![Mitsubishi Electric MSH-C18TV Скачать руководство пользователя страница 26](http://html.mh-extra.com/html/mitsubishi-electric/msh-c18tv/msh-c18tv_service-manual_1810454026.webp)
26
9-1-3. HEAT mode of “I FEEL CONTROL”
1. Indoor fan speed control
(1) In AUTO the fan speed is as follows.
Set temperature minus room temperature: 2 degrees or more ·············································· High
Set temperature minus room temperature: Between 1 and 2 degrees··································· Med.
Set temperature minus room temperature: less than 1 degree ·············································· Low
(2) Cold air prevention control
The fan runs at set speed when the indoor coil thermistor RT12 temperature exceeds 22°C. The fan operates at Very
Low when the temperature of indoor coil thermistor RT12 is below 18°C. But the fan stops when the indoor fan operates
at Very Low and the room temperature is 15°C or less.
NOTE : If the temperature of RT12 reads from 18°C to 22°C at the air conditioner starting and also after defrosting, this
control works.
(3) Warm air control.
When compressor starts in heating operation or after defrosting, the fan changes the speed due to the indoor coil ther-
mistor RT12 temperature to blow out warm air.
After releasing of cold air prevention, when the indoor coil thermistor RT12 temperature is 37°C or above, the fan speed
shifts to the set speed, and when the fan speed is changed by the remote controller, the fan speed is the set speed.
When the indoor coil thermistor RT12 temperature is less than 37°C, the fan speed is controlled by time as below.
<Time condition> <Indoor fan speed>
less than 2 minutes ························Low
2 minutes to 4 minutes···················Med.
4 minutes or more ··························High
The upper limit of the fan speed is the set speed.
If the thermostat turns off, this operation changes to flow soft control.
(4) Flow soft control
After the thermostat turns off, the indoor fan operates at Very Low.
NOTE : When the thermostat turns on, the fan operates at the set speed. Due to the cold air prevention control, the fan
does not start at set speed until the indoor coil thermistor RT12 reads 22°C or more.
Difference between room
temperature and set temperature
during operation
1deg. 1.7deg.
4deg.
2deg.
Initial temperature difference
Fan speed
Released
Cold Air Prevention
18
:
22
:
Fan speed
Set speed
Very Low or stop
High pressure protection
Released
52
:
56
:
ON
Outdoor fan
OFF
3. High pressure protection
During heating operation, the outdoor fan motor is controlled by the temperature of indoor coil thermistor RT12 for excess
rise protection of compressor discharge pressure.
Outdoor fan OFF : 56°C
Outdoor fan ON : 52°C
High pressure protection chart
Example
Indoor coil thermistor
RT12 temperature
56˚C
52˚C
Outdoor fan motor
Outdoor fan motor
turn OFF
Outdoor fan motor
turn ON
ON
ON
OFF
OFF
NOTE 1 During high pressure protection and for 4 minutes and 15 seconds (MUH-C18TV)/ 10 seconds (MUH-C24TV) after
high pressure protection, defrosting of outdoor heat exchanger is not detected by the defrost thermistor RT61.
Indoor coil thermistor
RT12 temperature
2. Outdoor fan control <MSH-C24TV only>
Outdoor fan speed is controlled according to the temperature of ambient temperature thermistor RT63.
Outdoor fan Low operation : Until the outside temperature decreases to 12°C.
When the outside temperature goes to 14°C or more.
Outdoor fan High operation :When the outside temperature decreases to 12°C or less.
Until the outside temperature goes to 14°C.
Outdoor fan speed
12
:
14
:
High
Ambient temperature
thermistor RT63 temperature
Low
OB279-1.qxp 2/15/01 10:44 AM Page 26
Содержание MSH-C18TV
Страница 59: ...OB279 2 qxp 2 15 01 10 56 AM Page 59 ...