65
PCA-RP50GA
PCA-RP60GA
PCA-RP71GA
PCA-RP100GA
PCA-RP125GA
PCA-RP140GA
PCH-P50GAH
PCH-P60GAH
PCH-P71GAH
PCH-P100GAH
PCH-P125GAH
PCH-P140GAH
X4
X1
FAN
(WHT)
1 3
1 3
1 3
1 3
5
1 2 3
BLK
WHT
RED
C
MF
DP
X4
X1
BCR
POWER
CNDK
(RED)
D.U.M
CNP
(BLU)
(OPTION)
ZNR
POWER
CND
(ORN)
1
2
1
2
3
P.B
I.B
CNDK
(RED)
DC13.1V
CN2S
(WHT)
WHT
RED
YLW
ORN
BLK
BLK
BLK
BLK
BLK
BLU
BLU
BRN
ORN
WHT
FUSE
1 2
POWER
CN2D(WHT)
1 3
INDOOR/OUTDOOR
COMMUNICATION
CN3C(BLU)
SWE
ON
OFF
SW2
SW1
Refer to tables 1
and 2 for service PCB.
LED3 LED2 LED1
TO OUTDOOR UNIT
TB4
S1
S2
S3
YLW
ORN
ORN
BRN
50~71 TYPE
CN41
CN2L
CN51
CN32
VANE
CN6V
(GRN)
MV
6
6
9
MV
6
6
WIRELESS
CN90
(WHT)
INTAKE
CN20
(RED)
LIQUID
CN21
(WHT)
D.SENSOR
CN31
(WHT)
CN31
DRAIN SENSOR
DS
PIPE
CN29
(BLK)
1 2
1 2 3
1 2 3
1 2
1 2
TH5
TH1
TH2
REMOCON
CN22
(BLU)
1 2
2
1
TB5
R.B
TB6
1 2
TRANSMISSION WIRES DC12V
1 2
1 2
W.B
BZ
CNB
RECEIVER
RU
LED1 LED2 SW2 SW1
100~140 TYPE
MV
5
5
3
1
3
1
POWER
CND
(ORN)
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(BLU)
TB2
TB4
POWER SUPPLY
~(1PHASE)
230V 50Hz
RED
BLU
YLW
GRN/YLW
ORN
ORN
BRN
TO OUTDOOR UNIT
L
S1
S2
S3
N
I.B
YLW
ORN
W
1 (Fig.1)
(WHT)
I.B
HEATER
CN24
(YLW)
26H
RED
6
1
RED
GRY
2
6
5
1
88H
YLW
YLW
TB2
POWER SUPPLY
~(1PHASE)
230V 50Hz
88H
FS2
H1
L
RED
RED 5
3
RED
BLU
GRN/YLW
WHT
N
2
1
FS1
PCH-P50~P140GAH
models only
Please set the voltage using the remote
controller.
For the setting method, please refer to
the indoor unit Installation Manual.
SW1
Table 1
Service board
1 2 3 4 5
ON
OFF
MODELS
PCA-RP.GA
PCH-P.GAH
SW2
Table 2
Service board
1 2 3 4 5
ON
OFF
MODELS
PCA-RP50GA
PCH-P50GAH
1 2 3 4 5
ON
OFF
PCA-RP60GA
PCH-P60GAH
1 2 3 4 5
ON
OFF
PCA-RP71GA
PCH-P71GAH
Service board
1 2 3 4 5
ON
OFF
MODELS
PCA-RP100GA
PCH-P100GAH
1 2 3 4 5
ON
OFF
PCA-RP125GA
PCH-P125GAH
1 2 3 4 5
ON
OFF
PCA-RP140GA
PCH-P140GAH
P.B
INDOOR POWER BOARD
SYMBOL
NAME
I.B
INDOOR CONTROLLER BOARD
FUSE
FUSE (T6.3AL250V)
ZNR
VARISTOR
CN2L CONNECTOR(LOSSNAY)
CN32 CONNECTOR(REMOTE SWITCH)
CN41 CONNECTOR(HA TERMINAL-A)
CN51 CONNECTOR(CENTRALLY CONTROL)
SW1
SWITCH (MODEL SELECTION)
W
See Table 1.
SW2
SWITCH (CAPACITY CODE)
W
See Table 2.
SWE
SWITCH(EMERGENCY OPERATION)
X4
RELAY(FAN MOTOR)
X1
RELAY(DRAIN PUMP)
BCR
POWER SUPPLY(R.B)
LED1 POWER SUPPLY(I.B)
LED2
TRANSMISSION(INDOOR-OUTDOOR)
LED3
FAN CONTROL ELEMENT
C
CAPACITOR(FAN MOTOR)
FAN MOTOR
VANE MOTOR
MF
MV
DRAIN-UP MACHINE (OPTION)
DP
DRAIN SENSOR (OPTION)
DS
SYMBOL
NAME
TB4
TERMINAL BLOCK(INDOOR/OUTDOOR CONNECTING LINE)
TB2
TERMINAL BLOCK (HEATER)
W
PCH-P.GAH
models only or option for PCA RP.GA models.
TERMINAL BLOCK(REMOTE CONTROLLER
TRANSMISSION LINE )
ROOM TEMP.THERMISTOR
(0
;
/15k
'
, 25
;
/5.4k
'
DETECT)
PIPE TEMP.THERMISTOR/LIQUID
(0
;
/15k
'
, 25
;
/5.4k
'
DETECT)
COND./EVA.TEMP.THERMISTOR
(0
;
/15k
'
, 25
;
/5.4k
'
DETECT)
TB5,TB6
TH5
TH1
TH2
W.B
WIRELESS REMOTE CONTROLLER BOARD(OPTION)
RECEIVING UNIT
BUZZER
LED(RUN INDICATOR)
LED(HOT ADJUST)
SWITCH(HEATING ON/OFF)
SWITCH(COOLING ON/OFF)
WIRED REMOTE CONTROLLER BOARD
R.B
HEATER
RU
BZ
LED1
LED2
SW1
SW2
NAME
SYMBOL
HEATER
H1
HEATER THERMAL SWITCH
26H
HEATER CONTACTOR
88H
THERMAL FUSE(98
;
10A:50GAH/117
;
16A:100GAH
110
;
16A:60,71,125,140GAH)
FS1,2
NOTES:
1. Since the outdoor side electric wiring may change be sure to
check the outdoor unit electric wiring for servicing.
2. Indoor and outdoor connecting wires are made with polarities, make
wiring matching terminal numbers (S1, S2, S3).
3. Make sure that the main power supply of the booster heater is
independent.
4. Symbols used in wiring diagram above are,
: Connector, : Terminal (block).
W
1. When work to supply power separately to
Indoor and Outdoor unit was applied, refer to Fig 1.
W
2. For power supply system of this unit,
refer to the caution label located near this diagram.
[Servicing]
Fasten terminal of the terminal board "TB4"equips lock system.
To remove the fastened terminal, pull it while pressing the protruding
portion (locking lever) of the terminal. The fastened terminal protruding
portion should face upward.
When installing drain-up
machine (Optional part).
W
When installing optional
drain-up machine disconnect
the CN31 jumper connector
and replace it with the
drain sensor (DS).
OCS02-3.qxp 05.7.20 5:17 PM Page 65
Содержание Mr.Slim PU-P100VGAA
Страница 56: ...56 WIRED REMOTE CONTROLLER Unit mm 130 120 19 ...
Страница 57: ...57 WIRELESS REMOTE CONTROLLER Unit mm 159 3 55 58 19 ...
Страница 60: ...60 PEAD RP35EA PEAD RP50EA PEAD RP60EA PEAD RP71EA PEAD RP100EA PEAD RP125EA PEAD RP140EA ...
Страница 61: ...61 PEHD P35EAH PEHD P50EAH PEHD P60EAH PEHD P71EAH PEHD P100EAH PEHD P125EAH PEHD P140EAH ...
Страница 62: ...62 PEAD P60GA PEAD P71GA PEAD P100GA ...
Страница 77: ...77 8 2 PLA RP AA PLH P AAH 8 2 1 FRESH AIR INTAKE AMOUNT ...
Страница 78: ...78 8 2 2 BRANCH DUCT Installation at site ...
Страница 89: ...89 PEAD RP60GA PEAD RP71GA ...
Страница 90: ...90 PEAD RP100GA ...
Страница 95: ...95 ...