SERVICE MANUAL

CONTENTS

1. REFERENCE MANUAL ·································· 2
2. SAFETY PRECAUTION ·································· 2
3. FEATURES ······················································ 6
4. SPECIFICATIONS ··········································· 7
5. DATA ································································ 8
6. OUTLINES AND DIMENSIONS ···················· 10
7. WIRING DIAGRAM ·········································11
8. WIRING SPECIFICATIONS ··························· 12
9. REFRIGERANT SYSTEM DIAGRAM ·············· 16

10. TROUBLESHOOTING ··································· 17
11. EASY MAINTENANCE FUNCTION··············· 70
12. FUNCTION SETTING ···································· 73
13. MONITORING THE OPERATION DATA BY THE REMOTE CONTROLLER ············ 81
14. DISASSEMBLY PROCEDURE ······················ 91

No. OCH504

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS

R410A

July 2011

PUZ-HA30NHA4
PUZ-HA36NHA4

Outdoor unit

NOTE:
• This manual describes only 

service data of the outdoor 
units.

• RoHS compliant products have 

<G> mark on the spec name 
plate.

Outdoor unit

[model name]

PUZ-HA30NHA4

PUZ-HA36NHA4

[Service Ref.]

PUZ-HA30NHA4
PUZ-HA36NHA4

PARTS CATALOG (OCB504)

Содержание Mr.Slim PUZ-HA30NHA2

Страница 1: ... FUNCTION 70 12 FUNCTION SETTING 73 13 MONITORING THE OPERATION DATABYTHE REMOTE CONTROLLER 81 14 DISASSEMBLY PROCEDURE 91 No OCH504 SPLIT TYPE HEAT PUMP AIR CONDITIONERS R410A July 2011 PUZ HA30NHA4 PUZ HA36NHA4 Outdoor unit NOTE This manual describes only service data of the outdoor units RoHS compliant products have G mark on the spec name plate Outdoor unit model name PUZ HA30NHA4 PUZ HA36NHA4...

Страница 2: ...e Prepare the proper tools Prepare the proper protectors Provide adequate ventilation After stopping the operation of the air conditioner turn off the power supply beaker Discharge the condenser before the work involving the electric parts Precautions during the repair service Do not perform the work involving the electric parts with wet hands Do not pour water into the electric parts Do not touch...

Страница 3: ...hat can cause deterio ration of refrigerant oil etc Do not use refrigerant other than R410A If other refrigerant R22 etc is used chlorine in refrige rant can cause deterioration of refrigerant oil etc Use a vacuum pump with a reverse flow check valve Vacuum pump oil may flow back into refrigerant cycle and that can cause deterioration of refrigerant oil etc Use the following tools specifically des...

Страница 4: ...e 7 Refrigerant cylinder Only for R410A Top of cylinder Pink Cylinder with syphon 8 Refrigerant recovery equipment 1 Cautions for service 1 Perform service after recovering the refrigerant left in unit completely 2 Do not release refrigerant in the air 3 After completing service charge the cycle with specified amount of refrigerant 4 When performing service install a filter drier simultaneously Be...

Страница 5: ...Outside diameter mm Dimension A 0 0 4 Unit mm inch R410A R22 1 4 3 8 1 2 5 8 3 4 6 35 9 52 12 70 15 88 19 05 17 0 43 64 22 0 7 8 26 0 1 3 64 29 0 1 9 64 17 0 22 0 24 0 27 0 36 0 Nominal dimensions inch Flare nut dimensions Outside diameter mm Dimension B Unit mm inch R410A R22 Gauge manifold Charge hose Gas leak detector Refrigerant recovery equipment Refrigerant cylinder Applied oil Safety charge...

Страница 6: ...ceiver always control the optimal refrigerant level regardless of the length max 100ft 30m and mim 16ft 5m of piping The additional refrigerant charging work during installation often causes problems It is completely eliminated by chargelss system This unique system improves the quality and reliability of the work done It also helps to speed up the installation time PUZ HA30NHA4 PUZ HA36NHA4 Outdo...

Страница 7: ... 40 Airflow m3 min 100 CFM 3530 Sound level Cooling dB 52 Heating dB 53 Protection devices HP switch LP switch Discharge thermo Dimension W mm 950 D mm 330 30 H mm 1350 W in 37 12 32 D in 13 1 3 16 H in 53 5 32 Weight kg lbs Refrigerant Charged kg 5 5 R410A lbs 12 Control Linear expansion valve Oil Model Ether FV50S Charged L 1 4 oz 45 Refrigerant Pipe size OD mm 9 52 piping Liquid in 3 8 Pipe siz...

Страница 8: ...ipe than 100 ft additional charge is required Service Ref Compressor model Winding Registance U V U W W V at 20 C 68 F PUZ HA30NHA4 PUZ HA36NHA4 ANB33FJEMT 0 188 0 188 0 188 5 1 REFILLING REFRIGERANT CHARGE R410A oz kg 5 2 COMPRESSOR TECHNICAL DATA 5 DATA 5 3 NOISE CRITERION CURVES 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE O...

Страница 9: ...perature DB C Intake air temperature WB C Discharge air temperature DB C side Outdoor Intake air temperature DB C Intake air temperature WB C side Indoor Intake air temperature DB F Intake air temperature WB F Discharge air temperature DB F side Outdoor Intake air temperature DB F Intake air temperature WB F SHF BF PKA A30KA4 COOLING HEATING 12 2 A 2 58 0 87 70 8 44 4 10 5 7 6 374 126 159 112 51 2...

Страница 10: ...ht trunking hole Knockout Conduit hole 2 27 1 1 16 Knockout 9 2 3 5 8 92 3 5 8 65 2 9 16 45 1 25 32 40 1 9 16 27 1 1 16 55 2 3 16 23 29 32 73 2 7 8 63 2 1 2 Front piping hole Knockout Front trunking hole Knockout Conduit hole 2 27 1 1 16 Knockout 9 2 3 5 8 371 14 19 32 330 13 30 1 3 16 175 6 7 8 600 23 5 8 175 6 7 8 42 1 21 32 66 2 5 8 950 37 13 32 322 12 11 16 1350 53 5 32 635 25 19 3 4 417 16 13...

Страница 11: ...ut Fuse T6 3AL250V X51 X52 X55 Relay SS Connector Connection for Option SYMBOL M NET ADAPTER NAME TB7 CN5 CND CN2M SW1 SW11 SW12 LED1 LED2 LED3 LED4 LED5 Terminal Block M net connection Connector Transmission Connector Power Supply Connector M NET communication Switch Status of communication Switch Address setting 1s digit Switch Address setting 10s digit LED Power Supply DC5V LED Connection to Ou...

Страница 12: ...d Max 80m 262ft 2 The 10 m 30 ft wire is attached in the remote controller accessory Max 1500 ft 3 The figures are NOT always against the ground S3 terminal has DC 24 V against S2 terminal However between S3 and S1 these terminals are NOT electrically insulataed by the transformer or other device 4 Use earth leakage breaker NV 1 Wiring size must comply with the applicable local and national code 2...

Страница 13: ...ry Max 500 m 1500 ft 3 The figures are NOT always against the ground Notes 1 Wiring size must comply with the applicable local and national code 2 Use copper supply wires 3 Use wires rated 300V or more for the power supply cables 4 Install an earth longer than other cables Indoor unit model Indoor unit power supply Minimum circuit ampacity Maximum rating of overcurrent protective device Indoor uni...

Страница 14: ...e non polar 2 cores is arranged in addition to the wiring for A control 4 Ground only one of any appliances through M NET transmission wire shield wire Communication error may occur due to the influence of electromagnetic noise Ed error will appear on the LED display of outdoor unit 0403 error will appear on the central control remote controller If there are more than 2 grounding spots on the shie...

Страница 15: ...esses are 00 1 234 5 6 7 8 9 0 1 23 4 5 6 7 8 9 0 1 23 4 5 6 7 8 9 0 1 23 4 5 6 7 8 9 0 1 23 4 5 6 7 8 9 0 1 23 4 5 6 7 8 9 0 1 2 50 M NET Address No Setting example Switching setting SW11 ones digit SW12 tens digit OFF ON 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5...

Страница 16: ...e remote controller If CENTRALLY CONTROLLED is displayed the refrigerant recovering pump down cannot be completed normally 2 After the liquid stop valve is closed set the SWP switch on the control board of the outdoor unit to ON The compressor outdoor unit and ventilators indoor and outdoor units start operating and refrigerant collecting operation begins LED1 and LED2 on the control board of the ...

Страница 17: ...no abnormality concerning of parts such as electrical component controller board remote controller and etc Re check the abnormal symptom Conduct trouble shooting and ascertain the cause of the trouble according to 10 5 Troubleshooting by inferior phenomena Continue to operate unit for the time being if the cause is not ascertained There is no abnormality concerning of parts such as electrical comp...

Страница 18: ...ernately F1 After startup is displayed green once and red twice blink alternately F3 F5 F9 After startup is displayed green twice and red once blink alternately EA Eb After startup is displayed only green lights up 00 After startup is displayed only green lights up 00 indicates digital display 2 Press TEST button twice 1 Turn on the main power supply 3 Press OPERATION SWITCH button 4 Press AIR DIR...

Страница 19: ...est run To change test run mode stop the unit by SW4 1 change the operation mode and restart the test run by SW4 1 ON OFF TEMP FAN VANE MODE CHECK LOUVER TEST RUN AUTO STOP AUTO START h min RESET SET CLOCK TEST RUN COOL Test run for IR wireless remote controller Measure an impedance between the power supply terminal block on the outdoor unit and ground with a 500V Megger and check that it is equal...

Страница 20: ...or unit s installation manual or service handbook Reset the error history Display the error history in the diagnosis result display screen see step Error code 2 or 4 digits Alternating Display Address 3 digits or unit number 2 digits The refrigerant address will begin to blink approximately 3 seconds after being selected and the self diagnosis process will begin Unit number or refrigerant address ...

Страница 21: ...isplay content will change as shown below Press the FILTER button to start self diagnosis Remote controller self diagnosis result When the remote controller is functioning correctly Check for other possible causes as there is no problem with the remote controller When the remote controller malfunctions Error display 1 NG blinks The remote controller s transmitting receiv ing circuit is defective T...

Страница 22: ...ncelled Procedure 1 Press the CHECK button twice 2 Press the temperature buttons 3 Point the remote controller at the sensor on the indoor unit and press the HOUR button 4 Point the remote controller at the sensor on the indoor unit and press the ON OFF button Malfunction diagnosis method at maintenance service 10 3 4 Malfunction diagnosis method by IR wireless remote controller In case of trouble...

Страница 23: ...TOR lamp blinks Check code Number of times IR wireless remote controller Wired remote controller Errors detected by unit other than indoor unit outdoor unit etc Symptom Remark 1 Indoor outdoor unit communication error 2 Transmitting error Outdoor unit 3 Open short of outdoor unit thermistors 4 Compressor overcurrent interruption When compressor locked 5 Abnormal high discharging temperature 49C wo...

Страница 24: ...B1 2 Check following items a Connection of power supply terminal block TB1 b Connection of terminal on outdoor power circuit board Disconnection of connector TABT or TABS Refer to 10 9 3 Check connection of the connector CNDC on the outdoor controller circuit board Check connection of the connector CNDC on the outdoor power circuit board Refer to 10 9 4 Check connection of reactor DCL Check connec...

Страница 25: ...is S1 S2 S3 3 Check the number of indoor units that are connected to one outdoor unit If EA is detected 4 6 Turn the power off once and on again to check Replace outdoor controller circuit board indoor controller board or indoor power board if abnormality occurs again 7 Check if refrigerant addresses SW1 3 to SW1 6 on outdoor controller circuit board are overlapping in case of group control system...

Страница 26: ...r on LED display SW2 on A Control Service Tool Refer to 10 10 4 6Turn the power off and check F5 is displayed when the power is on again When F5 is displayed refer to Judgment and action for F5 7 Check linear expansion valve Refer to 10 6 8 Replace outdoor controller board Case U2 1102 High discharging temperature 1 Abnormal if discharge temperature thermistor TH4 exceeds 125 257 F or 110 230 F co...

Страница 27: ... operation Open detection of thermistors TH3 TH32 TH33 and TH6 is inoperative for 10 seconds to 10 minutes after compressor starting and 10 minutes after and during defrosting WCheck which unit has abnormality in its thermistor by switching the mode of SW2 PAC SK52ST Refer to 11 10 1 Check connection of connector TH3 TH 32 TH33 TH7 6 on the outdoor controller circuit board Check connection of conn...

Страница 28: ...ssor wiring 3 Defective noise filter circuit board 4 Disconnection or loose connec tion of CN52C 5 Defective ACT module 6 Defective ACT module drive circuit of outdoor power circuit board 7 Disconnection or loose connec tion of CNAF 8 Defective 52C drive circuit of noise filter circuit board 9 Disconnection or loose con nection of CN5 on the outdoor power circuit board 0 Disconnection or loose con...

Страница 29: ... any trans mission from indoor unit of refrigerant address 0 for 3 minutes Error code E0 2 Abnormal if sub remote controller could not receive any signal for 2 minutes Error code E0 1 Abnormal if indoor controller board can not receive any data normally from remote controller board or from other indoor controller board for 3 minutes Error code E4 2 Indoor controller board cannot receive any signal...

Страница 30: ...same time compares the data and when detecting it judges different data to be abnormal 30 continuous times Error code E5 1 Set a remote controller to main and the other to sub 2 Remote controller is connected with only one indoor unit 3 The address changes to a separate setting 4 6 Diagnose remote controller a When RC OK is displayed remote con trollers have no problem Turn the power off and on ag...

Страница 31: ...ith outdoor controller circuit board after connecting A Control Service Tool PAC SK52ST 23Check converse connection of extension pipe or converse wiring of indoor outdoor unit connecting wire 1 2 3 4 5 6 ON OFF 1 2 3 4 5 6 ON OFF 1 2 3 4 5 6 ON OFF 1 2 3 4 5 6 ON OFF A Control Service Tool SW2 setting Temperature display of indoor liquid pipe Indoor 1 Temperature display of indoor liquid pipe Indo...

Страница 32: ...ly because of noise or etc Note The address and attribute displayed at remote controller indicate the con troller that detected abnormality 1 Transmission processor could not transmit signal because short cycle voltage of noise and the like have entered into transmission wire continuously 2 Transmission quantity has increased and transmission is not possible because there was wiring mistake of ter...

Страница 33: ...itch of abnormality gener ated address 3 Check disconnection or looseness of abnor mality generated or abnormality detected transmission wire terminal block and con nector 4 Check if tolerance range of transmission wire is not exceeded 5 Check if type of transmission wire is correct or not If there were some troubles of 1 5 above repair the defective then turn off the power supply of outdoor unit ...

Страница 34: ...same refriger ant system with LOSSNAY is turn off or within 2 minutes of restart abnormality is detected 3 Contact failure of transmis sion wire of indoor unit of LOSSNAY 4 Disconnection of transmission connector CN2M of indoor unit 5 Defective transmitting receiv ing circuit of indoor unit or LOSSNAY 7 If displayed address or attribute is non existent 1 The unit of former address does not exist a...

Страница 35: ...heck LED3 on indoor controller board 1 When LED3 is not blinking Check indoor outdoor connecting wire for miswiring Converse wiring of S1 and S2 or break of S3 wiring 2 When LED3 is blinking Indoor outdoor connecting wire is nor mal 4 Check LED display on outdoor controller circuit board Refer to 10 10 Check protection device connector 63L and 63H for contact failure Refer to 10 9 Error Code Abnor...

Страница 36: ...f by the remote controller 12 Normal operation For protection of compressor 12 Normal operation 4 Even controlling by the IR wireless remote controller no beep is heard and the unit does not start operat ing Operation display is indicated on the IR wireless remote controller 1 The pair number settings of the IR wireless remote controller and indoor controller board are mismatched 1 Check the pair ...

Страница 37: ...osis after turning on the main power Normal The start up diagnosis will be over in around 2 minutes Miswiring of indoor outdoor connecting wire Breaking of indoor outdoor connecting wire S3 Defective indoor controller board Defective outdoor controller circuit board Refer to Self diagnosis action table in order to solve the trouble In case of communication errors the display of remote controller m...

Страница 38: ...iring of the outdoor unit Check if the wiring is bad Check if the fuses are blown The fuses on the outdoor controller circuit board will be blown when the indoor outdoor connecting wire short circuits Bad wiring of the outdoor controller board The fuses on the outdoor controller circuit board are blown Check if miswiring breaking or poor contact is causing this problem Indoor outdoor connecting wi...

Страница 39: ...rd Replace the outdoor controller circuit board Normal Only the unit which has the refrigerant address 0 supplies power to the remote controller Set the refrigerant address to 0 In case of the multiple grouping system recheck the refrigerant address again Defective indoor power board Replace the indoor power board Defective outdoor power circuit board Replace the outdoor power circuit board Defect...

Страница 40: ...ntact of the remote controller wire Check the voltage of the terminal block TB5 connecting the remote controller wire If it is not between DC 10V and DC16V the indoor controller board must be defective The remote controller wire short circuits Check if the remote controller wire is short circuited Defective indoor controller board Replace the indoor controller board Diagnosis flow Cause Inspection...

Страница 41: ...ice to clear FILTER from the display See the operation manual that came with the product for how to clean the filters STANDBY is displayed on the screen This is displayed when the unit starts HEAT operation when the thermostat puts the compressor in operation mode or when the outdoor unit ends DEFROST operation and returns to HEAT operation The display will automatically disappear around 10 minute...

Страница 42: ... outdoor unit is controlling the airflow amount in order to keep the optimum operating condition A sound similar to water flowing is heard from the unit This is not a malfunction This is the sound which is heard when the refrigerant is flowing inside the indoor unit The fan speed doesn t match the setting of the remote controller in HEAT operation The up down vane will be automatically set to hori...

Страница 43: ...d The airflow direction doesn t change Up down vane left right louver 1 Check if the vane is set to a fixed position Check if the vane motor connector is removed 2 Check if the air conditioner has a function for switching the air direction 3 If the air conditioner doesn t have that function NOT AVAILABLE will be displayed on the remote controller when AIR DIRECTION or LOUVER button is pressed Some...

Страница 44: ...r drips down Heating water drips down from the heat exchanger Use optional parts Drain Socket and Drain pan if these water needs to be collected and drained out for once Water or moisture is expelled from the outdoor unit Batteries are being exhausted Replace them and press the reset button of remote controller The display of the IR wireless remote controller gets dim or doesn t come on The indoor...

Страница 45: ...al Open or short Measure the resistance between the terminals with a tester Ambient temperature 20 68 F Solenoid valve coil Four way valve 21S4 Motor for compressor MC Linear expansion valve LEV A LEV B LEV C Normal Abnormal Open or short Disconnect the connector then measure the resistance with a tester Winding temperature 20 68 F Refer to next page Fan motor MF1 MF2 1435 150 0 188 Measure the re...

Страница 46: ...ctor CNF1 2 Fuse check Check the fuse F5 on outdoor controller board Power supply check Remove the connector CNF1 2 Measure the voltage in the outdoor controller circuit board TEST POINT VDC between 1 and 4 of the fan connector VDC DC250 330V TEST POINT VCC between 5 and 4 of the fan connector VCC DC15V Wiring recovery Replace outdoor controller board Replace the fan motor Replace outdoor controll...

Страница 47: ... 20 30 40 50 20 10 0 10 20 30 40 50 4 14 32 50 68 86 104122 F Temperature Resistance k 500 400 300 200 100 0 25 50 75 100 120 77 122 167 212 248 F Temperature Resistance k 0 32 F 180k 25 77 F 50k 50 122 F 17k 70 158 F 8k 90 194 F 4k Medium temperature thermistor Thermistor Heatsink TH8 200 150 100 50 0 25 50 75 100 110 125 77 122 167 212 230 257 F Temperature Resistance k Thermistor R0 15k 3 B con...

Страница 48: ...s locked sound can be heard No sound is heard when the pulse number moves from B to A in case coil is burnt out or motor is locked by open phase Sound can be detected by placing the ear against the screw driv er handle while putting the screw driver to the linear expansion valve LEV M 1 6 4 4 3 2 1 1 Gray Orange Red Yellow Black 3 4 5 6 Connector LEV A LEV B LEV C DC12V Outdoor controller board Dr...

Страница 49: ...er to main body At this time be careful that stress is not added to lead wire and main body is not wound by lead wire If the stopper is not firmly attached to main body coil may be detached from the main body and that can cause defective operation of lin ear expansion valve To prevent piping stress be sure to attach the coil holding the main body of linear expansion valve firmly Otherwise pipe may...

Страница 50: ...g emergency operation the air conditioner will continuously be operated by supplying power and stopping it It can not be turned on or off by remote control and temperature control is not possible 4 Do not perform emergency heating operation for an extended period of time If the outdoor unit starts defrosting during this period cold air will blow out from the indoor unit 5 Do not perform emergency ...

Страница 51: ...5 41 F 5 41 F 7 45 F 5 30degC 54degF 5degC 9degF 1 1 1 1 2 Remarks 1 If the thermistor temperature data is normal not open short that data is loaded into the control as valid data If the unit enters emergency operation because TH values have become mismatched setting the thermistors to open short corrects the settings 2 If one thermistor is set to open short the values for each will be different E...

Страница 52: ...rmistor Outdoor 2 phase pipe CNDC 280V DC 1 3 Outdoor power circuit board VFG TEST POINT 4 Voltage between right pins of PC5C and PC5D pin 3 and pin 4 Same as CNF17 4 VSP TEST POINT 3 Voltage between pins of C5A C5B DC 0V when stopped DC 1 6 5V when operated SW7 Demand control setting CN51 External signal output Compressor operat ing signal Abnormal signal LEV A B C Linear expansion valve SWP Pump...

Страница 53: ...er circuit board CN5 LO NO Voltage of 208 230V AC is output Connect to the outdoor power circuit board TABS TABT Outdoor noise filter circuit board PUZ HA30NHA4 PUZ HA36NHA4 CN52C 52C driving signal Connect to the outdoor controller circuit board CN52C E2 Connect to the earth LI NI Voltage of 208 230V AC is input Connect to the terminal block TB1 RS1 ...

Страница 54: ...ct to the outdoor controller circuit board TABS TABT Connect to the outdoor noise filter circuit board Voltage among phases 208 230V AC Brief check of POWER MODULE W Usually they are in a state of being short circuited if they are broken Measure the resistance in the following points connectors etc If they are short circuited it means that they are broken 1 Check of diode bridge TABP1 TABS TABN1 T...

Страница 55: ...is in trouble and Io open less than 1 1 The unit does not operate can not be switched ON and L2 short 100k 1M 1 The breaker operates open W1 1 The unit does not operate can not be switched ON 2U9 Abnormal stop W2 P and L2 short 100k 1M 1 The breaker operates open W1 1 The unit does not operate can not be switched ON 2U9 Abnormal stop W2 P and Io short 100k 1M 1 The breaker operates open W1 1 The u...

Страница 56: ...witch Dip switch Push switch SW1 1 2 No Function Effective timing Action by the switch operation Forced defrost 1 Start Normal When compressor is working in heating operation 1 Abnormal history clear Refrigerant address setting When power supply ON Clear Normal off or operating SWP 6 5 4 3 Under suspension Pump down Start Normal SW4 SW8 1 2 1 2 3 Test run Operating OFF Under suspension Test run mo...

Страница 57: ...ays Setting of demand control 3 1 2 SW7 1 SW7 2 OFF 0 Operation stop 75 50 OFF ON OFF OFF ON Power consumption Demand switch ON Model select Following SW5 6 reference CN31 Types Connector Function Effective timing Connector Start Short Open Action by open short operation Emergency operation When power supply ON Normal 2 Function of connector w2 Power failure automatic recovery can be set by either...

Страница 58: ... to release Low level sound priority mode and normal operation b On demand control Local wiring Demand control is available by external input In this mode power consumption is decreased within the range of usual 0 100 How to wire Basically the wiring is same with a Connect an SW 1 which is procured locally between Orange and Red 1 and 3 of the adapter for external signal input PAC SC36NA and insul...

Страница 59: ...ler transmitting error is detected by remote controller Remote controller signal receiving error is detected by indoor unit Remote controller transmitting error is detected by indoor unit Serial communication error Communication between outdoor controller board and outdoor power board Communication between outdoor controller board and M NET P C board Communication error of M NET system 1 Error cod...

Страница 60: ...troller board and connector CN3 on outdoor power board are not disconnected Measure resistance value of outdoor thermistors Abnormality of heatsink temperature Check if indoor outdoor units have a short cycle on their air ducts Measure resistance value of outdoor thermistor TH8 Check the outdoor fan motor Check if connector TH3 on outdoor controller board is disconnected Abnormality of voltage Che...

Страница 61: ...hen the display blinks Inspection code is displayed when compressor stops due to the work of protection devices Display Contents to be inspected When power is turned on F3 F5 F9 E8 E9 EA Eb EC E0 E7 63L connector red is open 63H connector yellow is open 2 connectors 63H 63L are open Indoor outdoor communication error Signal receiving error Outdoor unit Indoor outdoor communication error Transmitti...

Страница 62: ... When it is 100 hours or more hundreds digit tens digit and ones digit are displayed by turns Example When 2450 hours 245 10 hours 0 5 secs 0 5secs 2 secs 1 ON 2 3 4 5 6 1 ON 2 3 4 5 6 1 ON 2 3 4 5 6 Compressor operating current 0 50 LEV A opening pulse 0 480 0 50 wOmit the figures after the decimal fractions 0 480 When it is 100 pulse or more hundreds digit tens digit and ones digit are displayed...

Страница 63: ...ory 2 Alternate display of error unit number and code 37 327 3 164 When the temperature is 100 F or more the hundreds digit tens digit and ones digit are displayed by turns Example When 130 F 0 5 secs 0 5secs 2 secs F A Code display Code display 0 50 When no error history 0 and are displayed by turns When no error history 0 and are displayed by turns 1 ON 2 3 4 5 6 Thermostat ON time 0 999 Test ru...

Страница 64: ...ils 0 H P 1 Cooling only 0 Single phase 2 3 phase Setting details Defrosting switch Display details 0 Normal 1 For high humidity Example When heat pump 3 phase and defrosting normal are set up 20 is displayed 1 ON 2 3 4 5 6 1 ON 2 3 4 5 6 Indoor pipe temperature Cond Eva TH5 1 Indoor 1 38 190 38 190 39 88 When the temperature is 0 F or less and temperature are displayed by turns F 38 190 39 88 Whe...

Страница 65: ...DC bus voltage 180 370 180 370 When it is 100V or more hundreds digit tens digit and ones digit are displayed by turns V 1 ON 2 3 4 5 6 1 ON 2 3 4 5 6 1 ON 2 3 4 5 6 1 ON 2 3 4 5 6 SW2 setting 1 ON 2 3 4 5 6 Display detail Explanation for display Unit F 1 ON 2 3 4 5 6 1 ON 2 3 4 5 6 1 ON 2 3 4 5 6 Indoor setting temperature 62 86 Outdoor pipe temperature 2 phase TH6 38 190 Outdoor heatsink tempera...

Страница 66: ...tdoor unit Postponement code display Blinking During postponement Lighting Cancellation of postponement 00 is displayed in case of no postponement Code display Error code history 3 Oldest Alternate display of abnormal unit number and code When no error history 0 and are displayed by turns 3 Outdoor pipe temperature Liquid TH3 TH32 6 Outdoor pipe temperature 2 phase TH6 7 Outdoor outside temperatur...

Страница 67: ...re is 0 F or less and temperature are displayed by turns Example When 15 F 0 5 secs 0 5secs 2 secs 15 Outdoor pipe temperature 2 phase TH6 on error occurring 38 190 38 190 39 88 C When the temperature is 0 F or less and temperature are displayed by turns Example When 15 F 0 5 secs 0 5secs 2 secs 15 Outdoor ambient temperature TH7 on error occurring 38 190 38 190 39 88 C When the temperature is 0 F...

Страница 68: ...ervoltage error Undervoltage error Input current sensor error L1 or L2 phase open error Abnormal power synchronous signal ACTM error Undervoltage Display examples for multiple errors Overvoltage 01 Undervoltage 02 03 Undervoltage 02 Power sync signal error 08 0A L1 phase open error 04 ACTM error 20 24 Power circuit board Controller circuit board Controller circuit board Power circuit board Check C...

Страница 69: ...2 1 4 8 2 The tens digit The ones digit In this digit the total number of activated control is displayed Preventive control for excessive temperature rise of discharge temperature Preventive control for excessive temperature rise of condensing temperature Frosting preventing control Preventive control for excessive temperature rise of heatsink Example The following controls are activated Primary c...

Страница 70: ... air conditioner stopped skip to step 4 Fixed Hz operation The operating frequency can be fixed to stabilize operation of inverter model If the air conditioner is currently stopped start it by this operation 2 Press the MODE button to select the desired operation mode Display 3 Press the FILTER button to confirm the setting Display Waiting for stabilization HEAT STABLE MODE STABLE MODE CANCEL COOL...

Страница 71: ...rature Comp discharge temperature Outdoor ambient temperature INDOOR UNIT INLET TEMP INDOOR UNIT H EXC TEMP INDOOR UNIT FILTER USE H Indoor room temperature Heat exchanger temperature Filter operating time 12 340 hours Display Waiting for response Flashing After approx 10 seconds 1 1 Refrigerant address 00 Twin Refrigerant address 00 Outdoor unit Indoor unit 02 Indoor unit 01 Outdoor unit Remote c...

Страница 72: ...heat exchanger temperature Indoor intake air temperature Cool Classification Item Result Inspection Temperature difference Heat Inspection Temperature difference Stable Unstable F F Stable Unstable F F Fixed Hz operation may not be possible under the following tempera ture ranges A In cool mode outdoor intake air temperature is 104 For higher or indoor intake air temperature is 73 F or lower B In ...

Страница 73: ...mote controller RF thermostat Function Settings Setting No Initial setting when sent from the factory Remarks 12 1 UNIT FUNCTION SETTING BY THE REMOTE CONTROLLER Each function can be set according to necessity using the remote controller The setting of function for each unit can only be done by the remote controller Select function available from the table 1 1 Functions available when setting the ...

Страница 74: ...able Not available PLA BA Initial setting Factory setting Not available 4 Way cassette PLA BA PKA HA PKA HAL PKA KA PKA KAL Ceiling Suspended PCA KA Mode No Wired remote controller RF thermostat Wall mounted 2 Functions available when setting the unit number to 01 03 or AL 07 in the case of the IR wireless remote controller When setting functions for an indoor unit in an independent system set the...

Страница 75: ... setting Press Specified indoor unit FAN operation Change refrigerant address or unit No Switch to function setting mode Press and at the same time with stop the remote controller 12 1 1 Selecting functions using the wired remote controller First try to familiarize yourself with the flow of the function selection procedure In this section an example of setting the room temperature detection positi...

Страница 76: ... and blinks in the unit number display area and the refrigerant address display area also blinks there are no units that corre spond to the selected unit number In this case the refrigerant address and unit number may be incorrect so repeat steps and to set the correct ones When grouping different refrigerant systems if an indoor unit other than the one to which the refrigerant address has been se...

Страница 77: ...tton once to set 50 Direct the IR wireless remote controller toward the receiver of the indoor unit and press the button 3 Set the unit number Press the temp button to set the unit number Press 01 to specify the indoor unit whose unit number is 01 Direct the IR wireless remote controller toward the receiver of the indoor unit and press the min button If a unit number that cannot be recognized by t...

Страница 78: ... value The automatic mode is displayed when the operation mode is selected OFF The automatic mode is not displayed when the operation mode is selected 4 3 Mode selection setting 1 Remote controller main sub setting To switch the setting press the ON OFF button Main The controller will be the main controller Sub The controller will be the sub controller 2 Use of clock setting To switch the setting ...

Страница 79: ...ed Initial setting value The automatic mode is not displayed when the operation mode is selected The temperature range limit is not active Initial setting value The temperature range can be changed on cooling dry mode The temperature range can be changed on heating mode The temperature range can be changed on automatic mode The remote controller will be the main controller Initial setting value Th...

Страница 80: ...ODEL SELECT blinks 2 Press the AUTO START button F blinks 3 Press the button C blinks 4 Press the set button with something sharp at the end MODEL SELECT is lighted for 3 seconds then turned off ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOUVER MODE CHECK RESET SET CLOCK MODEL SELECT NOT AVAILABLE SWING CHECK FAN TEST RUN F C AMPM STOP START AMPM COOL DRY AUTO FAN HEAT ...

Страница 81: ... 4 Press the CLOCK buttons and to set the desired request code No 5 Press the FILTER button to perform data request The requested data will be displayed at in the same way as in maintenance mode Data collected during operation of the remote controller will be displayed The collected data such as temperature data will not be updated automatically even if the data changes To display the updated data...

Страница 82: ...e 4 deg correction Indoor unit Intake air temperature Unit No 2 Heat mode 4 deg correction Indoor unit Intake air temperature Unit No 3 Heat mode 4 deg correction Indoor unit Intake air temperature Unit No 4 Heat mode 4 deg correction Indoor unit Liquid pipe temperature Unit No 1 Indoor unit Liquid pipe temperature Unit No 2 Indoor unit Liquid pipe temperature Unit No 3 Indoor unit Liquid pipe tem...

Страница 83: ... unit Error postponement history 2 previous Outdoor unit Error postponement history 3 last but one 0 255 Refer to14 2 1 DetailContentsinRequestCode Refer to14 2 1 DetailContentsinRequestCode Refer to14 2 1 DetailContentsinRequestCode Refer to14 2 1 DetailContentsinRequestCode 0000 Not connected Examples Ver 5 01 Auxiliary information displayed after version information Examples Ver 5 01 A000 Displ...

Страница 84: ... Error history 3 third to last Abnormal thermistor display TH3 TH6 TH7 TH8 Operation mode at time of error Compressor Operating current at time of error Compressor Accumulated operating time at time of error Compressor Number of operation times at time of error Discharge temperature at time of error Outdoorunit Liquidpipe1temperature TH3 attimeoferror Outdoor unit Liquid pipe 2 temperature at time...

Страница 85: ...g time Fan motor ON time Indoor fan output value Sj value Indoor fan output value Pulsation ON OFF Indoor fan output value duty value Indoor unit Model setting information Indoor unit Capacity setting information Indoor unit SW3 information Wireless pair No indoor control board side setting Indoor unit SW5 information Indoor unit Microcomputer version information Indoor unit Microcomputer version ...

Страница 86: ...isplay area C 4 Relay output state Operation mode Indoor unit Control state Request code 50 Data display Operation mode Display Operation mode 0 STOP FAN C COOL DRY H HEAT d DEFROST Relay output state Display Power currently Compressor Four way valve Solenoid valve supplied to compressor Unit No 4 state Unit No 3 state Unit No 2 state Unit No 1 state Display State 0 Normal 1 Preparing for heat ope...

Страница 87: ...lay SV1 Four way valve Compressor 0 1 2 3 4 5 6 7 8 9 A b C d E F ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON Actuator output state Display 52C SV2 SS 0 1 2 3 4 5 6 7 ON ON ON ON ON ON ON ON ON ON ON ON Error content U9 Request code 55 Data display Error content Error content 0 0 Error content Detected Display Overvoltage Undervoltage L1 phase Po...

Страница 88: ...etting display Request code 70 Data display Capacity 10 18 9 12 11 24 14 30 20 36 25 42 Outdoor unit Setting information Request code 71 Data display Setting information Setting information 0 0 Setting information Display Defrost mode 0 Standard 1 For high humidity Setting information Display Single Heat pump three phase cooling only 0 Single phase Heat pump 1 Cooling only 2 Three phase Heat pump ...

Страница 89: ...0 0 1 1 1 1 0 0 1 1 1 0 1 0 1 1 1 1 1 0 1 1 1 0 0 1 1 1 1 1 0 1 1 1 1 0 1 1 1 1 1 1 1 1 1 1 1 Outdoor unit switch setting display SW1 to SW10 except SW3 Request codes 73 to 82 0 Switch OFF 1 Switch ON Data display SW5 1 2 3 4 0 0 0 0 00 00 1 0 0 0 00 01 0 1 0 0 00 02 1 1 0 0 00 03 0 0 1 0 00 04 1 0 1 0 00 05 0 1 1 0 00 06 1 1 1 0 00 07 0 0 0 1 00 08 1 0 0 1 00 09 0 1 0 1 00 0A 1 1 0 1 00 0b 0 0 1 ...

Страница 90: ...1b 3b 1C 3C 1d 3d 1E 3E 1F 3F Indoor unit Capacity setting information Request code 163 Data display 0 0 See the table on the right Display Capacity setting state Display Capacity setting state 00 10 42 01 11 02 12 03 13 04 14 05 15 06 12 16 07 17 08 18 09 18 19 0A 1A 0b 24 1b 0C 1C 0d 30 1d 0E 1E 0F 36 1F Display Pair No setting state 00 No 0 01 No 1 J41 disconnected 02 No 2 J42 disconnected 03 N...

Страница 91: ...or pipe thermistor Discharge thermistor Outdoor 2 phase pipe thermistor Outdoor high pressure switch low pressure switch solenoid valve coil Four way valve Then remove a screw 4 8 from the valve bed to remove the lead wire Pull out the disconnected wire from the electrical parts box Diagram symbol in the connector housing Fan motor CNF1 CNF2 Linear expansion valve LEV A LEV B and LEV C Thermistor ...

Страница 92: ...en clamps for the lead wire in the rear of the electrical parts box See Photo 4 and separator See Photo 6 4 Pull out the thermistor Discharge TH4 from the sensor holder Photo 7 6 Removing the thermistor Outdoor pipe TH3 TH32 TH33 1 Remove the service panel See Figure 1 2 Disconnect the connectors TH3 white and TH32 black TH33 yellow on the controller circuit board in the electri cal parts box 3 Lo...

Страница 93: ...l See Figure 1 2 Remove the top panel See Figure 1 3 Remove 3 valve bed fixing screws 4 10 and 4 ball valve and stop valve fixing screws 5 16 then remove the valve bed 4 Remove 4 right side panel fixing screws 5 10 in the rear of the unit then remove the right side panel 5 Remove the linear expansion valve coil 6 Recover refrigerant 7 Remove the welded part of linear expansion valve Note 1 Recover...

Страница 94: ...ixing screws 5 10 and remove the front cover panel See Photo 3 4 Remove 2 back cover panel fixing screws 5 10 and remove the back cover panel 5 Remove the electrical parts box See Photo 3 6 Remove 3 valve bed fixing screws 4 10 and 4 ball valve and stop valve fixing screws 5 16 then remove the valve bed 7 Remove 3 right side panel fixing screws 5 10 in the rear of the unit then remove the right si...

Страница 95: ...95 ...

Страница 96: ... MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN CCopyright 2011 MITSUBISHI ELECTRIC ENGINEERING CO LTD Distributed in Jul 2011 No OCH504 Made in Japan New publication effective Jul 2011 Specifications subject to change without notice ...