background image

1-3. SPECIFICATIONS

1-3-1. POWER SUPPLY AND INDOOR/OUTDOOR WIRE CONNECTION

•  Power should be taken from an exclusive branched circuit.

•  Wiring work should be based on applicable technical standards.

•  Wiring connections should be made following the diagram.

•  Securely tighten screws.

Connecting wires and the ground wire

•  Use solid conductor Min. AWG14 or stranded conductor Min. AWG14.

•  Use double insulated copper wire with 600 V insulation.

•  Use copper conductors only.

* Follow local electrical codes.

Power supply cable and ground wire

•  Use solid or stranded conductor Min. AWG12.

•  Use copper conductors only.

* Follow local electrical codes.

Note: 

When the indoor unit is powered from the outdoor unit, depending on local code, a 

disconnect switch needs to be installed to a power supply circuit.

Pipe length

Up to 25 ft. (7.5 m)

No additional charge is 

required.

Exceeding 25 ft. (7.5 m)

Additional charge is required.

(Refer to the table below.)

•  Refrigerant adjustment... If pipe length exceeds 25 ft. (7.5 m), additional refrigerant 

(R410A) charge is required.

(The outdoor unit is charged with refrigerant for pipe length up to 25 ft. [7.5 m])

Limits

Pipe length

100 ft. (30 m) max.

Height difference

 50 ft. (15 m) max.

No. of bends

10 max.

‡ 7KHXQLWKDVÀDUHGFRQQHFWLRQVRQERWKLQGRRUDQGRXWGRRUVLGHV

•  Remove the valve cover from the outdoor unit, then connect the pipe.

•  Refrigerant pipes are used to connect the indoor and outdoor units.

•  Be careful not to crush or over bend the pipe in pipe bending.

1-3-2. REFRIGERANT PIPES

•  To prevent condensation, insulate the two refrigerant pipes.

•  Refrigerant pipe bending radius must be 4 in. (100 mm) or more.

 CAUTION

%HVXUHWRXVHWKHLQVXODWLRQRIVSHFL¿HGWKLFNQHVVWDEOHRQWKHULJKW([FHVVLYHLQVXOD

tion may cause incorrect installation of the indoor unit, and too little insulation may cause 

condensate to form.

Pipe

Outside 

diameter

Minimum 

wall thick-

ness

Insulation 

thickness

Insulation material

inch (mm)

For liquid

1/4 (6.35)

0.0315 (0.8) 5/16 (8)

Heat resistant foam 

SODVWLF6SHFL¿F

gravity

For gas

5/8 (15.88)

0.0394 (1.0) 5/16 (8)

(OHFWULFDOVSHFL¿FDWLRQV

MODEL

MSY-GS30NA MSY-GS36NA MSZ-GS30NA MSZ-GS36NA

INDOOR UNIT
Power supply 

(V, PHASE, Hz)

208/230, 1, 60

Min. Circuit Ampacity (A)

1.0

Fan motor (F.L.A.)

(A)

0.76

OUTDOOR UNIT
Power supply 

(V, PHASE, Hz)

208/230, 1, 60

Max. Fuse size 

(time delay) 

(A)

20

Min. Circuit Ampacity (A)

19

Fan motor (F.L.A.)

(A)

0.93

Compressor

(R.L.A) (A)

13.8

(L.R.A) (A)

17.3

Control voltage

Indoor unit - Remote controller: (Wireless)

Indoor unit - Outdoor unit: DC12-24 V (Polar)

1-2. SELECTING THE INSTALLATION LOCATION

Refrigerant to be added

1.08 oz. each 5 ft. (20 g/m)

INDOOR UNIT 

‡ :KHUHDLUÀRZLVQRWEORFNHG

•  Where cool (or warm) air spreads over the entire room.

•  On a rigid wall to reduce the possibility of vibration.

•  Where it is not exposed to direct sunlight. Do not expose 

to direct sunlight also during the period following unpack-

ing to before use.

•  Where it can be easily drained.

•  At a distance 3 ft. (1 m) or more away from a TV and 

radio. Operation of the air conditioner may interfere with 

UDGLRRU79UHFHSWLRQ$QDPSOL¿HUPD\EHUHTXLUHGIRU

the affected device.

‡ ,QDSODFHDVIDUDZD\DVSRVVLEOHIURPÀXRUHVFHQWDQG

incandescent lights. In order to make the infrared remote 

control operate the air conditioner normally. The heat 

from the lights may cause deformation or the ultraviolet 

may cause deterioration.

• 

:KHUHWKHDLU¿OWHUFDQEHUHPRYHGDQGUHSODFHGHDVLO\

•  Where it is away from the other heat or steam source.

Note:

 

Install the indoor unit high on the wall where air can 

distribute over the entire room.

REMOTE CONTROLLER 

•  Where it is convenient to operate and easily visible.

•  Where children cannot easily touch it.

‡ 6HOHFWDSRVLWLRQDERXWIWPDERYHWKHÀRRU

Check that signals from the remote controller from 

that position are received by the indoor unit (‘beep’ 

or ‘beep beep’ receiving tone sounds). Then, attach 

remote controller holder to a pillar or wall and install 

wireless remote controller.

Note: 

,QURRPVZKHUHLQYHUWHUW\SHÀXRUHVFHQWODPSVDUHXVHG

the signal from the wireless remote controller may not be 

received.

OUTDOOR UNIT

•  Where it is not overly exposed to strong winds.

‡ :KHUHDLUÀRZLVJRRGDQGGXVWOHVV

•  Where neighbours are not annoyed by operation sound 

or hot air.

•  Where rigid wall or support is available to prevent the 

increase of operation sound or vibration.

•  Where there is no risk of combustible gas leakage.

•  If installing the unit in a location high above the ground, 

be sure to secure the unit legs.

•  Where it is at least 10 ft. (3 m) away from the antenna of TV 

set or radio. Operation of the air conditioner may interfere 

with radio or TV reception in areas where reception is 

ZHDN$QDPSOL¿HUPD\EHUHTXLUHGIRUWKHDIIHFWHGGHYLFH

•  Install the unit horizontally.

•  Please install it in an area not affected by snowfall or 

blowing snow. In areas with heavy snow, please install 

DFDQRS\DSHGHVWDODQGRUEDIÀHERDUGV

Note:

•  It is advisable to make a piping loop near outdoor unit 

so as to reduce vibration.

‡ )RU LQFUHDVHG HI¿FLHQF\ LQVWDOO WKH RXWGRRU XQLW LQ D

location where continuous direct sunlight or excessive 

water can be avoided as much as possible.

Note:

When operating the air conditioner in low outside tem-

perature, be sure to follow the instructions described 

below.

•  Never install the outdoor unit in a place where its air 

inlet/outlet side may be exposed directly to wind.

•  To prevent exposure to wind, install the outdoor unit 

with its air inlet side facing the wall and 

DEDIÀHERDUG

on the air outlet side.

Avoid the following places for installation where air 

conditioner trouble is liable to occur.

‡ :KHUHÀDPPDEOHJDVFRXOGOHDN

•  Where there is an excessive amount of machine oil 

in the air.

‡ :KHUHRLOLVVSODVKHGRUZKHUHWKHDUHDLV¿OOHGZLWK

oily smoke (such as cooking areas and factories, in 

which the properties of plastic could be changed and 

damaged).

•  Salty places such as the seaside.

‡ :KHUHVXO¿GHJDVLVJHQHUDWHGVXFKDVDKRWVSULQJ

•  Where there is high-frequency or wireless equipment.

•  Where  there  is  emission  of  high  levels  of  VOCs, 

including phthalate compounds, formaldehyde, etc., 

which may cause chemical cracking.

Содержание MSY-GS36NA

Страница 1: ...DUWV DUH IRXQG RQ WKH SRZHU VXSSO SOXJ UHSODFH LW Securely attach the electrical cover to the indoor unit and the service panel to the outdoor unit If the electrical cover of the indoor unit and or the service panel of the outdoor unit are QRW DWWDFKHG VHFXUHO GXVW ZDWHU HWF FRXOG FROOHFW LQ WKH XQLW DQG FRXOG FDXVH D UH RU an electric shock When installing relocating or servicing the unit make su...

Страница 2: ...io Operation of the air conditioner may interfere with UDGLR RU 79 UHFHSWLRQ Q DPSOL HU PD EH UHTXLUHG IRU the affected device Q D SODFH DV IDU DZD DV SRVVLEOH IURP À XRUHVFHQW DQG incandescent lights In order to make the infrared remote control operate the air conditioner normally The heat from the lights may cause deformation or the ultraviolet may cause deterioration KHUH WKH DLU OWHU FDQ EH UH...

Страница 3: ...be attached to a wall comprised of tin plate or metal netting use chemically treated wooden piece 25 32 in 20 mm or thicker between the wall and the piping or wrap insulation vinyl tape 7 to 8 turns around the piping To use existing piping perform COOL operation for 30 minutes and pump down before removing the old air conditioner 5HPDNH À DUH DFFRUGLQJ WR WKH GLPHQVLRQ for new refrigerant 4 in 100...

Страница 4: ...d wire Fig 3 Connect it to the ground terminal of electrical parts box 10 Process the end of indoor outdoor unit connecting wire A Fig 3 Attach it to the terminal block Be careful not to make mis wiring Attach the wire to the terminal block securely so that its core cannot be seen and no external force affects the connecting section of the terminal block 11 Firmly tighten the terminal screws After...

Страница 5: ... Connect the refrigerant piping with the extension pipe B 9 Attach the lower part of the indoor unit into the installation plate 1 Drain cap Drain hose Drain cap Drain hose Fig 1 Fig 2 Fig 3 Fig 4 Fig 5 2 4 2 DRAIN PIPING If the extension drain hose has to pass through a room be sure to wrap it with insu ODWLRQ HOG VXSSOLHG The drain hose should point downward for easy drain Fig 1 I WKH GUDLQ KRVH...

Страница 6: ...l result in damage on the screw 7R FRQQHFW UVW DOLJQ WKH FHQWHU WKHQ WLJKWHQ WKH UVW WR WXUQV RI À DUH QXW E KDQG Use tightening torque table above as a guideline for indoor unit side joints and tighten XVLQJ WZR ZUHQFKHV FHVVLYH WLJKWHQLQJ GDPDJHV WKH À DUH VHFWLRQ Outdoor unit connection Connect pipes to stop valve pipe joint of the outdoor unit following the same procedure detailed in Indoor un...

Страница 7: ...m the indoor unit Press the OFF ON button again to turn the air conditioner off Once the compressor stops the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner 4 3 AUTO RESTART FUNCTION This product is equipped with an auto restart function When the power supply is cut off during operation such as during blackouts the function automa...

Страница 8: ...move Square hole Push Lower Corner box Fig 1 Fig 2 When pumping down the refrigerant stop the compressor before disconnecting the refrigerant pipes The compressor may burst if air etc get into it WARNING HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN CN105 6 CONNECTING THE INTERFACE CONNECTOR CABLE TO THE AIR CONDITIONER Fix the connecting cable at the prescribed posit...

Отзывы: