
18
19
Start and finish of test run [For outdoor controller board]
•
Operation from the indoor unit
Execute the test run using the installation manual for the indoor unit.
•
Operation from the outdoor unit
By using the DIP switch SW on the control board of outdoor unit, test run can be started and finished, and its operation
mode (cooling/heating) can be set up.
1
Set the operation mode (cooling/heating) using SW-.
2
Turn on SW-1 to start test run with the operation mode set by SW-.
3
Turn off SW-1 to finish the test run.
•
There may be a faint knocking sound around the machine room after power is supplied,
but this is no problem with product because the linear expansion pipe is just moving to
adjust opening pulse.
•
There may be a knocking sound around the machine room for several seconds after com-
pressor starts operating. But this is not a problem with product because the check valve
itself generates the sound because pressure difference is small in the refrigerant circuit.
Note:
The operation mode cannot be changed by SW4-2 during test run. (To change test run mode, stop the unit by SW4-1,
change the operation mode and restart the test run by SW4-1.)
ON/OFF
TEMP
FAN
VANE
MODE
CHECK LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESET
SET
CLOCK
TEST
RUN
COOL
,
Test run [for IR wireless remote controller]
Measure an impedance between the power supply terminal block on
the outdoor unit and ground with a 00V Megger and check that it is
equal to or greater than 1.0M
"
.
1
Turn on the main power to the unit.
2
Press the
TEST RUN
button twice continuously.
(Start this operation from the turned off status of remote controller
display.)
TEST RUN
and current operation mode are displayed.
3
Press the
MODE
(
) button to activate
COOL
mode, then
check whether cool air is blown out from the unit.
4
Press the
MODE
(
) button to activate
HEAT
mode, then
check whether warm air is blown out from the unit.
5
Press the
FAN
button and check whether strong air is blown out
from the unit.
6
Press the
VANE
button and check whether the auto vane operates
properly.
7
Press the ON/OFF button to stop the test run.
Note:
• Point the remote controller towards the indoor unit receiver
while following steps
2
to
7
.
• It is not possible to run in FAN, DRY or AUTO mode.
OFF
1
2
ON
<SW4>
Stop
Operation
Cooling
Heating
Содержание Mr.Slim PUZ-HA30NHA2
Страница 95: ...95 ...