2. Indoor fan speed control
Indoor fan operates at the set speed by FAN SPEED CONTROL button.
In Auto fan speed becomes Low.
3.
The operation of the compressor and indoor/outdoor fan
Compressor operates by room temperature control and time control.
Set temperature is controlled to fall 2°C from initial room temperature.
Indoor fan and outdoor fan operate in the same cycle as the compressor.
●
When the room temperature is 23°C or over:
When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
●
When the room temperature is under 23°C.
When the thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
Set temperature is as shown on the right chart.
The system for dry operation uses the same refrigerant circuit as the
cooling circuit.
The compressor and the indoor fan are controlled by the room tem-
perature.
By such controls, indoor flow amounts will be reduced in order to
lower humidity without much room temperature decrease.
DRY operation will not work when the room temperature is 13°C or
below.
1-2. DRY ( ) OPERATION
35
30
25
20
15
10
10 15 20 25 30 35
Set temperature
Initial room temperature
Set temperature and
initial room temperature in DRY mode
Thermostat
Indoor fan
Outdoor fan
Compressor
ON
8 minutes
3
minutes
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
Operation time chart
Example
When the room temperature is 23°C or over:
4. Coil frost prevention
• The operation is the same as coil frost prevention during COOL mode.
• The indoor fan operates at the set speed and the compressor does not operate for 5 minutes because the coil frost pre-
vention has priority.
1
minute
4
minutes
-0.3
°C
0.3
°C
1. Thermostat control (MSC-GE20/25/35VB)
Thermostat turns ON or OFF by the difference between room temperature and set temperature.
Initial temperature difference
Thermostat
Room temperature minus set temperature : 0.3°C or more ·············································· ON
Room temperature minus set temperature : less than -0.3°C ··········································· OFF
Set temperature
Difference between room
temperature and set tem-
perature during operation
-0.3
°
C
0.3°C
Set temperature
Difference between room
temperature and set tem-
perature during operation
1. Thermostat control (MSC-GE20/25/35VB)
Thermostat turns ON or OFF by the difference between room temperature and set temperature.
Initial temperature difference
Thermostat
Room temperature minus set temperature : less than -0.3°C ············································· ON
Room temperature minus set temperature : 0.3°C or more ················································ OFF
1-3. HEAT ( ) OPERATION (MSC-GE20/25/35VB, MSH-GD80VB, MSH-GE50VB)