14
NOTE:
•
The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the
remote controller.
•
If main power is turned OFF or a power failure occurs while AUTO START/STOP timer is active, the timer setting is
cancelled.
•
If the unit has been turned OFF with the remote controller before power failure, the auto restart function does not
work as the power button of the remote controller is OFF.
•
To prevent the breaker from tripping OFF due to the rush of starting current, systematize other home appliance not to
turn ON at the same time.
•
When some air conditioners are connected to the same supply system, if they are operated before power failure, the
starting current of all the compressors may flow simultaneously at restart.
Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting cur-
rent by adding to the system that allows the units to start one by one.
7-3. AUTO RESTART FUNCTION
When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed
are memorized by the indoor electronic control P.C. board. “AUTO RESTART FUNCTION” automatically starts operation in
the same mode just before the shut-off of the main power.
Operation
If the main power has been cut, the operation settings remain.
After the power is restored, the unit restarts automatically according to the memory.
(However, it takes at least 3 minutes for the compressor to start running.)
How to disable “AUTO RESTART FUNCTION”
Turn OFF the main power of the unit.
Solder the Jumper wire JR07 on the indoor electronic control P.C. board.
(GL06/09/12/15NA)
Cut the Jumper wire JR77 on the indoor electronic control P.C. board.
(GL18/24NA)
(Refer to 9-7.)
CN
111
CN1
12
CN152
CN10A
Indoor electronic
control P.C. board
JR77
CN151
JR77
Indoor electronic
control P.C. board
CN10A
CN
111
CN151
CN112
CN110
MSZ-GL24NA
MSY-GL24NA
MSZ-GL18NA
MSY-GL18NA
CN
11
1
CN1
12
CN151
CN10A
Indoor electronic
control P.C. board
JR07
MSZ-GL06/09/12/15NA
MSY-GL09/12/15NA
OBH732D