EN-3
(G)
(E)
(C)
(4)
(D)
(F)
(5)
(3)
(6)
(7)
(2)
(1)
(B)
(K)
(A)
(I)
ACCESSORIES
Check the following parts before installation.
<Indoor unit>
(1) Installation plate
1
(2)
Installation plate fixing screw 4 × 25 mm
5
(3) Wireless remote controller
1
(4) Felt tape (For left or left-rear piping)
1
(5) Battery (AAA) for (3)
2
(6) Remote controller holder
1
(7) Fixing screw for (5) 3.5 × 16 mm (Black)
2
<Outdoor unit>
(8) Drain socket
1
PARTS TO BE PROVIDED AT YOUR SITE
(A) Indoor/outdoor unit connecting wire*1
1
(B) Extension pipe
1
(C) Wall hole sleeve
1
(D) Wall hole cover
1
(E)
Pipe fixing band
2 to 5
(F) Fixing screw for (E) 4 × 20 mm
2 to 5
(G) Piping tape
1
(H) Putty
1
(I)
Drain hose
(or soft PVC hose, 15 mm inner diameter or hard PVC pipe
VP16)
1 or 2
(J) Refrigeration oil
1
(K) Power supply cord*1
1
108 mm
or more
81 mm
or more
66 mm or more/ 142 mm or more
for left/left rear piping (using spacer)
17 mm or more
1-4. INSTALLATION DIAGRAM
1.8 m or more from the floor.
Up to 2.3 m is recommended.
Outdoor unit installation
Air inlet
Air outlet
40 mm
2-10 mm × 21 mm slot
800 mm
150 mm
500 mm
344.5 mm
285 mm
304-325 mm
Air inlet
clear *2
100 mm
or more
100 mm
or more
200 mm *3
or more
*2 100 mm or more when front
and sides of unit are clear
350 mm
or more
Appearance of the outdoor unit may differ from some models.
*3 When any 2 sides of left, right and rear of unit are clear
(8)
(I)
Note:
Install the unit horizontally.
Do not use drain socket (8) in cold regions. Drain may freeze and make the
fan stop.
The outdoor unit produces condensate during the heating operation. Select
the installation place to ensure to prevent the outdoor unit and/or the grounds
from being wet by drain water or damaged by frozen drain water.
Drain piping for outdoor unit
• Provide drain piping before indoor and outdoor pip-
ing connection.
• Connect drain hose (I) I.D.15 mm as shown in the
illustration.
• Make sure to provide drain piping with a downhill
grade for easy drain flow.
Note:
*1 Place indoor/outdoor unit connecting wire (A) and power supply cord (K) at
least 1 m away from the TV antenna wire.
IMPORTANT NOTES
• Units should be installed by licensed contractor according to local code
requirements.
• To comply with the requirements of Australian standard AS/NZS 3000
electrical installations (wiring rules), the electrical wiring required between
the indoor and outdoor units must be installed by a licenced electrical
contractor.
• Check that cabling will not be subject to wear, corrosion, excessive pres-
sure, vibration, sharp edges or any other adverse environmental effects.
The check shall also take into account the effects of aging or continual
vibration from sources such as compressors or fans.
WARNING
To avoid risk of fire, flare connection should be installed outdoors.
Reusable mechanical connectors and flared joints are not allowed
indoors.
When the piping is to be attached to a wall containing metals (tin plated) or metal
netting, use a chemically treated wooden piece 20 mm or thicker between the
wall and the piping or wrap 7 to 8 turns of insulation vinyl tape around the piping.
To use existing piping, perform COOL operation for 30 minutes and pump
down before removing the old air conditioner. Remake flare according to the
dimension for new refrigerant.
After the leak test, apply insulating material tightly
so that there is no gap.
WARNING
To avoid risk of fire, embed or protect the refrigerant piping.
External damage on the refrigerant piping can be cause of fire.
Be sure to use wall hole sleeve (C)
to prevent indoor/outdoor connect-
ing wire (A) from contacting metal
parts in the wall and to prevent
damage by rodents in case the
wall is hollow.
Indoor unit
Wall hole
sleeve (C)
Cut off the
extra length.
Pipe fixing band (E)
Wall hole cover (D)
Fixing screw (F)
Seal the wall hole
gap with putty (H).
Fix the pipe to wall
with pipe fixing band
(E).
VG79J830H01.indd 3
2020/03/09 10:50:41