14
OCH773
4
DATA
4-1. REFILLING REFRIGERANT CHARGE (R32: kg)
Additional charge is required for pipes longer
than 30 m.
Service Ref.
Piping length (one way)
Initial
charged
5 m
10 m 15 m 20 m 25 m 30 m 40 m 50 m 55 m 60 m 65 m
PUZ-M100VKA2(-ET/-ER).TH 3.1
3.1
3.1
3.1
3.1
3.1
3.5
3.9
4.1
-
-
3.1
PUZ-M125VKA2(-ET/-ER).TH 3.6
3.6
3.6
3.6
3.6
3.6
4.0
4.4
4.6
4.8
5.0
3.6
PUZ-M140VKA2(-ET/-ER).TH
PUZ-M100YKA2(-ET/-ER).TH 3.1
3.1
3.1
3.1
3.1
3.1
3.5
3.9
4.1
-
-
3.1
PUZ-M125YKA2(-ET/-ER).TH 3.6
3.6
3.6
3.6
3.6
3.6
4.0
4.4
4.6
4.8
5.0
3.6
PUZ-M140YKA2(-ET/-ER).TH
4-2. COMPRESSOR TECHNICAL DATA
(Winding temperature at 20°C)
Service Ref.
PUZ-M100VKA2(-ET/-ER).TH
PUZ-M100YKA2(-ET/-ER).TH PUZ-M125/140VKA2(-ET/-ER).TH
PUZ-M125/140YKA2(-ET/-ER).TH
Compressor model
SVB220FBGMT
SVB220FBAMT
MVB33FBVMC
Winding
Resistance
(Ω)
U-V
0.95
1.64
0.88
U-W
0.95
1.64
0.88
W-V
0.95
1.64
0.88
Содержание MR. SLIM PUZ-M100VKA2
Страница 17: ...17 OCH773 5 OUTLINES AND DIMENSIONS Unit mm ...
Страница 18: ...18 OCH773 6 WIRING DIAGRAM PUZ M100VKA2 ET ER TH ...
Страница 19: ...19 OCH773 PUZ M125VKA2 ET ER TH PUZ M140VKA2 ET ER TH ...
Страница 20: ...20 OCH773 PUZ M100YKA2 ET ER TH PUZ M125YKA2 ET ER TH PUZ M140YKA2 ET ER TH ...
Страница 115: ...115 OCH773 ...