81
OCH738
(2) Functions available when setting the unit number to 01–03 or AL (07 in case of wireless remote controller)
• When setting functions for an indoor unit in an independent system, set the unit number to 01 referring to
4
setting the
indoor unit number of Operating Procedure.
• When setting functions for a simultaneous- Twin Triple indoor unit system, set the unit number to 01 to 03 for each indoor
unit in case of selecting different functions for each unit referring to
4
setting the indoor unit number of Operating Procedure.
• When setting the same functions for an entire simultaneous Twin Triple-indoor unit system, set refrigerant address to AL (07
in case of wireless remote controller) referring to
4
setting the indoor unit number of Operating Procedure.
PEAD-M
•
JA(L)
Function
Settings
No.
Mode
No.
Setting : Initial setting
(Factory setting)
Filter sign
100h
1
2500h
07
2
No filter sign indicator
3
External static pressure 35/50/70/100/150Pa
08
10
1
2
Extra low
3
Fan speed during the
heating thermo OFF
Stop
25
1
Set fan speed
2
27
1
2
Detection of abnormality
of the pipe
1
28
2
Set temperature in heating
24
mode (4 degree-up)
Refer to the right table
External static pressure 35/50/70/100/150Pa
Refer to the right table
Available
Not available
Fan speed during the
cooling thermo OFF
Set fan speed
Stop
Available
Not available
External static
pressure
Setting No.
Initial setting
(Factory setting)
35Pa
50Pa
70Pa
100Pa
150Pa
2
3
1
2
3
Mode No. 08 Mode No. 10
1
1
2
2
2
Mode No.11
Setting No.
Settings
PLA-ZM
・
EA
PCA-M
・
KA
1
No Vanes
Vane No.3 setting
( Downward position than the standard )
Less smudging
No vane function
2
Vane No.1 setting
Standard
Standard
3
Vane No.2 setting
Less draft * (Upward position than the standard) Less draft * (Upward position than the standard)
* In this setting, the ceiling may be smudged.
Function
Settings
Mode
No.
Setting
No.
Initial setting (factory setting) ─: Not available
4-way cassette
Ceiling suspended
Wall mounted
PLA-ZM•EA
PCA-HAQ
PCA-M•KA
PKA-M•HA(L)
PKA-M•KA(L)
Filter sign
100 h
07
1
●
●
●
2500 h
2
●
●
No filter sign indicator
3
Airflow
(Fan speed)
Quiet
08
1
–
–
Standard
2
●
–
●
●
●
High ceiling
3
–
–
–
No. of air outlets
4 directions
09
1
●
–
–
–
–
3 directions
2
–
–
–
–
2 directions
3
–
–
–
–
Optional high efficiency
filter
Not supported
10
1
●
–
●
–
–
Supported
2
–
–
–
Vane setting
No vanes (Vane No. 3 setting: PLA only)
11
1
–
–
–
Vane No.1 setting
2
–
●
–
–
Vane No.2 setting
3
●
–
–
–
3D i-See sensor
positioning
Position
1
("□" stamp position)
12
1
–
–
–
–
(Position
2
)
2
–
–
–
–
Position
3
("□" stamp position)
3
●
–
–
–
–
Optional humidifier
(PLA only)
Not supported
13
1
●
–
–
–
–
Supported
2
–
–
–
–
–
Vane differential setting in
heating mode
(cold wind prevention)
No.1 setting (TH5: 24–28
:
)
14
1
–
No.2 setting (Standard, TH5: 28–32
:
)
2
●
–
●
●
●
No.3 setting (TH5: 32–38
:
)
3
–
Swing
Not available Swing
23
1
Available
Wave airflow
2
●
–
●
●
●
Set temperature in heating
mode (4 degree-up)*
Available
24
1
●
●
●
●
●
Not available
2
Fan speed during the
heating thermo-OFF
Extra low
25
1
●
●
●
●
●
Stop
2
Setting fan speed
3
3D i-See sensor ceiling
height setting
Low ceiling
26
1
–
–
–
–
Standard
2
●
–
–
–
–
High ceiling
3
–
–
–
–
Fan speed during the
cooling thermo-OFF
Setting fan speed
27
1
●
–
–
–
Stop
2
Extra low
3
●
–
●
●
●
Detection of abnormality of
the pipe temperature (P8)
Available
28
1
●
●
●
●
●
Not available
2
*PKA-HAL/KAL: 2 degree-up
}
PLA-EA