Operation time chart
Example
3. Coil frost prevention
• The operation is as same as coil frost prevention during COOL mode of “I FEEL CONTROL”.
• Indoor fan operates at the set speed and the compressor stops for 5 minutes, because protection(Coil frost
prevention) has the priority.
However, when coil frost prevention works while the compressor is not operating, it’s speed becomes Low.
4. Outdoor fan control <MSH-C24TV only>
Outdoor fan control is as same as one of COOL mode of “I FEEL CONTROL”.
Thermostat
Indoor fan
Outdoor fan
Compressor
ON
8 min.
1 min.
4 min.
3 min.
ON
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
Compressor
Outdoor fan
OFF
ON
(continuously at set speed)
Indoor fan
ON
ON
OFF
Operation chart
Example
9-1-2. DRY mode of “I FEEL CONTROL”
The system for dry operation uses the same refrigerant circuit as the cooling circuit.
The compressor and the indoor fan are controlled by the room temperature.
By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature
decrease.
1. Indoor fan speed control
Indoor fan operates at the set speed by FAN SPEED CONTROL button.
However, in AUTO fan operation, fan speed becomes Low.
2. The operation of the compressor and indoor/ outdoor fan
Compressor operates by room temperature control and time control.
Set temperature is controlled to fall 2°C from initial room temperature.
Indoor fan and outdoor fan operate in the same cycle as the compressor.
•When the room temperature is 23°C or over:
When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
•When the room temperature is under 23°C.
When the thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
OFF
OFF
OFF
3. Outdoor fan control <MSH-C24TV only>
Outdoor fan speed is controlled according to the temperature of ambient temperature
thermistor RT63.
Outdoor fan Low operation : When the outside temperature decreases to 28°C or less.
Until the outside temperature goes to 31°C or more.
Outdoor fan High operation : Until the outside temperature decreases to 28°C or less.
When the outside temperature goes to 31°C or more.
NOTE : If the temperature of RT63 reads from 28
:
to 31
:
at the air conditioner starting, outdoor fan speed is High.
Outdoor fan speed
28
:
31
:
High
Ambient temperature
thermistor RT63 temperature
Low