79
Outdoor power circuit board
PUHZ-ZRP100YKAR1
PUHZ-ZRP125YKAR1
PUHZ-ZRP140YKAR1
Brief Check of POWER MODULE
* Usually, they are in a state of being short-circuited if they are broken.
Measure the resistance in the following points (connectors, etc.).
If they are short-circuited, it means that they are broken.
1. Check of DIODE MODULE
L1 - P1 , L2 - P1 , L3 - P1 , L1 - N1 , L2 - N1 , L3 - N1
2. Check of DIP-IPM
P2 - U , P2 - V , P2 - W , N2 - U , N2 - V , N2 - W
Note: The marks L1 , L2 , L3 , N1 , N2 , P1 , P2 , U , V and W
shown in the diagram are not actually printed on the board.
CN5
Detection of primary
current (Connect to
the outdoor noise filter
circuit board (CNCT))
CN4
Connect to the
outdoor controller
circuit board (CN4)
CN2
Connect to the outdoor controller circuit board (CN2)
1
-
5
: Power circuit board
→
Transmitting
signal to the controller board (0-5V DC)
2
-
5
: Zero cross signal (0-5V DC)
3
-
4
: Not used
6
-
5
: 16V DC
7
-
5
: 16V DC
[
5
: –
1
,
2
,
6
,
7
: + ]
CN7
Connect to the
outdoor converter
circuit board (CN7)
TB-U, TB-V, TB-W
Connect to the compressor (MC)
Voltage among phases:
10V-400V AC
TB-N
Connect to the CK capacitor
Diode module
U
P2
V
W
N2
L3
N1
L1
P1
L2
DIP-IPM
TAB connector
on X52CA
Connect to the
RS resistor
CN6
Thermistor
<Heat sink> (TH8)
TB-L1,
TB-L2,
TB-L3
Connect to the
outdoor converter
circuit board
(L1-OU, L2-OU,
L3-OU)
400V AC
L3OUT-L3IN
Lead connect
OCH527B