background image

English

Deutsch

Français

Nederlands

Español

Italiano

Ελληνικά

Português

Dansk

Svenska

Türkçe

Русский

INSTALLATION MANUAL

For safe and correct use, read this manual and the indoor unit installation manual thoroughly before installing 

the air-conditioner unit.

INSTALLATIONSHANDBUCH

Aus Sicherheitsgründen und zur richtigen Verwendung vor der Installation die vorliegende Bedienungsanleitung 

und die Installationsanleitung der Innenanlage gründlich durchlesen die Klimaanlage.

MANUEL D’INSTALLATION

Avant d’installer le climatiseur, lire attentivement ce manuel, ainsi que le manuel d’installation de l’appareil inté-

rieur pour une utilisation sûre et correcte.

INSTALLATIONSMANUAL

Läs bruksanvisningen och inomhusenhetens installationshandbok noga innan luftkonditioneringen installeras så 

att den används på ett säkert och korrekt sätt.

INSTALLATIEHANDLEIDING

Lees deze handleiding en de installatiehandleiding van het binnenapparaat zorgvuldig door voordat u met het 

installeren van de airconditioner begint.

MANUALE DI INSTALLAZIONE

Per un uso sicuro e corretto, leggere attentamente il presente manuale ed il manuale d’installazione dell’unità 

interna prima di installare il condizionatore d’aria.

MANUAL DE INSTALACIÓN

Para un uso correcto y seguro, lea detalladamente este manual y el manual de instalación de la unidad interior 

antes de instalar la unidad de aire acondicionado.

EΓXEIPIΔIO OΔHΓIΩN EΓKATAΣTAΣHΣ 

Για σωστή και ασφαλή χρήση, διαβάστε προσεκτικά αυτό το εγχειρίδιο καθώς και το εγχειρίδιο εγκατάστασης της 

εσωτερικής μονάδας, προτού εγκαταστήσετε τη μονάδα του κλιματιστικού

MANUAL DE INSTALAÇÃO

Para uma utilização segura e correcta, leia atentamente este manual e o manual de instalação da unidade inte-

rior antes de instalar o aparelho de ar condicionado.

INSTALLATIONSMANUAL

Læs af sikkerhedshensyn denne manual samt manualen til installation af indendørsenheden grundigt, før du 

installerer klimaanlægget.

MONTAJ ELKİTABI

Emniyetli ve doğru kullanım için, klima cihazını monte etmeden önce bu kılavuzu ve iç ünite montaj kılavuzunu 

tamamıyla okuyun.

РУКОВОДСТВО ПО УСТАНОВКЕ

Для обеспечения безопасной и надлежащей эксплуатации внимательно прочтите данное руко

-

водство и руководство по установке внутреннего прибора перед установкой кондиционера.

FOR INSTALLER

FÜR INSTALLATEURE

POUR L’INSTALLATEUR

VOOR DE INSTALLATEUR

PARA EL INSTALADOR

PER L’INSTALLATORE

ΓΙΑ ΑΥΤΟΝ ΠΟΥ ΚΑΝΕΙ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ

PARA O INSTALADOR

TIL INSTALLATØREN

FÖR INSTALLATÖREN

ДЛЯ УСТАНОВИТЕЛЯ

MONTÖR İÇİN

Air-Conditioners

PUHZ-P200, 250YHA

BH79D068H02_cover.indd   1

8/24/2007   2:24:50 PM

Содержание Mr.Slim PUHZ-P200

Страница 1: ...installare il condizionatore d aria MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado EΓXEIPIΔIO OΔHΓIΩN EΓKATAΣTAΣHΣ Για σωστή και ασφαλή χρήση διαβάστε προσεκτικά αυτό το εγχειρίδιο καθώς και το εγχειρίδιο εγκατάστασης της εσωτερικής μονάδας προτού εγκαταστήσετε τη ...

Страница 2: ...0 copper phosphorus for copper and copper alloy seamless pipes to connect the refrigerant pipes If the pipes are not connected cor rectly the unit will not be properly grounded and electric shock may result Use only specified cables for wiring The connections must be made se curely without tension on the terminals If the cables are connected or in stalled incorrectly overheating or fire may result...

Страница 3: ... to the flared sections If mineral oil is mixed in the refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use a vacuum pump with a reverse flow check valve If the vacuum pump oil flows backward into the refrigerant lines refrigerant oil deterioration may result Use the foll...

Страница 4: ...outlet guides for upward airflow 3 Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance is 1000 mm or more 4 Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance is 1000 mm or more 5 Single parallel unit arrangement Fig 2 16 When using an optional air outlet guide installed for upward airflow the clearance is 1000 mm or m...

Страница 5: ...he flare nuts for the following pipe size D Fig 4 1 RP50 RP60 71 RP100 140 Gas side Pipe size mm ø12 7 ø15 88 ø15 88 Liquid side Pipe size mm ø6 35 ø9 52 ø9 52 When bending the pipes be careful not to break them Bend radii of 100 mm to 150 mm are sufficient Make sure the pipes do not contact the compressor Abnormal noise or vibration may result 1 Pipes must be connected starting from the indoor un...

Страница 6: ...nutes and make sure the pressure does not decrease 3 Pressurize to 4 15 MPa 41 5 kgf cm2 G and measure the surrounding tem perature and refrigerant pressure 3 If the specified pressure holds for about one day and does not decrease the pipes have passed the test and there are no leaks If the surrounding temperature changes by 1 C the pressure will change by about 0 01 MPa 0 1 kgf cm2 G Make the nec...

Страница 7: ...piping Limits of refrigerant piping installation 5 Drainage piping work Outdoor unit drainage pipe connection When drain piping is necessary use the drain socket or the drain pan option Drain socket PAC SG61DS E Drain pan PAC SG64DP E 6 Electrical work 6 1 Outdoor unit Fig 6 1 Fig 6 2 1 Remove the service panel 2 Wire the cables referring to the Fig 6 1 and the Fig 6 2 A Indoor unit B Outdoor unit...

Страница 8: ...ng size 3 1 5 Polar 3 A 10 m wire is attached in the remote controller accessory 4 The voltage are NOT against the ground S3 terminal has DC 24 V against S2 terminal However between S3 and S1 these terminals are not electrically insulated by the transformer or other device Notes 1 Wiring size must comply with the applicable local and national code 2 Power supply cords and Indoor unit Outdoor unit ...

Страница 9: ...drop below 1 MΩ due to refrigerant accumulat ing in the compressor This is not a malfunction Perform the following procedures 1 Remove the wires from the compressor and measure the insulation resistance of the compressor 2 If the insulation resistance is below 1 MΩ the compressor is faulty or the resist ance dropped due the accumulation of refrigerant in the compressor 3 After connecting the wires...

Страница 10: ...wn operation make sure that the low pressure is lowered to near 0 MPa gauge 9 System control Fig 9 1 SW1 Function table SW1 Function Operation according to switch setting ON OFF SW1 function settings 1 Compulsory defrosting Start Normal 2 Error history clear Clear Normal 3 4 5 6 Refrigerant system ad dress setting Settings for outdoor unit addresses 0 to 15 ON OFF A Outdoor unit B Indoor unit C Ma...

Страница 11: ...ed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BH79D068H02 Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 89 336 EEC The product at hand is based on the following EU regulations ...

Отзывы: