29
OCH773
OPERATION
INDICATOR
lamp blink
pattern
Beep
Beep Beep Beep
Beep
Beep
Beep
Off
Approx. 2.5 s
On
Approx. 3 s
On
0.5 s
On
0.5 s
On
0.5 s
On
0.5 s
Off
Approx. 2.5 s
On
Approx. 3 s
On
0.5 s
On
0.5 s
· · · Repeated
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “U2”)
Number of blinks/beeps in pattern indicates
the check code in the following table
n
th
1
st
2
nd
3
rd
1
st
2
nd
Self-check
starts
(Start signal
received)
Beeper sounds
[Output pattern B]
OPERATION
INDICATOR
lamp blink
pattern
Beep
Beep Beep Beep
Beep
Beep Beep
Off
Approx. 2.5 s
On
0.5 s
On
0.5 s
On
0.5 s
On
0.5 s
Off
Approx. 2.5 s
On
0.5 s
On
0.5 s
· · · Repeated
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “P5”)
Number of blinks/beeps in pattern indicates
the check code in the following table
n
th
1
st
2
nd
3
rd
1
st
2
nd
Self-check
starts
(Start signal
received)
Beeper sounds
• Refer to the following tables for details on the check codes.
[Output pattern A]
[Output pattern A] Errors detected by indoor unit
Wireless remote controller
Wired remote controller
Symptom
Remarks
Beeper sounds/OPERATION
INDICATOR lamp blinks
(Number of times)
Check code
1
P1
Intake sensor error
As for indoor unit, refer
to indoor unit's service
manual.
2
P2
Pipe (TH2) sensor error
P9
Pipe (TH5) sensor error
3
E6, E7
Indoor/outdoor unit communication error
4
P4
Drain sensor error/Float switch connector (CN4F) open
5
P5
Drain pump error
PA
Forced compressor stop(due to water leakage abnormality)
6
P6
Freezing/Overheating protection operation
7
EE
Combination error between indoor and outdoor units
8
P8
Pipe temperature error
9
E4, E5
Remote controller signal receiving error
10
–
–
11
Pb
Indoor unit fan motor error
12
Fb (FB)*
Indoor unit control system error (memory error, etc.)
14
PL
Abnormality of refrigerant circuit
-
E0, E3
Remote controller transmission error
-
E1, E2
Remote controller control board error
[
Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wireless remote controller
Wired remote controller
Symptom
Beeper sounds/OPERATION
INDICATOR lamp blinks
(Number of times)
Check code
1
E9
Indoor/outdoor unit communication error
(Transmitting error) (Outdoor unit)
2
UP
Compressor overcurrent interruption
3
U3, U4
Open/short of outdoor unit thermistors
4
UF
Compressor overcurrent interruption (When compressor locked)
5
U2
Abnormal high discharging temperature/49C operated/
insufficient refrigerant
6
U1, Ud (UD)*
Abnormal high pressure (63H operated)/Overheating
protection operation
7
U5
Abnormal temperature of heat sink
8
U8
Outdoor unit fan protection stop
9
U6
Compressor overcurrent interruption/Abnormal of power module
10
U7
Abnormality of superheat due to low discharge temperature
11
U9, UH
Abnormality such as overvoltage or undervoltage and abnormal synchronous signal to main circuit/
Current sensor error
12
-
-
13
-
-
14
Others
Other errors (Refer to the technical manual for the outdoor unit.)
Notes:
1. If the beeper does not sound again after the initial 2 beeps to confirm the self-check start signal was received and
the OPERATION INDICATOR lamp does not come on, there are no error records.
2. If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 seconds)” after the initial 2 beeps to confirm
the self-check start signal was received, the specified refrigerant address is incorrect.
* The check code in the parenthesis indicates PAR-3xMAA ("x" represents 0 or later) model.
Содержание MR. SLIM PUZ-M100VKA2
Страница 17: ...17 OCH773 5 OUTLINES AND DIMENSIONS Unit mm ...
Страница 18: ...18 OCH773 6 WIRING DIAGRAM PUZ M100VKA2 ET ER TH ...
Страница 19: ...19 OCH773 PUZ M125VKA2 ET ER TH PUZ M140VKA2 ET ER TH ...
Страница 20: ...20 OCH773 PUZ M100YKA2 ET ER TH PUZ M125YKA2 ET ER TH PUZ M140YKA2 ET ER TH ...
Страница 115: ...115 OCH773 ...