10 4-WAY AIR FLOW SYSTEM
10-1. FRESH AIR INTAKE (LOCATION FOR INSTALLATION)
At the time of installation, use the duct holes (cut out) located at the positions shown in following diagram, as and when required.
120°
120°
[
100
140
186
37
+5 0
208
Detail drawing of fresh air intake
Ceiling surface
Refrigerant pipe
Drain pipe
Electrical Box
Fresh air intake
Cut out hole
Burring hole
Static pressure : P
[Pa]
Air flow : Q [m
3
/min]
−
150
−
120
−
90
−
60
−
30
0
0.3
0.6
0.9
1.2
1.5
Taking air into the unit
10-2. FRESH AIR INTAKE AMOUNT & STATIC PRESSURE CHARACTERISTICS
Q
0
B
A
C
1
Curve in the
left graphs
Duct characteristics
at site
Q
A
E
C
2
Q
Qa
A
D
3
How to read curves
● Whenever the indoor unit operates, the
duct fan operates.
(1) Connect the optional multiple remote
controller adapter (PAC-SA88HA-E)
to the connector CN51 on the indoor
controller board.
(2) Drive the relay after connecting the
12 V DC relay between the Yellow
and Orange connector wires.
Use a relay of 1W or smaller.
MB: Electromagnetic switch power
relay for duct fan.
X: Auxiliary relay (12 V DC LY-1F)
Be sure to secure insulation
material by tape, etc.
5
Green
Yellow
−
Orange
+
Connector (5P)
Indoor unit side
Multiple remote
controller adapter
PAC-SA88HA-E
Be sure to secure insulation
material by tape, etc.
Installation at site
CN51
on
indoor unit
board
Red
Brown
1
~
MB
Multiple remote
controller adapter
PAC-SA88HA-E
Indoor controller board
Distance between indoor
controller board and relay
must be within 10m.
CN51
10-3. OPERATION IN CONJUNCTION WITH DUCT FAN (BOOSTER FAN)
NOTE: Fresh air intake amount should be 10% or less of
whole air amount to prevent dew dripping.
Q…
Designed amount of fresh air intake
<m
3
/min>
A
…
Static pressure loss of fresh air
intake duct system with air flow
amount Q
<Pa>
B
…
Forced static pressure at air condi-
tioner inlet with air flow amount Q
<Pa>
C
…
Static pressure of booster fan with
air flow amount Q
<Pa>
D
…
Static pressure loss increase
amount of fresh air intake duct sys-
tem for air flow amount Q
<Pa>
E
…
Static pressure of indoor unit with
air flow amount Q
<Pa>
Qa…
Estimated amount of fresh air
intake without D
<m
3
/min>