background image

16

Error Code

Abnormal point and detection method 

Cause

Countermeasure

P9

Pipe temperature thermistor / Condenser 
/ Evaporator (TH5)

1

 The unit is in 3-minute resume protec-

tion mode if short/open of thermistor is 
detected. Abnormal if the unit does not 
get back to normal within 3 minutes. (The 
unit returns to normal operation, if it has 
been reset normally.)

2

 Constantly detected during cooling, 

drying, and heating operation (except 
defrosting)

  Short: 194°F or more
  Open: -40°F or less

1

 Defective thermistor 

 characteristics

2

 Contact failure of  connector 

(CN29) on the indoor controller 
board (Insert failure)

3

 Breaking of wire or contact 

  failure of thermistor wiring

4

 Temperature of thermistor is 

194°F or more or -40°F or less 
caused by defective refrigerant 
circuit.

5

 Defective indoor controller 

board

1

Check resistance value of thermistor.

 

For characteristics, refer to (P1) above.

2

 Check contact failure of  connector (CN29) 

on the indoor controller board. 

  Refer to 6-4.
  Turn the power on and check restart after 

inserting connector again.

4

 Operate in test run mode and check pipe 

<condenser/evaporator> temperature with 
outdoor controller circuit board. If pipe 

  <condenser/evaporator> temperature is 

extremely low (in cooling mode) or high (in 
heating mode), refrigerant circuit may have 
defect.

5

 Operate in test run mode and check pipe 

<condenser/evaporator> temperature with 
outdoor control circuit board. If there is 

  extreme difference with actual pipe 
  <condenser/evaporator> temperature replace 

indoor controller board.

  There is no abnormality if none of above 

comes within the unit.

  Turn  the power off and on again to operate.

E0

or

E4

Remote controller transmission 
error(E0)/signal receiving error(E4)

1

 Abnormal if main or sub remote con-

troller cannot receive any transmission 
normally from indoor unit of refrigerant 
address “0” for 3 minutes.

  (Error code : E0)

2

 Abnormal if sub-remote controller could 

not receive for any signal for 2 minutes. 
(Error code: E0) 

1

 Abnormal if indoor controller board 

cannot receive normally any data from 
remote controller board or from other 
indoor controller board for 3 minutes. 
(Error code: E4)

2

 Indoor controller board cannot receive 

any signal from remote controller for 2 
minutes. (Error code: E4)

1

 Check disconnection or looseness of indoor 

unit or transmission wire of remote controller.

2

 Set one of the remote controllers “main”,

  if there is no problem with the action above.

3

 Check wiring of remote controller.

• Total wiring length: max. 500m
  (Do not use cablex 3 or more)
• The number of connecting indoor units: 

max. 16 units

• The number of connecting remote control-

ler: max. 2 units

When the above-mentioned problem of 

1

~

are not seen.

4

 Diagnose remote controllers.

a) When “RC OK” is displayed,

remote controllers have no problem. 
Turn the power off, and on again to check. 
If abnormality generates again, replace 
indoor controller board.

b) When “RC NG” is displayed,

replace remote controller.

c) When “RC E3”or “ERC 00-66” is dis-

played, noise may be causing abnormality.

E3

or

E5

Remote controller transmission 
error(E3)/signal receiving error(E5)

1

 Abnormal if remote controller could not 

find blank of transmission path for 6 sec-
onds and could not transmit.

    (Error code: E3)  

2

 Remote controller receives transmitted 

data at the same time, compares the 
data, and when detecting it, judges 

  different data to be abnormal 30 
  continuous times. (Error code: E3) 

1

 Abnormal if indoor controller board could 

not find blank of transmission path.

   (Error code: E5)   

2

 Indoor controller board receives trans-

mitted data at the same time, compares 
the data,and when detecting it, judges 
different data to be abnormal 30 

  continuous times. (Error code: E5)

1

 Set a remote controller to main, and the 

other to sub.

2

 Remote controller is connected with only one 

indoor unit.

3

 The address changes to a separate setting.

4

~

Diagnose remote controller.

a) When “RC OK”is displayed, remote con-

trollers have no problem.

   Turn the power off, and on again to check.
   When becoming abnormal again, replace 

indoor controller board.

b) When “RC NG” is displayed, replace 

remote controller.

c) When “RC E3”or “ERC 00-66” is dis-

played, noise may be causing abnormal-
ity.

1

 Contact failure at transmission 

wire of remote controller

2

 All remote controllers are set 

as “sub” remote controller. In 
this case, E0 is displayed on 
remote controller, and E4 is 
displayed at LED (LED1, LED2) 
on the outdoor controller circuit 
board.

3

 Miswiring of remote controller

4

 Defective transmitting/receiving 

circuit of remote controller

5

 Defective transmitting/receiving 

circuit of indoor controller board 
of refrigerant address “0”

6

 Noise has entered into the 

transmission wire of remote 
controller.

1

 2 remote controllers are set as 

“main.”   

    (In case of 2 remote con-
     trollers)

2

 Remote controller is connected 

with 2 indoor units or more.

3

 Repetition of refrigerant 

address

4

 Defective transmitting/receiving 

circuit of remote controller

5

 Defective transmitting/receiving 

circuit of indoor controller board

6

 Noise has entered into trans-

mission wire of remote control-
ler.

Содержание Mr.Slim SLZ-KA09NA

Страница 1: ...YSTEM 26 9 DISASSEMBLY PROCEDURE 28 November 2010 No OCH487 REMOTE CONTROLLER Option Indoor unit Model names Service Ref SLZ KA09NA SLZ KA09NA TH SLZ KA12NA SLZ KA12NA TH SLZ KA15NA SLZ KA15NA TH INDOOR UNIT Model name indication ON OFF TEMP Note This manual describes only service data of the indoor units RoHS compliant products have G mark on the spec name plate For servicing RoHS compli ant prod...

Страница 2: ...er Removes dust and pollutants from inhaled air Horizontal Air Outlet Sets horizontal airflow automatically during cooling or dehumidifying Air Intake Intakes air from room Indoor Unit SLZ KA09NA TH SLZ KA12NA TH SLZ KA15NA TH Radio frequency interface RF thermostat Wired remote controller Remote controller Optional parts ON OFF TEMP ...

Страница 3: ...ng the cover ON OFF button Fan Speed button Filter button Enter button Test Run button Check button Clear button Airflow Up Down button Louver button Operation button To return operation number Ventilation button Operation button To go to next operation number Built in temperature sensor Wired remote controller Option Once the controllers are set the same operation mode can be repeated by simply p...

Страница 4: ...is off Temperature Setting Shows the target temperature Day of Week Shows the current day of the week Time Timer Display Shows the current time unless the simple or Auto Off timer is set If the simple or Auto Off timer is set the time to be switched off is shown Sensor indication Displays when the remote controller sensor is used Locked indicator Indicates that remote controller but tons have been...

Страница 5: ...sconnect switch A 15 Min circuit ampacity A 1 0 Fan motor F L A 0 23 0 28 0 28 Airflow Low Med High Dry CFM 280 320 350 280 320 390 280 320 390 Wet CFM 250 290 320 250 290 350 250 290 350 Moisture removal pt h 1 2 2 3 4 5 Sound pressure level Low Med High dB A 29 32 38 30 34 39 31 35 40 External finish color Unit Galvanized sheets with gray heat insulation Grille ABS resin Munsell 6 4Y 8 9 0 4 Dim...

Страница 6: ...TAVE BAND SOUND PRESSURE LEVEL dB 0 dB 0 0002 μbar BAND CENTER FREQUENCIES Hz NOISE CRITERION CURVES UNIT 5 ft MICROPHONE CEILING SLZ KA15NA TH High Medium 40 SPL dB 35 LINE 60Hz NOTCH Low 31 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC 60 NC 50 NC 40 NC 30 NC 20 NC 70 OCTAVE BAND SOUND PRESSURE LEVEL dB 0 dB 0 0002 μbar BAN...

Страница 7: ...1 27 32 301 11 27 32 301 14 27 32 377 14 27 32 377 25 19 32 650 Suspension bolt M10 or W3 8 9 1 16 230 7 5 32 182 1 7 8 48 Wiring entry Terminal block Ceiling surface 9 1 4 235 8 3 16 208 7 19 32 193 25 32 20 3 21 32 93 1 1 2 2 9 32 38 58 2 19 32 66 4 3 4 121 21 32 17 7 15 16 202 2 7 32 56 2 1 14 57 3 7 16 87 1 7 32 31 Ceiling hole Suspension bolt pitch 19 32 1 15 32 15 37 19 32 1 15 32 15 37 22 1...

Страница 8: ...8 WIRED REMOTE CONTROLLER Unit inch mm 5 1 8 130 3 4 19 4 23 32 120 1 23 32 43 5 Option ...

Страница 9: ...ERMINAL A CENTRALLY CONTROL POWER SUPPLY I B POWER SUPPLY I B TRANSMISSION INDOOR OUTDOOR DRAIN PUMP DEW PREVENTION HEATER SWITCH EMERGENCY OPERATION SWITCH CAPACITY CODE FAN MOTOR WITH THERMAL FUSE VANE MOTOR DRAIN PUMP DRAIN SENSOR TERMINAL BLOCK INDOOR OUTDOOR CONNECTING LINE TERMINAL BLOCK REMOTE CONTROLLER TRANSMISSION LINE TERMINAL BLOCK REMOTE CONTROLLER TRANSMISSION LINE ROOM TEMP THERMIST...

Страница 10: ...50 Condenser evaporator temperature thermistor TH5 Room temperature thermistor TH1 Refrigerant flow in cooling Refrigerant flow in heating Strainer 50 Strainer 50 Heat exchanger Refrigerant GAS pipe connection Flare Refrigerant LIQUID pipe connection Flare SLZ KA09NA TH SLZ KA12NA TH SLZ KA15NA TH ...

Страница 11: ...ors hold the housing of the connector DO NOT pull the lead wires Lead wire PAR 21MAA ON OFF FILTER CHECK OPERATION CLEAR TEST TEMP MENU BACK DAY MONITOR SET CLOCK ON OFF ERROR CODE ERROR CODE ERROR CODE Turn on the power Press the CHECK button twice Set address with TEMP button if system control is used Press the ON OFF button to stop the self check CHECK button Address TEMP button IC Indoor unit ...

Страница 12: ...tom Remark Number of times IR wireless remote controller Wired remote controller Beeper sounds OPERATION INDICATOR lamp blinks Check code Number of times IR wireless remote controller Wired remote controller 1 P1 Intake sensor error P9 Pipe TH5 sensor error 2 P2 Pipe TH2 sensor error 3 E6 E7 Indoor outdoor unit communication error 4 P4 Drain sensor error 5 P5 Drain pump error 6 P6 Freezing Overhea...

Страница 13: ...r terminal block Incorrect wiring between indoor and outdoor units incorrect polarity of S1 S2 S3 Remote controller wire short Note Operation is not possible for about 30 seconds after cancellation of function selection Correct operation For description of each LED LED1 2 3 provided on the indoor controller refer to the following table LED1 power for microprocessor Indicates whether control power ...

Страница 14: ...ture with remote controller in test run mode If pipe liquid temperature is extremely low in cooling mode or high in heating mode refrigerant circuit may have defect 5 Check pipe liquid temperature with remote controller in test run mode If there is extreme difference with actual pipe liquid tempera ture replace indoor controller board Turn the power off and on again to operate after checking P4 Dr...

Страница 15: ... outdoor fan control 6 Overcharge of refrigerant 7 Defective refrigerant circuit clogging 8 Bypass circuit of outdoor unit is defective Cooling or drying mode 1 Check clogging of the filter 2 Remove blockage 4 Measure the resistance of fan motor s winding Measure the output voltage of fan s connector FAN on the indoor controller board WThe indoor controller board should be normal when voltage of A...

Страница 16: ...3 Check wiring of remote controller Total wiring length max 500m Do not use cablex 3 or more The number of connecting indoor units max 16 units The number of connecting remote control ler max 2 units When the above mentioned problem of 1 3 are not seen 4 Diagnose remote controllers a When RC OK is displayed remote controllers have no problem Turn the power off and on again to check If abnormality ...

Страница 17: ...y of the remote controller control board Error code E1 2 Abnormal if the clock function of remote controller cannot be normally operated Error code E2 1 Defective remote controller 1 Replace remote controller PA 2502 2500 Forced compressor stop due to water leakage abnormality 1 When the intake temperature subtracted with liquid pipe temperature is less than 14 F drain sensor detects whether it is...

Страница 18: ... 6 4 1 Indoor power board SLZ KA09NA TH SLZ KA12NA TH SLZ KA15NA TH CNSK Connect to the indoor controller board CNDK between 1 to 3 208 230V AC CN2S Connect to the indoor controller board CN2D between 1 to 3 12 6 13 7V DC Pin1 ...

Страница 19: ...VDC 3 3 5 Malfunction indicator 13VDC 3 CN6V Vane motor output MV CN90 Connect to the IR wireless remote con troller board CNB CN31 Drain sensor DS CN29 Condenser evaporator temperature thermistor TH5 CN21 Pipe temperature thermistor Liquid TH2 CN20 Room temperature thermistor TH1 CN22 Remote controller connecting wire 10 4 14 6V DC LED3 Transmission Indoor outdoor LED2 Power supply R B LED1 Power...

Страница 20: ...thermistor liquid TH2 Indoor fan motor MF Check method and criterion Part name Normal KA09NA Normal WHT BLK BLK BLU BLU YLW YLW RED RED BRN 387 418 77 83 19 21 179 193 KA12NA 303 328 105 114 39 42 235 254 KA15NA 272 295 79 85 37 40 191 206 4 3k 9 6k Abnormal Abnormal Opened or short circuited Opened or short circuited Measure the resistance between the terminals with a tester At the ambient temper...

Страница 21: ...k 90_F 3 9k 100_F 3 2k Thermistor R0 6 0k 5 Fixed number of B 3390 2 Rt 6exp 3390 30_F 6 3k 50_F 3 9k 70_F 2 5k 80_F 2 0k 90_F 1 6k 100_F 1 3k Thermistor for lower temperature 1 273 t 32 1 8 1 273 1 273 t 32 1 8 1 273 Thermistor for drain sensor 0 10 20 30 40 50 0 20 20 40 60 80 100 120 Thermistor for lower temperature Temperature F Resistance k 20 40 60 80 100 120 140 170 Thermistor for drain sen...

Страница 22: ...t type setting JP1 0 1 2 3 9 Wireless remote controller setting Control PCB setting J41 J42 Initial setting IR wireless remote controller 0 Control PCB for both J41 and J42 Four pair number settings are supported The pair number settings of the IR wireless remote controller and indoor control PCB J41 J42 are given in the table on the left in the table indicates the jumper wire is disco nnected The...

Страница 23: ...on Outline of functions Main and sub units operate alternately according to the interval of rotation setting w Main and sub unit should be set by refrigerant address Outdoor Dip switch setting Refrigerant address 00 Main unit Refrigerant address 01 Sub unit When error occurs to one unit another unit will start operation Back up function System constraint This function is available only by the grou...

Страница 24: ... up function No 5 314 Rotation ON Alternating interval 3 day and back up function No 6 315 Rotation ON Alternating interval 5 day and back up function No 7 316 Rotation ON Alternating interval 7 day and back up function No 8 317 Rotation ON Alternating interval 14 day and back up function No 9 318 Rotation ON Alternating interval 28 day and back up function Setting No Request code Setting contents...

Страница 25: ...s the button to perform function setting If above setting operations are done correctly Request code number will appear in data display area Example When the 311 of Request code number is set 311 appears on the screen Refererence You can check current request code number setting by setting the request code number 310 or 320 and pressing the button Example When the current setting is Setting No 2 R...

Страница 26: ...roller board and relay must be within 10m Be sure to secure insulation material by tape etc 5 Green Yellow Orange Connector 5P Indoor unit side Multiple remote controller adapter PAC SA88HA E Be sure to secure insulation material by tape etc Installation at site CN51 on indoor unit board Red Brown 1 CN51 MB CN51 WHT 8 3 OPERATION IN CONJUNCTION WITH DUCT FAN BOOSTER FAN Static pressure P in W G 10...

Страница 27: ...e Vane motor Horizontal vane Connector Unlocking button Vane motor 3 Set the vertical vane of the air outlet by hand slowly within the range in the table below Measured standard posi tion of the grille Horizontal vane Specified range Up down airflow direction Horizontal 30 Downward 45 Downward 55 Downward 70 A 21 mm 13 16 inch 25 mm 31 32 inch 28 mm 1 3 32 inch 30 mm 1 3 16 inch The vanes can be s...

Страница 28: ...ke grille knob 3 Removing the panel 1 Remove the air intake grille Refer to step 1 Corner panel See Figure 2 1 Remove the screw of the corner 2 Slide the corner panel to the direction of the arrow 3 and remove the corner panel Panel See Photo 2 1 Disconnect the connector that connects with the unit 2 Remove the 2 screws from the panel and loose another 2 screws which are fixed to the oval hole hav...

Страница 29: ...astener wireless controller board relay connector 9P red and panel relay connector 10P white 3 Remove the 4 screws fixed to the drain pan and remove the drain pan 4 Remove the fan guard Refer to step 2 5 Removing the room temperature thermistor TH1 1 Remove the panel Refer to step 3 2 Pull out the room temperature thermistor from the drain pan 3 Remove the 2 screws fixed to the control box cover a...

Страница 30: ...nd the holder Photo 7 Screw Screws Drain sensor DS Drain pump DP Drain hose Fixing band Control box Cover Screw Control box Photo 8 Lead wires 8 Removing the fan motor MF 1 Remove the panel Refer to step 3 2 Remove the drain pan Refer to step 6 3 Remove the nut and the washer from the turbo fan and remove the turbo fan 4 Remove the 2 screws fixed to the control box cover and remove the control box...

Страница 31: ...over and remove the piping cover See Photo 9 7 Remove the pipe temperature thermistor liquid and condenser evaporator temperature thermistor Refer to step 7 8 Disconnect the lead wires to the direction of the fan motor 9 Remove the 1 coil support screw the 2 inside coil screws See Photo 10 and the 4 outside coil screws See Photo 9 from the heat exchanger and remove the heat exchanger Photo 9 Photo...

Страница 32: ... MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN CCopyright 2010 MITSUBISHI ELECTRIC ENGINEERING CO LTD Distributed in Nov 2010 No OCH487 Made in Japan New publication effective Nov 2010 Specifications subject to change without notice ...

Отзывы: