background image

18

8. Electrical work

8.4.  Function settings (Function selection via the 

remote controller)

8.4.1 Function setting on the unit (Selecting the unit functions)

1) Changing the external static pressure setting

[Fig. 8-20] (P.8)

Hour button

Minute button

TEMP button

TEMP button

ON/OFF button

CHECK button

• 

Be sure to change the external static pressure setting depending on the duct and 

the grill used.

  Go to the function select mode 

Press the CHECK button 

 twice continuously. 

(Start this operation from the status of remote controller display turned off.) 

CHECK

 is lighted and “00” blinks. 

Press the TEMP button 

 once to set “50”. Direct the wireless remote controller 

toward the receiver of the indoor unit and press the Hour button 

  Setting the unit number 

Press the TEMP button 

 and 

 to set the unit number to 01-04 or 07. Direct 

the wireless remote controller toward the receiver of the indoor unit and press 

the Minute button 

.

  Selecting a mode 

Enter 08 to change the external static pressure setting using the 

 and 

 buttons. 

Direct the wireless remote controller toward the receiver of the indoor unit and 

press the Hour button 

.

 

Current setting number: 

1 = 1 beep (one second)

 

 

2 = 2 beeps (one second each)

 

 

3 = 3 beeps (one second each)

  Selecting the setting number 

Use the 

 and 

 buttons to change the external static pressure setting to be 

used. 

Direct the wireless remote controller toward the sensor of the indoor unit and  

press the Hour button 

.

  To set the external static pressure 

Repeat steps 

 and 

 to set the mode number to 10.

  Complete function selection 

Direct the wireless remote controller toward the sensor of the indoor unit and 

press the ON/OFF button 

.

External static  

pressure

Setting no. of mode 

no. 08

Setting no. of mode 

no. 10

05 Pa

1

2

15 Pa (before shipment)

1

1

35 Pa

2

1

50 Pa

3

1

Note: 

• 

Whenever changes are made to the function settings after installation or 

maintenance, be sure to record the changes with a mark in the “Check” 

column of the Function table.

2) Other functions

  Select unit number 00 for the settings. (Settings for all indoor units) 

Refer to Function table 1.

  Select unit number 01 to 04 or 07 for the settings. (Settings for each indoor unit) 

To set the indoor unit in the individual system, select unit number 01. 

To set each indoor unit of two, three or four indoor units, which are connected 

when these units are simultaneously in operation, select unit number 01 to 04. 

To set all indoor units of two, three or four indoor units which are connected 

when these units are simultaneously in operation, select 07. 

Refer to Function table 2.

Function table 1

Select unit number 00

Mode

Settings

Mode no.

Setting no. Initial setting

Check

Power failure automatic recovery 

(AUTO RESTART FUNCTION)

Not available

01

1

*2

Available *1

2

*2

Indoor temperature detecting

Indoor unit operating average

02

1

Set by indoor unit’s remote controller

2

Remote controller’s internal sensor

3

LOSSNAY connectivity

Not Supported

03

1

Supported (indoor unit is not equipped with outdoor-air intake)

2

Supported (indoor unit is equipped with outdoor-air intake)

3

Function table 2

Select unit numbers 01 to 04 or all units (AL [wired remote controller]/07 [wireless remote controller])

Mode

Settings

Mode no.

Setting no. Initial setting

Check

Filter sign

100 Hr

07

1

2500 Hr

2

No filter sign indicator

3

External static pressure

15 Pa

08

1

35 Pa

2

50 Pa

3

The same as setting of mode no. 08

10

1

5 Pa (set mode no. 08 to 1)

2

*1 When the power supply returns, the air conditioner will start 3 minutes later.

*2  Power failure automatic recovery initial setting depends on the connecting outdoor unit.

Note: 

  When the function of an indoor unit were changed by function selection after the end of installation, always indicate the contents by entering a 

 or other mark in 

the appropriate check filed of the tables.

9. Test run

9.1. Before test run

 

After completing installation and the wiring and piping of the indoor and 

outdoor units, check for refrigerant leakage, looseness in the power supply 

or control wiring, wrong polarity, and no disconnection of one phase in the 

supply.

 

Use a 500-volt megohmmeter to check that the resistance between the 

power supply terminals and ground is at least 1.0 MΩ.

 

Do not carry out this test on the control wiring (low voltage circuit) terminals.

 Warning:

Do not use the air conditioner if the insulation resistance is less than 1.0 MΩ.

Insulation resistance

After installation or after the power source to the unit has been cut for an extended 

period, the insulation resistance will drop below 1 MΩ due to refrigerant accumulating 

in the compressor. This is not a malfunction. Perform the following procedures.

1.  Remove the wires from the compressor and measure the insulation resistance of 

the compressor.

2.  If the insulation resistance is below 1 MΩ, the compressor is faulty or the 

resistance dropped due the accumulation of refrigerant in the compressor.

3.  After connecting the wires to the compressor, the compressor will start to warm 

up after power is supplied. After supplying power for the times indicated below, 

measure the insulation resistance again.

• 

The insulation resistance drops due to accumulation of refrigerant in the 

compressor. The resistance will rise above 1 MΩ after the compressor is 

warmed up for two to three hours.

  (The time necessary to warm up the compressor varies according to 

atmospheric conditions and refrigerant accumulation.)

• 

To operate the compressor with refrigerant accumulated in the compressor, the 

compressor must be warmed up at least 12 hours to prevent breakdown.

4. If the insulation resistance rises above 1 MΩ, the compressor is not faulty.

 Caution:

• 

The compressor will not operate unless the power supply phase 

connection is correct.

• 

Turn on the power at least 12 hours before starting operation.

 - Starting operation immediately after turning on the main power switch can 

result in severe damage to internal parts. Keep the power switch turned on 

during the operational season.

Содержание Mr. Slim SEZ-M25DAL

Страница 1: ...nditioners INDOOR UNIT SEZ M25 M35 M50 M60 M71DAL INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit FOR INSTALLER English ORIGINAL ...

Страница 2: ...ess door 1 450 mm x 450 mm Ⓕ Maintenance access space Ⓖ Supply air mm Model P Q R S SEZ M25 700 50 150 800 1300 SEZ M35 50 900 150 250 1000 1500 SEZ M60 71 1100 250 350 1200 1700 777 S 50 50 P 700 Min 300 mm Viewed from the direction of the arrow B Ⓖ Ⓗ Ⓚ Ⓕ Ⓐ Ⓘ Fig 3 1 5 Ⓖ Ⓗ Ⓘ Ⓕ 700 450 475 450 Q 50 150 450 450 100 200 Min 300 mm Viewed from the direction of the arrow A P Ⓔ Ⓐ Ⓓ Fig 3 1 2 Unit mm Mi...

Страница 3: ...3 4 Fig 4 1 5 Y X L W Ⓐ Z Ⓐ Center of gravity 5 1 Ⓒ Ⓓ Ⓒ Ⓔ Ⓓ Ⓒ Nuts field supply Ⓓ Washers accessory Ⓔ M10 hanging bolt field supply Fig 5 2 Ⓑ Ⓐ Ⓐ Unit body Ⓑ Lifting machine Fig 5 1 ...

Страница 4: ... 3 6 5 Ⓓ Ⓔ Ⓗ Ⓖ Ⓘ Ⓕ Ⓑ Ⓒ 5 25 Ⓐ Ⓐ Indoor unit Ⓑ Pipe cover short accessory Ⓒ Tie band accessory Ⓓ Band fixing part Ⓔ Insertion margin Ⓕ Drain hose accessory Ⓖ Drain pipe O D ø32 PVC TUBE field supply Ⓗ Insulating material field supply Ⓘ Max 145 5 mm Fig 6 11 Ⓐ Pipe cover small accessory Ⓑ Caution Pull out the thermal insulation on the refrigerant piping at the site insert the flare nut to flare the ...

Страница 5: ... ordinary bushing Ⓘ Signal receiving unit wiring Ⓙ Terminal bed for power source and indoor transmission Ⓚ Indoor outdoor unit connecting wire Ⓛ Connecting the signal receiving unit Connect the signal receiving unit to the CN90 Connect to the wireless remote controller board on the indoor unit using the supplied remote controller wire Connect the signal receiving units to all the indoor units Ⓐ Te...

Страница 6: ...ord Outdoor terminal block Always install an earth wire 1 core 1 5 mm2 longer than other cables Signal receiving unit cable accessory wire length 5 m Signal receiving unit Power supply cord Ⓕ Indoor controller board 8 8 2 J41 J42 JP1 JP2 JP3 CN90 CN4F CN44 CN20 Red CNMF SW1 SW2 CN32 CN41 CN51 ON OFF SWE CN2L CN22 Blue CNP Blue CN3C Blue CN01 Black CN90 Connector for remote controller wire connecti...

Страница 7: ...r wire Fig 8 13 Ⓐ Insert the minus screwdriver toward the arrow pointed and wrench it to remove the cover A flat screwdriver whose width of blade is between 4 and 7 mm 5 32 9 32 inch must be used Fig 8 14 Ⓐ Indoor unit Hang the cover to the upper hooks 2 places Mount the cover to the lower case Ⓐ Cross section of upper hooks Fig 8 10 Fig 8 15 Ⓗ Ⓙ Ⓘ When using the switch box When installing directl...

Страница 8: ...nstalling the lower case directly on the wall or the ceiling use wood screws Insert the minus screwdriver toward the arrow pointed and wrench it to remove the cover A flat screwdriver whose width of blade is between 4 and 7 mm 5 32 9 32 inch must be used Fig 8 19 Ⓐ Hang the cover to the upper hooks 2 places Mount the cover to the lower case Ⓐ Cross section of upper hooks Ⓐ Hour button Ⓑ Minute but...

Страница 9: ...lve Ⓕ Outdoor unit Ⓖ Refrigerant gas cylinder operating valve Ⓗ Refrigerant gas cylinder for R32 R410A with siphon Ⓘ Refrigerant liquid Ⓙ Electronic scale for refrigerant charging Ⓚ Charge hose for R32 R410A Ⓛ Gauge manifold valve for R32 R410A Ⓜ Service port 10 1 ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOUVER MODE CHECK RESET SET CLOCK TESTRUN Ⓑ Ⓐ Ⓒ Ⓓ ...

Страница 10: ...efective insulation exceeding the permissible current etc Check that the refrigerant gas does not leak after installation has completed Perform the installation securely referring to the installation manual Incomplete installation could cause a personal injury due to fire electric shock the unit falling or leakage of water Perform electrical work according to the installation manual and be sure to...

Страница 11: ...all room or similar location make sure that there are no refrigerant leaks before performing the work If refrigerant leaks and accumulates it may ignite or poisonous gases may be released For installation and relocation work follow the instructions in the installation manual and use tools and pipe components specifically made for using with refrigerant specified in the outdoor unit installation ma...

Страница 12: ...re high humidity due point above 26 C due condensation may be produced in the indoor unit When operating the units in this condition add insulation material 10 20 mm to the entire surface of the indoor unit to avoid due condensation 3 1 Install the indoor unit on a ceiling strong enough to sustain its weight Secure enough access space to allow for the maintenance inspection and replacement of the ...

Страница 13: ...ing boards Center of gravity and Product Weight Model name W L X Y Z Product Weight kg SEZ M25 625 752 263 351 106 17 5 SEZ M35 625 952 286 448 104 21 SEZ M50 625 952 280 437 104 22 SEZ M60 625 1152 285 527 104 25 5 SEZ M71 625 1152 285 527 104 25 5 5 Installing the unit 5 1 Hanging the unit body Bring the indoor unit to an installation site as it is packed To hang the indoor unit use a lifting ma...

Страница 14: ... flare nut included with this indoor unit 6 2 4 Flaring work Fig 6 6 P 4 ⓐ Flaring tool ⓑ Die ⓒ Copper tube ⓓ Flare nut ⓔ Yoke Carry out flaring work using flaring tool as shown below Pipe diameter mm Dimension A mm B 0 0 4 mm When the tool for R32 R410A is used Clutch type 6 35 0 0 5 9 1 9 52 0 0 5 13 2 12 7 0 0 5 16 6 15 88 0 0 5 19 7 Firmly hold copper tube in a die in the dimension shown in th...

Страница 15: ...Downward slope 1 100 or more Ⓑ Connection dia R1 external thread Ⓒ Indoor unit Ⓓ Collective piping Ⓔ Maximize this length to approx 10 cm Ensure that the drain piping is downward pitch of more than 1 100 to the outdoor discharge side Do not provide any trap or irregularity on the way Ensure that any cross wise drain piping is less than 20 m excluding the difference of elevation If the drain piping...

Страница 16: ...t connecting wire 3 core 1 5 mm2 or more Ⓓ Outdoor terminal block Ⓔ Power supply cord Ⓕ Indoor controller board Connecting cable Cable 3 core 1 5 mm2 in conformity with Design 245 IEC 57 Indoor terminal block Outdoor terminal block Always install an earth wire 1 core 1 5 mm2 longer than other cables Signal receiving unit cable accessory wire length 5 m Signal receiving unit Power supply cord Perfo...

Страница 17: ... position depending on the indoor unit model Connect the remote controller wire securely to the order wire To pass the remote controller wire through the conduit follow the procedure as shown in Fig 8 12 Fig 8 12 P 7 Ⓐ Fix tightly with tape Ⓒ Order wire Ⓑ Remote controller wire Note The point where the remote controller wire is connected differs depending on the indoor unit model Take into account...

Страница 18: ...ntroller s internal sensor 3 LOSSNAY connectivity Not Supported 03 1 〇 Supported indoor unit is not equipped with outdoor air intake 2 Supported indoor unit is equipped with outdoor air intake 3 Function table 2 Select unit numbers 01 to 04 or all units AL wired remote controller 07 wireless remote controller Mode Settings Mode no Setting no Initial setting Check Filter sign 100 Hr 07 1 2500 Hr 2 ...

Страница 19: ...rol system error memory error etc 14 PL Refrigerant circuit abnormal No sound No corresponding Output pattern B Errors detected by unit other than indoor unit outdoor unit etc Wireless remote controller Symptom Remark Beeper sounds OPERATION INDICATOR lamp flashes Number of times 1 Indoor outdoor unit communication error Transmitting error Outdoor unit For details check the LED display of the outd...

Страница 20: ... between the indoor and outdoor units Make sure that this LED is always blinking 9 3 AUTO RESTART FUNCTION Indoor controller board This model is equipped with the AUTO RESTART FUNCTION When the indoor unit is controlled with the remote controller the operation mode set temperature and the fan speed are memorized by the indoor controller board The auto restart function sets to work the moment the p...

Страница 21: ......

Страница 22: ...owing EU regulations Low Voltage Directive 2014 35 EU Electromagnetic Compatibility Directive 2014 30 EU Energy related Products Directive 2009 125 EC Machinery Directive 2006 42 EC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Отзывы: