Piping Length (one way)
Charged
Factory
Service Ref.
100 ft
110 ft
120 ft
130 ft
140 ft
150 ft
160 ft
165 ft
30 m
33 m
37 m
40 m
43 m
46 m
49 m
50 m
PUZ-HA42NKA
212 oz
218 oz
224 oz
230 oz
236 oz
242 oz
248 oz
255 oz
212 oz
6.0 kg
6.2 kg
6.5 kg
6.7 kg
6.9 kg
7.1 kg
7.2 kg
7.4 kg
180 ft
200 ft
210 ft
230 ft
245 ft
55 m
61 m
64 m
70 m
75 m
260 oz
272 oz
278 oz
290 oz
298 oz
7.7 kg
7.9 kg
8.2 kg
8.4 kg
6.4 kg
6.0 kg
For pipes longer than 100 ft, additional charge is required.
Service Ref.
Compressor model
(
'
)
Winding Registance
U-V
U-W
W-V
(at 68°F [20°C] )
PUZ-HA42NKA
ANB42FJTMT
0.188
0.188
0.188
5-1. REFILLING REFRIGERANT CHARGE (R410A: oz, kg)
5-2. COMPRESSOR TECHNICAL DATA
5
DATA
5-3. NOISE CRITERION CURVES
90
80
70
60
50
40
30
20
10
63
125
250
500
1000
2000
4000
8000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
OCT
A
VE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
μ
bar)
BAND CENTER FREQUENCIES, Hz
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
PUZ-HA42NKA
COOLING
MODE
HEATING
49
SPL(dB)
51
LINE
5 ft
3.3 ft
MICROPHONE
UNIT
GROUND
OCH567