5-3. PUMPING DOWN

When relocating or disposing of the air conditioner, pump down the system following the procedure below so that refrigerant is not released into the atmosphere.

1) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit.

2) Fully close the stop valve on the liquid pipe side of the outdoor unit.

3) Close the stop valve on the gas pipe side of the outdoor unit almost completely so that it can be easily closed fully when the pressure gauge shows 0 psi [Gauge] (0 Mpa).

4) Start the emergency COOL operation.

  To start the emergency operation in COOL mode, disconnect the power supply plug and/or turn off the breaker. After 15 seconds, connect the power supply plug and/or turn on 

the breaker, and then press the E.O. SW once. (The emergency COOL operation can be performed continuously for up to 30 minutes.)

5) Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure gauge shows  (0.1 to 0 psi [Gauge] (0.05 to 0 Mpa)).

6) Stop the emergency COOL operation.

  To stop operation, press the E.O. SW several times until all LED lamps turn off. Refer to operating instructions for details.

5-2. REMOVING THE INDOOR UNIT

Remove the bottom of the indoor unit from the installation plate. (Fig. 1, 2)

•  Remove the panel assembly. (Refer to 5-1)

‡ ,QVHUWÀDWVFUHZGULYHUVLQWRWKHVTXDUHKROHVDWWKHOHIWDQGULJKWERWWRPRIWKHLQGRRU

unit and push them up; the bottom of the indoor unit goes down and the hooks are 

released.

*1 Remove the screw.

*2 Remove the tab of corner box from the indoor unit, and pull the corner box.

*3 Pull the indoor unit to remove.

Square hole

Push Lower

Corner box

Fig. 1

Fig. 2

When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes. The compressor may burst if air etc. get into it.

 

WARNING

HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, 

TOKYO 100-8310, JAPAN

CN105

6.  CONNECTING THE INTERFACE/CONNECTOR CABLE TO THE AIR CONDITIONER

Fix the connecting cable at the prescribed position securely. Incorrect installation 

PD\FDXVHHOHFWULFVKRFN¿UHDQGRUPDOIXQFWLRQ

 WARNING

•  Connect the INTERFACE/CONNECTOR CABLE to the Indoor electronic control P.C. board of the air conditioner with the connecting cable.

•  Cutting or extending the connecting cable of the INTERFACE/CONNECTOR CABLE results in defects in connecting. 

  Do not bundle the connecting cable together with power supply cord, indoor/outdoor connecting wire, and/or earth wire. Keep as much distance as possible between the 

connecting cable and those wires. 

•  The thin part of the connecting cable should be stored and placed where customers cannot touch it.

Air conditioner

Thin part of the connecting cable. 

Place this part where customers cannot touch it.

Thick part of the connecting cable

Indoor electronic 

control P.C. board

CN105 for INTERFACE

Connecting

1

  Remove the panel and the lower right corner box.

2

  Open the covers of the Indoor electronic control P.C. board.

3

  Connect the connecting cable to CN105 on the Indoor electronic control P.C. board.

4

  Attach the cable clamp provided with Interface to the thick part of the connecting 

FDEOHZLWKDVFUHZîDVVKRZQLQWKH¿JXUH

5

 3DVVWKHFRQQHFWLQJFDEOHWKURXJKWKHULEDVVKRZQLQWKH¿JXUH

6

  Close the covers of the Indoor electronic control P.C. board. Be careful not to catch 

the thin part of the connecting cable in the cover. Reinstall the panel and the lower 

right corner box.

Содержание MSY-GS36NA

Страница 1: ...DUWV DUH IRXQG RQ WKH SRZHU VXSSO SOXJ UHSODFH LW Securely attach the electrical cover to the indoor unit and the service panel to the outdoor unit If the electrical cover of the indoor unit and or the service panel of the outdoor unit are QRW DWWDFKHG VHFXUHO GXVW ZDWHU HWF FRXOG FROOHFW LQ WKH XQLW DQG FRXOG FDXVH D UH RU an electric shock When installing relocating or servicing the unit make su...

Страница 2: ...io Operation of the air conditioner may interfere with UDGLR RU 79 UHFHSWLRQ Q DPSOL HU PD EH UHTXLUHG IRU the affected device Q D SODFH DV IDU DZD DV SRVVLEOH IURP À XRUHVFHQW DQG incandescent lights In order to make the infrared remote control operate the air conditioner normally The heat from the lights may cause deformation or the ultraviolet may cause deterioration KHUH WKH DLU OWHU FDQ EH UH...

Страница 3: ...be attached to a wall comprised of tin plate or metal netting use chemically treated wooden piece 25 32 in 20 mm or thicker between the wall and the piping or wrap insulation vinyl tape 7 to 8 turns around the piping To use existing piping perform COOL operation for 30 minutes and pump down before removing the old air conditioner 5HPDNH À DUH DFFRUGLQJ WR WKH GLPHQVLRQ for new refrigerant 4 in 100...

Страница 4: ...d wire Fig 3 Connect it to the ground terminal of electrical parts box 10 Process the end of indoor outdoor unit connecting wire A Fig 3 Attach it to the terminal block Be careful not to make mis wiring Attach the wire to the terminal block securely so that its core cannot be seen and no external force affects the connecting section of the terminal block 11 Firmly tighten the terminal screws After...

Страница 5: ... Connect the refrigerant piping with the extension pipe B 9 Attach the lower part of the indoor unit into the installation plate 1 Drain cap Drain hose Drain cap Drain hose Fig 1 Fig 2 Fig 3 Fig 4 Fig 5 2 4 2 DRAIN PIPING If the extension drain hose has to pass through a room be sure to wrap it with insu ODWLRQ HOG VXSSOLHG The drain hose should point downward for easy drain Fig 1 I WKH GUDLQ KRVH...

Страница 6: ...l result in damage on the screw 7R FRQQHFW UVW DOLJQ WKH FHQWHU WKHQ WLJKWHQ WKH UVW WR WXUQV RI À DUH QXW E KDQG Use tightening torque table above as a guideline for indoor unit side joints and tighten XVLQJ WZR ZUHQFKHV FHVVLYH WLJKWHQLQJ GDPDJHV WKH À DUH VHFWLRQ Outdoor unit connection Connect pipes to stop valve pipe joint of the outdoor unit following the same procedure detailed in Indoor un...

Страница 7: ...m the indoor unit Press the OFF ON button again to turn the air conditioner off Once the compressor stops the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner 4 3 AUTO RESTART FUNCTION This product is equipped with an auto restart function When the power supply is cut off during operation such as during blackouts the function automa...

Страница 8: ...move Square hole Push Lower Corner box Fig 1 Fig 2 When pumping down the refrigerant stop the compressor before disconnecting the refrigerant pipes The compressor may burst if air etc get into it WARNING HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN CN105 6 CONNECTING THE INTERFACE CONNECTOR CABLE TO THE AIR CONDITIONER Fix the connecting cable at the prescribed posit...

Отзывы: