet bulb temperature 19 C Heating Dry bulb temperature 20 C...

Страница 7: ...n Ø9 52 Drain hose Insulation Ø28 Connected part Ø16 O D 232 5 69 41 799 785 7 290 120 630 49 57 80 42 43 69 57 42 7 103 130 100 5 7 225 225 80 5 80 5 61 5 59 5 340 338 41 42 249 248 21 5 3 167 157 207 5 206 5 172 14 46 Air in Installation plate Piping Drain hose Air out 11 26 Oblong hole 11 20 Oblong hole Installation plate Indoor unit Wall hole Ø65 132 56 18 OBH750 ...

Страница 8: ...8 MSZ DM25VA E1 ER1 MSZ DM35VA E1 ER1 6 WIRING DIAGRAM OBH750 ...

Страница 9: ...ure thermistor RT11 Flared connection Refrigerant flow in cooling Refrigerant flow in heating Refrigerant pipe ø9 52 with heat insulator Refrigerant pipe ø6 35 with heat insulator Indoor coil thermistor RT12 Indoor coil thermistor RT13 Unit mm 7 REFRIGERANT SYSTEM DIAGRAM OBH750 ...

Страница 10: ...t No 3 unit Solder J2 Same as at left No 4 unit Cut J1 and solder J2 How to set the remote controller exclusively for particular indoor unit After you turn the breaker ON the first remote controller that sends the signal to the indoor unit will be regarded as the remote controller for the indoor unit The indoor unit will only accept the signal from the remote controller that has been assigned to t...

Страница 11: ...Therefore the special countermeasures are required to prevent the main voltage drop or the rush of the starting current by adding to the system that allows the units to start one by one JR77 Indoor electronic control P C board CN10A CN111 CN151 CN112 CN110 8 3 AUTO RESTART FUNCTION When the indoor unit is controlled with the remote controller the operation mode the set temperature and the fan spee...

Страница 12: ... more away from set temperature The room temperature is approaching the set tem perature About 1 to 2 C from set temperature Standby mode Only during multi system operation Lighted Blinking Not lighted 9 MICROPROCESSOR CONTROL 9 1 COOL OPERATION 1 Press STOP OPERATE OFF ON button OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone 2 Select COOL mode with OPERATION SELECT button 3...

Страница 13: ...rol This mode continues until the temperature of indoor heat exchanger falls 3 Defrosting Defrosting starts when the temperature of outdoor heat exchanger becomes too low The compressor stops once the indoor outdoor fans stop the 4 way valve reverses and the compressor re starts This mode continues until the temperature of outdoor heat exchanger rises or the fixed time passes 3 Positioning To conf...

Страница 14: ...OL mode set temperature is automatically set 2 C higher Also the horizontal vane swings in various cycle SWING operation makes you feel cooler than set temperature So even though the set temperature is higher the air conditioner can keep comfort As a result energy can be saved ECONO COOL operation is cancelled when ECONO COOL button is pressed once again or VANE CONTROL button is pressed or change...

Страница 15: ...an speed shifts to Med The coil frost prevention works even in the test run or the emergency operation In the test run or emergency operation the horizontal vane operates in VANE AUTO mode Emergency operation continues until EMERGENCY OPERATION switch is pressed once or twice or the unit receives any signal from the remote controller In the latter case normal operation will start NOTE Do not press...

Страница 16: ...e replaced This function is equipped to prevent the microcomputer from malfunctioning due to the voltage drop caused by the battery replacement 3 Do not use the leaking batteries Press RESET button with a thin instrument and then use the remote controller Remove the back lid and insert batteries Then reattach the back lid 10 1 CAUTIONS ON TROUBLESHOOTING 1 Before troubleshooting check the followin...

Страница 17: ...ormal Check the blinking pattern and identify the abnormal point by referring to the indoor unit failure mode table Refer to 10 2 2 Make sure to check at least 2 consecutive blinking cycles 2 Releasing the failure mode recall function Release the failure mode recall function by the following procedures Turn OFF the power supply and turn it ON again Press RESET button of the remote controller The o...

Страница 18: ...he main indoor coil ther mistor the sub indoor coil thermistor 10 7 3 time flash 2 5 second OFF Serial signal The serial signal from outdoor unit is not re ceived for a maximum of 6 minutes Refer to 10 6 How to check miswiring and serial signal error 11 time flash 2 5 second OFF Indoor fan motor The rotational frequency feedback signal is not emitted for the 12 seconds after the indoor fan motor i...

Страница 19: ... operation means the operation within 30 minutes after EMERGENCY OPERA TION switch is pressed Refer to outdoor unit service manual Upper lamp Flash on and off at 0 5 sec ond intervals Cause Indoor Outdoor unit Miswiring or trouble of serial signal Upper lamp 2 time flash Cause Indoor unit Trouble of room temperature indoor coil thermistor Upper lamp 3 time flash Cause Indoor unit Trouble of indoor...

Страница 20: ...ctronic control P C board 5 Outdoor power sys tem Upper lamp flashes 5 time flash 2 5 second OFF It consecutively occurs 3 times that the com pressor stops for overcurrent protection or start up failure protection within 1 minute after start up Refer to How to check of in verter compressor Refer to outdoor unit service manual Check the stop valve 6 Outdoor thermistors Upper lamp flashes 6 time fla...

Страница 21: ...ls with a tester Part temperature 10 30 C Color of the lead wire Normal RED BLK 235 255 Ω BLK BLK RED BLK BLK ROTOR OPERATION INDICATOR No Abnormal point Operation indicator lamp Symptom Condition Remedy 1 MXZ type Operation mode setting Upper lamp lights and lower lamp flashes 2 5 second OFF Outdoor unit operates but indoor unit does not operate The operation mode of the each indoor unit is diffe...

Страница 22: ...is pressed the voltage measured at 2 above goes 0 VDC although the indoor P C board is normal Does the voltage between CN211 and on the power P C board rise to the range of 3 to 6 VDC within 12 seconds after EMERGENCY OPERATION switch is pressed Replace the indoor fan motor Yes No The indoor fan motor error has occurred and the indoor fan repeats 12 second ON and 30 second OFF 3 times and then sto...

Страница 23: ...tart type within the range of 1 m 2 Yes No Reinstall the unit away from lights Attach a filter on receiving part Replace the indoor electronic control P C board Including the receiver 1 Look at the image of the signal transmitting section of the remote controller through the monitor of a digital camera or a camera phone It is normal if the LED of the signal transmitting section lights up when the ...

Страница 24: ... and the indoor fan motor Replace the indoor electronic control P C board Measure the resistance of the vane motor coil Refer to 10 5 Short circuit Replace the vane motor and the indoor electronic control P C board 1 The fan motor connector s lead wire is red whereas is black 2 Connect of the tester to fan motor connector s lead wire and to lead wire otherwise the resistance cannot be measured pro...

Страница 25: ... the inverter P C board in the outdoor unit repeat 3 6 second OFF and 0 8 second ON quick blinking for 3 minutes after the outdoor unit is energized Check the blinking pattern within 3 minutes after LED is turned on Af ter 3 minutes LED will blink 6 times whether the inverter P C board in the outdoor unit is normal or not No Replace the inverter P C board in the outdoor unit 2 Yes A 2 Be careful o...

Страница 26: ...he installation condition combination of specific conditions such as antennas or wiring Check the following before asking for service 1 Devices affected by the electromagnetic noise TV sets radios FM AM broadcast shortwave 2 Channel frequency broadcast station affected by the electromagnetic noise 3 Channel frequency broadcast station unaffected by the electromagnetic noise 4 Layout of indoor outd...

Страница 27: ...1 3 6 VDC 15 VDC GND High voltage DC 325 VDC 0 or 15 VDC Indoor terminal block connecting TAB2 Timer short mode point Refer to 8 1 Room temperature thermistor RT11 CN111 Connector to Indoor coil thermistor RT12 RT13 CN112 Vane motor CN151 Connector to indoor power P C board CN10A 12V DC 5V DC To disable Auto restart function cut the Jumper wire to JR77 Refer to 8 3 Emergency operation switch E O S...

Страница 28: ...erminal with this connector has the locking mechanism Slide the sleeve Pull the terminal while pushing the locking lever Hold the sleeve and pull out the terminal slowly Connector Sleeve Locking lever Terminal with locking mechanism Detaching points The terminal which has the locking mechanism can be detached as shown below There are 2 types refer to 1 and 2 of the terminal with locking mechanism ...

Страница 29: ...rical cover and remove the electrical cover 8 Disconnect the following connectors Indoor power P C board CN211 Indoor fan motor CN201 TAB1 TAB2 Terminal block CN20A To the indoor electronic control P C board 9 Remove the upper catch of the electrical box and pull out the electrical box To attach the electrical box pass the wires connecting the indoor power P C board and the indoor electronic contr...

Страница 30: ...the back side of the control P C board holder 5 Unhook the catches of the control P C board holder and open the control P C board holder 6 Remove the indoor electronic control P C board from the control P C board holder 4 Removing the vane motor 1 Remove the panel Refer to 1 Remove the corner box 2 Remove the control P C board holder and the electrical box Refer to 2 3 Pull out the drain hose from...

Страница 31: ...lead wire of the fan motor from the motor band 10 Disengage the hooks of the motor band and remove the motor band Pull out the indoor fan motor 11 Remove the indoor coil thermistor from the heat exchanger Install the indoor coil thermistor in its former position when assembling it 12 Remove the screws fixing the left side of the heat exchanger 13 Lift the heat exchanger and pull out the line flow ...

Страница 32: ...oil thermistor to the clip shape holder shape part the lead wire should point down 1 Set the indoor coil thermistor in the center of the clip shape part 2 Check the marked mounting position 3 Mount the clip shape part Position and procedure for mounting the clip shape part About the same length Copyright 2015 MITSUBISHI ELECTRIC CORPORATION Distributed in Dec 2015 No OBH750 Made in Japan New publi...

Страница 33: ...Related Links Model Number MSZ DM35VA MSZ DM25 35VA Installation Manual JG79B577H01 MSZ DM25 35VA Operation Manual JG79Y073H01 MSZ DM25 35VA Parts Catalogue OBB750 MSZ DM25 35VA Service Manual OBH750 ...

Отзывы: