8
OCH594B
3-5. CAPACITY CORRECTION (Refrigerant piping length)
Cooling and heating capacity is lowered according to the piping length. Capacity can be obtained by referring to the following
capacity curves.
Corrected pipe length (m) = actual pipe length (m) + number of bends × 0.3 (m)
Cooling
Heating
HRP200
HRP200
5
10 15 20 25 30 35 40 45 50 55 60 65 70 75 80
70
75
80
85
90
95
100
Corrected pipe length [m]
Capacity ratio [%]
SHW230
SHW230
3-4. Standard operation data
Reference data (connect to Plate HEX)
(MWA2-38PA)
o
2 pcs [connected in parallel]
Mode
Cooling
(A35/W7)
Heating
(A7/W35)
Total
Capacity
W
20,000
23,000
Input
kW
9.01
6.31
Electrical circuit
Outdoor unit
PUHZ-SHW230YKA2
Phase, Hz
3, 50
Voltage
V
400
Current
A
13.7
9.6
Refrigerant circuit
Discharge pressure
MPa
3.0
2.0
Suction pressure
MPa
0.7
0.6
Discharge temperature
ºC
79
73
Condensing temperature
ºC
49
35
Suction temperature
ºC
8
8
Evaporating temperature
ºC
6
2
Evaporator inlet temperature
ºC
7
——
Evaporator outlet temperature
ºC
6
——
Condenser inlet temperature
ºC
——
65
Condenser outlet temperature
ºC
——
34
W
ater
conditions
Flow volume
L/min
57.3
65.9
Outlet water temperature
ºC
7
35
Outdoor conditions
Intake air
temperature
D.B. ºC
35
7
W.B. ºC
24
6
Piping length : Main 2.5 m, Branch 2.5 m/2.5 m
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is: 1 (MPa) = 10.2 (kgf/cm²)