76
Outdoor power circuit board
PUHZ-ZRP60VHA
PUHZ-ZRP71VHA
Brief Check of DIP-IPM and DIP-PFC
* Usually, they are in a state of being short-circuited if they are broken.
Measure the resistance in the following points (connectors, etc.). If they
are short-circuited, it means that they are broken.
1. Check of DIP-IPM
P2 - U , P2 - V , P2 - W , N2 - U , N2 - V , N2 - W
2. Check of DIP-PFC
P1 - L , P1 - N , L - N1 , N - N1
Note: The marks, L , N , N1 , N2 , P1 , P2 , U , V and W
shown in the diagram are not actually printed on the board.
CN2
Connect to the outdoor controller circuit board (CN2)
1
-
5
: Outdoor power circuit board
→
Transmitting signal
to the outdoor controller circuit board (0-5V DC)
2
-
5
: Zero cross signal (0-5V DC)
3
-
4
: Not used
6
-
5
: 16V DC
7
-
5
: 16V DC
1
,
2
,
6
,
7
: +
5
: –
]
[
LD1-LD2
280-380V DC
Connect to
the outdoor
controller
circuit board
(CNDC)
R, S
Connect to the ACL
230V AC
U, V, W
Connect to the compressor (MC)
Voltage among phases: 5V to 180V AC
LD9
Connect to
the earth
Only RP60/71
CN5
Primary current detection
(Connect to the outdoor
noise filter circuit board
(CN5))
CN4
Connect from the
outdoor controller
circuit board
(CN4)
CN3
Thermistor
<Heatsink>
(TH8)
DIP-IPM
DIP-PFC
OCH527B