17
Piping size O.D : mm
Length of connecting pipe : m
Model
Piping size O.D : mm
Length of connecting pipe : m
Model
Refrigerant piping
Max. length : m
A
10
15
Indoor unit
Gas 0.43
Liquid 0.5
Gas
9.52
12.7
Liquid
6.35
Outdoor unit
Gas 0
Liquid 0
MSC-C07TV -
E1
MUH-C07TV -
E1
MSC-C09TV -
E1
MUH-C09TV -
E1
MSC-C12TV -
E1
MUH-C12TV -
E1
{
{
{
Refrigerant piping
Max. length : m
A
10
15
Indoor unit
Gas 0.43
Liquid 0.5
Gas
9.52
12.7
Liquid
6.35
Outdoor unit
Gas 0
Liquid 0
MSC-C07TV -
E1
MU-C07TV -
E1
MSC-C09TV -
E1
MU-C09TV -
E1
MSC-C12TV -
E1
MU-C12TV -
E1
{
{
{
Indoor
unit
w
Max. Height
difference 5m
w
Height difference should be within
5m regardless of which unit,
indoor or outdoor position is high.
Outdoor unit
Refrigerant Piping
Max.length
A
Model
Refrigerant piping length (one way)
Model
Refrigerant piping length (one way)
Outdoor unit precharged
900
1000
1250
15m
200
7m
0
10m
75
MSC-C07TV -
E1
MUH-C07TV -
E1
MSC-C09TV -
E1
MUH-C09TV -
E1
MSC-C12TV -
E1
MUH-C12TV -
E1
{
{
{
Calculation : Xg=25g/m x(Refrigerant piping length (m) -7)
Outdoor unit precharged
770
880
900
15m
120
7m
0
10m
45
MSC-C07TV -
E1
MU-C07TV -
E1
MSC-C09TV -
E1
MU-C09TV -
E1
MSC-C12TV -
E1
MU-C12TV -
E1
{
{
{
Calculation : Xg=15g/m x(Refrigerant piping length (m) -7)
MAX. HEIGHT DIFFERENCE
ADDITIONAL REFRIGERANT CHARGE(R407C : g)
MAX. REFRIGERANT PIPING LENGTH