2. Table of indoor unit failure mode recall function
NOTE
: Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (10-4.).
The upper lamp
of OPERATION
INDICATOR lamp
Abnormal point
(Failure mode)
Condition
Remedy
Not lit
Normal
—
—
1-time blink every
0.5-second
Room temperature
thermistor
The room temperature thermistor short or
open circuit is detected every 8 seconds dur-
ing operation.
Refer to the characteristics of the room temperature
thermistor (10-7.).
2-time blink
2.5-second OFF
Indoor coil
thermistor
The indoor coil thermistor short or open circuit
is detected every 8 seconds during operation.
Refer to the characteristics of the main indoor coil ther-
mistor, the sub indoor coil thermistor (10-7.).
3-time blink
2.5-second OFF
Serial signal
The serial signal from outdoor unit is not re-
ceived for a maximum of 6 minutes.
Refer to 10-6. "How to check miswiring and serial
signal error".
11-time blink
2.5-second OFF
Indoor fan motor
The rotational frequency feedback signal is
not emitted for 12 seconds after the indoor fan
motor is operated.
Refer to 10-6. "Check of indoor fan motor".
12-time blink
2.5-second OFF
Indoor control
system
It cannot properly read data in the nonvolatile
memory of the indoor electronic control P.C.
board.
Replace the indoor electronic control P.C. board.
OBH788C
Содержание MSZ-AP25VG-E1
Страница 13: ...13 MSZ AP50VG E1 EN1 ER1 E2 EN2 MSZ AP50VG ET1 ET2 OBH788C ...
Страница 14: ...14 MSZ AP60VG E1 ER1 E2 MSZ AP71VG E1 ER1 E2 MSZ AP60VG ET1 ET2 MSZ AP71VG ET1 ET2 OBH788C ...
Страница 16: ...16 MSZ AP50VGK E1 EN1 ER1 E2 EN2 MSZ AP50VGK ET1 ET2 OBH788C ...
Страница 17: ...17 MSZ AP60VGK E1 ER1 E2 MSZ AP71VGK E1 ER1 E2 MSZ AP60VGK ET1 ET2 MSZ AP71VGK ET1 ET2 OBH788C ...