75
(c) Capacity correction
Cooling and heating capacity is lowered according to pipe length. Capacity can be obtained by referring to the capacity
curves below. When the diameter of gas pipe is one size smaller than standard diameter, cooling capacity is lowered com-
paring to the standard diameter. The lowered capacity can be obtained by referring to capacity curves for gas pipe which is
one size smaller than standard size.
Corrected pipe length (m) = actual pipe length (m) + number of bends x 0.3 (m)
1
1
Capacity curves for PUHZ-RP • HA model <Standard size>
2
2
Capacity curve for PUHZ-RP35, 50 models
<When gas pipe is one size smaller than standard size>
Cooling
Heating
100
95
90
85
80
75
70
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
Note: The permitted pipe length is up to 55m for RP35, 50, 60, 71 model.
Cooling RP71 model
Cooling RP35, 60 models
Cooling RP50, 100 models
Heating RP35, 50, 60,
71, 100, 125 and 140
models
(Up to 55m for RP35,
50, 60, 71 model)
Cooling RP125 model
Cooling RP140 model
Capacity ratio [%]
Corrected pipe length
5
10
15
20
25
30
35
40
45
50
55
80
Capacity ratio [%]
Corrected pipe length
85
90
95
100
Heating RP35, RP50
Cooling RP35
Cooling RP50
OCS01-3.qxp 05.5.16 10:09 AM Page 75
Содержание Mr.SLIM PUHZ-RP140YHA
Страница 50: ...50 WIRED REMOTE CONTROLLER Unit mm 130 120 19 ...
Страница 51: ...51 WIRELESS REMOTE CONTROLLER Unit mm 159 3 55 58 19 ...
Страница 53: ...53 PEAD RP35EA PEAD RP50EA PEAD RP60EA PEAD RP71EA PEAD RP100EA PEAD RP125EA PEAD RP140EA ...
Страница 54: ...54 PEAD RP60GA PEAD RP71GA PEAD RP100GA ...
Страница 83: ...83 9 2 PLA RP AA 9 2 1 FRESH AIR INTAKE AMOUNT ...
Страница 84: ...84 ...
Страница 85: ...85 9 2 2 BRANCH DUCT Installation at site ...
Страница 95: ...95 PEAD RP60GA PEAD RP71GA ...
Страница 96: ...96 PEAD RP100GA ...
Страница 103: ...103 ...