78
(3) Capacity correction
Cooling and heating capacity is lowered according to the piping length. Capacity can be obtained by referring
to the following capacity curves.
When the diameter of the gas pipe is smaller than the standard size, cooling capacity is lowered comparing to
the operation using the standard diameter pipe.
The lowered capacity can be obtained by referring to the capacity curves for gas pipe which is one or two size
smaller than standard size.
Corrected pipe length (m) = actual pipe length (m) + number of bends
o
0.3 (m)
1. Capacity curves 1 <Standard size>
2. Capacity curves 2 <When the gas pipe's diameter is one-size-smaller than the standard size>
3. Capacity curves 3 <When the gas pipe's diameter is two-size-smaller than the standard size>
Cooling
Heating
RP200,250
RP200,250
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100 105 110 115
125
120
70
75
80
85
90
95
100
Corrected pipe length [m]
Capacity ratio [%]
70
75
80
85
90
95
100
5
10
15
20
25
30
35
40
45
50
55
Corrected pipe length [m]
Capacity ratio [%]
Heating RP200(
[
22.2), RP250(
[
25.4)
Cooling RP200(
[
22.2)
Cooling RP250(
[
25.4)
70
75
80
85
90
95
100
5
10
15
20
25
Corrected pipe length [m]
Cpacity ratio [%]
Cooling RP250(
[
22.2)
Cooling RP200(
[
19.05)
Heating RP200(
[
19.05), RP250(
[
22.2)
OCS01-3.qxp 05.5.16 10:09 AM Page 78
Содержание Mr.SLIM PUHZ-RP140YHA
Страница 50: ...50 WIRED REMOTE CONTROLLER Unit mm 130 120 19 ...
Страница 51: ...51 WIRELESS REMOTE CONTROLLER Unit mm 159 3 55 58 19 ...
Страница 53: ...53 PEAD RP35EA PEAD RP50EA PEAD RP60EA PEAD RP71EA PEAD RP100EA PEAD RP125EA PEAD RP140EA ...
Страница 54: ...54 PEAD RP60GA PEAD RP71GA PEAD RP100GA ...
Страница 83: ...83 9 2 PLA RP AA 9 2 1 FRESH AIR INTAKE AMOUNT ...
Страница 84: ...84 ...
Страница 85: ...85 9 2 2 BRANCH DUCT Installation at site ...
Страница 95: ...95 PEAD RP60GA PEAD RP71GA ...
Страница 96: ...96 PEAD RP100GA ...
Страница 103: ...103 ...