background image

11

TROUBLESHOOTING

9

9-1. Cautions on troubleshooting

1. Before troubleshooting, check the following:
(1) Check the power supply voltage.
(2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during servicing.

(1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and then after

confirming the horizontal vane is closed, turn OFF the breaker and / or disconnect the power plug.

(2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic

control P.C. board.

(3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the

components.

(4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.

3. Troubleshooting procedure

(1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing ON and OFF to indicate an abnormality.

To make sure, check how many times the abnormality indication is flashing ON and OFF before starting service work.

(2) Before servicing, check that the connector and terminal are connected properly.
(3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the

components for bursting and discolouration.

(4) When troubleshooting, refer to 9-2. and 9-3.

4. How to replace batteries

Weak batteries may cause the remote controller malfunction.
In this case, replace the batteries to operate the remote controller normally.

1

Remove the front lid and insert batteries.

Then reattach the front lid.

Lead wiring

Housing point

MSH-GA50VB
MSH-GA60VB
MSH-GA80VB

RESET button

Insert the negative pole 
of the batteries first.
Check if the polarity of 
the batteries is correct.

2

Press the RESET button with tip end of ball point 
pen or the like, and then use the remote controller.

NOTE : If the RESET button is not pressed, the remote controller may not operate correctly.

OB367B-1.qxp  07.5.18 4:29 PM  Page 11

Содержание MSH-GA50VB

Страница 1: ...ARTS 25 MSH GA50VB MSH GA60VB MSH GA80VB E1 E1 E1 SPLIT TYPE HEAT PUMP AIR CONDITIONERS SERVICE MANUAL Wireless type Models INDOOR UNIT NOTE This service manual describes technical data of the indoor units RoHS compliant products have G mark on the spec name plate For servicing of RoHS compliant products refer to the RoHS PARTS LIST RoHS compliant Outdoor unit service manual MUH GA VB Series OB368...

Страница 2: ...SH GA50VB MSH A24WV MSH GA60VB MSH A30WV MSH GA80VB 1 Model name has been changed Indication of capacity has been changed BTU kW 2 Grille design has been changed 3 Unit size has been changed W 1 100aoH 325aoD 227a W1 100aoH 325aoD 258a E1 E1 E1 E1 E1 E1 ACCESSORIES 1 2 3 4 5 6 7 Installation plate Installation plate fixing screw 4 o 25 mm Remote controller holder Fixing screw for 3 o 3 5 o 1 6 mm ...

Страница 3: ...the front lid Signal transmitting section Operation display section OPERATE STOP ON OFF button TEMPERATURE buttons OPERATION SELECT button FAN SPEED CONTROL button OFF TIMER button HR button MIN button TIME SET button ON TIMER button RESET button ECONO COOL button VANE button Horizontal vane button CLOCK SET button LONG button WIDE VANE button Vertical vane button Indication of remote controller m...

Страница 4: ...eating 768 642 528 45 40 34 1 070 920 780 Electrical data Fan motor Special remarks Capacity NOTE Test conditions are based on ISO 5151 Cooling Indoor DB27 C WB19 C Heating Indoor DB20 C WB 15 5 C Outdoor DB35 C WB 24 C Outdoor DB 7 C WB 6 C Indoor Outdoor piping length 5m Indoor model Function Power supply Air flow High Med Low Power outlet Running current Power input Power factor Fan motor curre...

Страница 5: ...R FREQUENCIES Hz Test conditions Cooling Dry bulb temperature 27 Wet bulb temperature 19 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 42 SPL dB A LINE High FAN SPEED Heating Dry bulb temperature 20 Wet bulb temperature 15 5 OCTAVE BAND SOUND PRESSURE LEVEL dB re 0 0002 MICRO BAR 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 NC 60 NC 50 NC 40 NC 30 NC 20 NC 70 BAND CENTER F...

Страница 6: ...nnected part O D Installation plate Wall hole 75 Wireless remote controller Installation plate Indoor unit Liquid line 6 35 0 5m Gas line 12 0 43m Insulation 50 O D 32 I D Liquid line 9 52 0 5m Gas line 12 0 43m Insulation 50 O D 32 I D for MSH GA50 60VB for MSH GA80VB Power supply cord Lead to right 2 0m Lead to left 1 0m MSH GA50VB MSH GA60VB MSH GA80VB Unit mm ...

Страница 7: ... PE BRN TO OUTDOOR UNIT CONNECTING 12V 1 2 3 4 5 6 CIRCUIT BREAKER POWER SUPPLY CORD N 230V 50Hz 12V TO OUTDOOR UNIT CONNECTING BRN BLU GRN YLW BLK GRY YLW BRN WHT RED MF 3 SR141 4 3 1 CN 121 C11 HIC1 MV1 RT13 4 3 2 1 CN112 151 CN MV2 15 RT12 RT11 111 CN CN211 NR11 ELECTRONIC CONTROL P C BOARD F11 3 N L BRN 1 2 3 CN201 MV2 BLU RED CN 101 CN 102 DISPLAY P C BOARD RECEIVER P C BOARD REMOTE CONTROLLE...

Страница 8: ...t flow in cooling Refrigerant flow in heating MSH GA50VB Indoor heat exchanger Room temperature thermistor RT11 Refrigerant pipe 12 7 with heat insulator Flared connection Flared connection Indoor coil thermistor RT12 Refrigerant pipe 6 35 with heat insulator Distributor MSH GA60VB Indoor heat exchanger Room temperature thermistor RT11 Refrigerant pipe 15 88 with heat insulator Flared connection F...

Страница 9: ...t time 3 minute 3 second It takes 3 minutes for the compressor to start operation However the starting time is shortened by short circuit of JPG and JPS The P C board has the print J1 and J2 Solder J1 and J2 according to the number of indoor unit as shown in Table 1 After modification press the RESET button MSH GA50VB MSH GA60VB MSH GA80VB How to set the remote controller exclusively for particula...

Страница 10: ... failure the auto restart function does not work as the power button of the remote controller is OFF To prevent breaker OFF due to the rush of starting current systematize other home appliances not to turn ON at the same time When some air conditioners are connected to the same supply system if they are operated before power failure the starting current of all the compressors may flow simultaneous...

Страница 11: ...INDICATOR lamp on the indoor unit is flashing ON and OFF to indicate an abnormality To make sure check how many times the abnormality indication is flashing ON and OFF before starting service work 2 Before servicing check that the connector and terminal are connected properly 3 When the electronic control P C board seems to be defective check the copper foil pattern for disconnection and the compo...

Страница 12: ...6 time flash Cause Outdoor unit Trouble of thermistor in outdoor unit 7 time flash Cause Outdoor unit Trouble of outdoor control system Refer to 9 5 D How to check mis wiring When outdoor unit doesn t work Check room temperature thermistor and indoor coil thermis tor Refer to 9 6 Test point diagram and voltage Refer to 9 5 A Check of indoor fan motor Refer to Check of outdoor thermistor Replace th...

Страница 13: ... outdoor service manual Refer to 9 5 D How to check mis wiring 3 Indoor fan motor MUH GA80VB Low discharge temperature protection MUH GA80VB When discharge temperature has been 50 or less on cool operation or has been 49 or less on heat operation for 20 minutes Abnormal point Outdoor unit does not operate Room temperature thermistor 2 time flash 2 5 second OFF Detect Indoor coil room temperature t...

Страница 14: ...h a tester Part temperature 10 C 30 C Color of lead wire BRN YLW YLW GRY Normal 4 5 5 5V Measure the voltage power ON When fan revolved one time 0V 5V 0V Approx Normal 282 306 Measure the resistance between the terminal with a tester Part temperature 10 C 30 C BLK RED WHT GRY YLW BRN MAIN AUX FUSE BLK RED WHT GRY YLW BRN MSH GA80VB 132 144 152 166 Normal MSH GA50 GA60VB MSH GA80VB Measure the resi...

Страница 15: ...is pressed Is the voltage approx 4V DC Replace the indoor electronic control P C board Replace the receiver P C board Replace the remote controller Reinstall the unit away from lights Attach a filter on receiving part Yes 0 or No others Yes No Yes No Is LCD display on the remote con troller visible Remove the batteries then set them back and press the RESET button Check if the unit operates with t...

Страница 16: ...e varistor Yes Turn OFF the power supply Remove indoor fan motor connector CN211 and vane motor connector CN151 from the indoor electronic control P C board and turn ON the power supply No Does the unit operate with the remote controller Does the OPERATION INDICATOR lamp light up by pressing the EMERGENCY OPERATION switch Yes No Turn OFF the power supply Turn OFF the power supply Varistor NR11 Ind...

Страница 17: ...nnection Correct them Replace the indoor electronic control P C board Is there 230V AC between L N on the outdoor terminal block No Check the outdoor power supply and connection of wiring Yes No Replace the deicer P C board Yes No Make the wiring between CN730 on the deicer P C board and outdoor terminal block correct Replace the deicer P C board Yes Is there 5V DC between J205 J101 MUH GA50VB J10...

Страница 18: ...C 5V DC Indoor coil thermistor RT12 main Timer short mode point JPS JPG Refer to 8 1 Emergency operation switch 12V DC Indoor coil thermistor RT12 main RT13 sub Room temperature thermistor RT11 Resistance k Room temperature ther mistor RT11 Release of Auto restart function Solder jumper wire to JR07 Refer to 8 3 MSH GA80VB Indoor coil thermistor RT13 sub R132 Receiver P C board ...

Страница 19: ...rew caps of the front panel Remove the screws 2 Pull the panel down to your side slightly and unhook the catches at the top Photo 1 Photo 2 Front panel Screw of the V A clamp Indoor electronic control P C board Vane motor connector Fan motor connectors Screws of the earth wire Screws Screw of the electrical cover R L holder Screw of the terminal block Receiver P C board 2 Removing the electronic c...

Страница 20: ...e drain hose from the nozzle assembly and remove the nozzle assembly 6 Remove the screws of the vane motor and disconnect the connector 7 Remove the vane motor Screws fixing the fan motor 5 Removing the line flow fan and the indoor fan motor 1 Remove the front panel Refer to 1 2 Remove the electrical box Refer to 3 3 Pull out the drain hose from the nozzle assembly and remove the nozzle assembly 4...

Страница 21: ...ring Diagram Q ty unit Including No 4 5 6 4PCS SET 3PCS SET 1PCE SET Remarks Part No NO Part Name 1 2 3 4 5 6 7 8 9 1 1 1 4 3 1 2 1 1 1 1 1 4 3 1 2 1 1 1 1 1 4 3 1 2 1 1 11 2 INDOOR UNIT HEAT EXCHANGER 2 4 5 7 6 1 10 8 11 12 3 E02 891 620 E02 893 620 E02 179 667 E02 138 666 E02 151 667 E02 527 667 INDOOR HEAT EXCHANGER INDOOR HEAT EXCHANGER UNION GAS UNION GAS UNION LIQUID UNION LIQUID 12 7 15 88 ...

Страница 22: ... INDOOR COIL THERMISTOR VANE MOTOR SUPPORT SET RIGHT VANE MOTOR SUPPORT SET LEFT Symbol in Wiring Diagram Q ty unit 3 15A RIGHT LEFT UP DOWN Remarks Part No NO Part Name F11 NR11 MF MF MV2 MV1 RT11 TB RT12 RT12 RT13 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 MSH GA50 VB E1 MSH GA60 VB E1 MSH GA80 VB E1 RC4V32 ...

Страница 23: ... unit Including No 4 5 6 4PCS SET 3PCS SET 1PCE SET Remarks Part No NO Part Name 1 2 3 4 5 6 7 8 9 RoHS G G G G G G G G G 1 1 1 4 3 1 2 1 1 1 1 1 4 3 1 2 1 1 1 1 1 4 3 1 2 1 1 12 2 INDOOR UNIT HEAT EXCHANGER 2 4 5 7 6 1 10 8 11 12 3 E12 891 620 E12 893 620 E12 179 667 E12 138 666 E12 151 667 E12 527 667 INDOOR HEAT EXCHANGER INDOOR HEAT EXCHANGER UNION GAS UNION GAS UNION LIQUID UNION LIQUID 12 7 ...

Страница 24: ...OR SUPPORT SET RIGHT VANE MOTOR SUPPORT SET LEFT Symbol in Wiring Diagram Q ty unit 3 15A RIGHT LEFT UP DOWN Remarks Part No NO G G G G G G G G G G G G G G G G G G G G G G G G G G G RoHS Part Name F11 NR11 MF MF MV2 MV1 RT11 TB RT12 RT12 RT13 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 MSH GA50 VB E1 MSH GA60 V...

Страница 25: ...EANING FILTER is 4 months However when it becomes dirty replace it as soon as possible Clogged AIR CLEANING FILTER may reduce the air conditioner capacity or cause frost on the air outlet DO NOT reuse AIR CLEANING FILTER even if it is washed DO NOT remove or attach AIR CLEANING FILTER during unit operation Model Part No MAC 1700FT MSH GA50VB MSH GA60VB MSH GA80VB OPTIONAL PARTS ...

Страница 26: ...26 ...

Страница 27: ...27 ...

Страница 28: ...C C Copyright 2004 MITSUBISHI ELECTRIC ENGINEERING CO LTD Distributed in May 2007 No OB367 REVISED EDITION B 6 Distributed in May 2006 No OB367 REVISED EDITION A 6 Distributed in Oct 2004 No OB367 6 Made in Japan HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Отзывы: