background image

100 

(150

)

200 

(300

)

1000

Max. 500

500 

(1000

)

200 

(300

)

1000 

(1500

)

300 

(500

)

1000 

(1500

)

Max. 300

1000 

(1500

)

1000 

(1500

)

300 

(500

)

500 

(1000

)

400 

(600

) 1000 

(2000

)

100 

(150

)

1000 

(1500

)

500 

(800

)

150

1000 

(1500

)

400 

(600

)

2000 

(3000

)

300 

(500

)

Fig. 2-6

Fig. 2-7

Fig. 2-8

Fig. 2-9

Fig. 2-10

Fig. 2-11

Fig. 2-12

Fig. 2-13

Fig. 2-14

Fig. 2-15

Fig. 2-16

Fig. 2-17

Fig. 2-18

100 

(200

)

200 

(300

)

100 

(200

)

150 

(250

)

150 

(250

)

1000 (1500)

300 (500)

Max. 500

100 

(150

)

500 

(1000

)

UNIT: mm

(  ): P125, P140

01_BG79U892H05_EN.indd   13

4/19/2016   1:16:02 PM

Содержание Mr. Slim PU-P HA Series

Страница 1: ...ioners PU H P HA INSTALLATION MANUAL For safe and correct use read this manual and the indoor unit installation manual thoroughly before installing the air conditioner unit English 01_BG79U892H05_EN indd 1 4 19 2016 1 16 00 PM ...

Страница 2: ...efrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pressure in the refrigerant line and may result in an explosion and other hazards The use of any refrigerant other than that specified for the system will cause mechanical failure or syst...

Страница 3: ...ng If dust debris or moisture enters the refrigerant lines oil deterioration or compressor breakdown may result Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections If mineral oil is mixed in the refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will...

Страница 4: ...ace as shown Do not install the optional air outlet guides for upward airflow 3 Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance for P125 P140 models is 1000 mm or more 4 Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance for P125 P140 models is 1000 mm or more 5 Single parallel unit arrangement Fig 2 16 When using ...

Страница 5: ...or parts of the drain pipe should be wrapped with polyethylene foam insulation materials specific gravity of 0 03 thickness of 9 mm or more Apply thin layer of refrigerant oil to pipe and joint seating surface before tighten ing flare nut A Use 2 wrenches to tighten piping connections B Use leak detector or soapy water to check for gas leaks after connections are completed Apply refrigerating mach...

Страница 6: ...d pressure little by little 1 Pressurize to 0 5 MPa 5 kgf cm G wait 5 minutes and make sure the pres sure does not decrease 2 Pressurize to 1 5 MPa 15 kgf cm G wait 5 minutes and make sure the pressure does not decrease 3 Pressurize to 4 15 MPa 41 5 kgf cm G and measure the surrounding tem perature and refrigerant pressure 3 If the specified pressure holds for about one day and does not decrease t...

Страница 7: ...dditional refrigerant charging amount 31 40 m 41 50 m P71 140 50 m 30 m 0 6 kg 1 2 kg 4 Installing the refrigerant piping 4 7 For twin triple combination Refrigerant piping limitation of length height difference are shown in the figure Fig 4 8 A Indoor unit B Outdoor unit C Multi distribution pipe option D Height difference Indoor unit Outdoor unit Max 30 m E Height difference Indoor unit Indoor u...

Страница 8: ...r switch can result in severe damage to internal parts Keep the power switch turned on during the operational season The followings must be checked as well The outdoor unit is not faulty LED1 and LED2 on the control board of the out door unit flash when the outdoor unit is faulty Both the gas and liquid stop valves are completely open A protective sheet covers the surface of the DIP switch panel o...

Страница 9: ...opped However even if the unit is stopped and SW1 1 is set to ON less than three minutes after the compressor stops the refrigerant collecting operation cannot be performed Wait until com pressor has been stopped for three minutes and then set SW1 1 to ON again Set the refrigerant address using the DIP switch of the outdoor unit 1 Wiring from the Remote Control This wire is connected to TB5 termin...

Страница 10: ...dicated on the SPEC NAME PLATE Sequential number for each unit 00001 99999 Month of manufacture A 1 B 2 C 3 D 4 E 5 F 6 G 7 H 8 J 9 K 10 L 11 M 12 Year of manufacture western calendar 2014 4 2015 5 01_BG79U892H05_EN indd 10 4 19 2016 1 16 01 PM ...

Страница 11: ...d under eneansvar at de herunder beskrevne airconditionanlæg og varmepumper til brug i privat boligbyggeri erhvervsområder og inden for let industri intygar härmed att luftkonditioneringarna och värmepumparna som beskrivs nedan för användning i bostäder kommersiella miljöer och lätta industriella miljöer ev ticaret ve hafif sanayi ortamlarında kullanım amaçlı üretilen ve aşağıda açıklanan klima ve...

Страница 12: ...rtalingen van het origineel VOORZICHTIG Het lekken van koelvloeistof kan verstikking veroorzaken Zorg voor ventilatie in overeenstemming met EN378 1 Isoleer de leidingen met isolatiemateriaal Direct contact met de onbedekte leidingen kan leiden tot brandwonden of bevriezing Stop nooit batterijen in uw mond om inslikking te voorkomen Het inslikken van batterijen kan verstikking of vergiftiging vero...

Страница 13: ... 2000 100 150 1000 1500 500 800 150 1000 1500 400 600 2000 3000 300 500 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 100 200 200 300 100 200 150 250 150 250 1000 1500 300 500 Max 500 100 150 500 1000 UNIT mm P125 P140 01_BG79U892H05_EN indd 13 4 19 2016 1 16 02 PM ...

Страница 14: ...he residential commercial and light industrial environment HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Please be sure to put the contact address telephone number on this manual before handing it to the customer 01_BG79U892H05_EN indd 14 4 19 2016 1 16 02 PM ...

Отзывы: