![Mitsubishi Electric Mr.Slim PLH-P3AAH.UK Скачать руководство пользователя страница 41](http://html.mh-extra.com/html/mitsubishi-electric/mr-slim-plh-p3aah-uk/mr-slim-plh-p3aah-uk_technical-and-service-manual_1810251041.webp)
41
Total
Electrical circuit
Refrigerant circuit
Indoor side
Outdoor
side
Service Ref.
SHF
BF
W
kW
Mode
Capacity
Input
PLH-P3AAH.UK
PLH-P3AAH
1
.UK
PLH-P4AAH.UK
PLH-P4AAH
1
.UK
PLH-P5AAH.UK
PLH-P5AAH
1
.UK
PLH-P6AAH.UK
PLH-P6AAH
1
.UK
Cooling
7,800
3.44
Heating
9,300
3.50
Cooling
9,700
3.69
Heating
10,600
3.93
Cooling
12,800
5.00
(kgf/
F
)
(kgf/
F
)
Heating
14,900
5.34
Cooling
14,300
5.94
Heating
17,100
6.36
(23.2)
(4.7)
(26.4)
(4.21)
(23.2)
(4.6)
(24.1)
(4.2)
(20.2)
(5.5)
(21.6)
(4.3)
(23.4)
(4.8)
(24.3)
(4.0)
14.81/5.29
2.30
0.47
81.0
44.0
4.8
5
27
19
13.4
35
24
0.74
0.13
15.76/5.63
2.38
0.39
88.0
45.0
0
5
20
15
45.1
7
6
—
—
15.71/5.55
1.98
0.54
71.0
42.0
7.5
5
27
19
14.0
35
24
0.78
0.12
16.58/5.86
2.12
0.42
7.5
47.0
0.6
5
20
15
40.1
7
6
—
—
7.60
2.27
0.46
78.6
41.0
4.4
5
27
19
12.3
35
24
0.72
0.10
8.15
2.59
0.41
86.6
44.0
4.2
5
20
15
47.3
7
6
—
—
9.03
2.27
0.45
80.6
45.0
2.4
5
27
19
11.3
35
24
0.69
0.09
9.56
2.36
0.41
83.5
46.0
-1.0
5
20
15
51.2
7
6
—
—
1,50
240
0.81
1/3, 50
240/415
1,50
240
1.25
1/3, 50
240/415
1,50
240
1.43
PUH-P5YGAA.UK
3, 50
415
1,50
240
1.64
PUH-P6YGAA.UK
3, 50
415
Phase,Hz
Volts
Amperes
Outdoor unit Service Ref.
Phase,Hz
Volts
Amperes
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
V
A
V
A
Mpa
Mpa
°
C
°
C
°
C
m
°
C
°
C
°
C
°
C
°
C
Indoor unit Service Ref.
D.B.
W.B.
D.B.
D.B.
W.B.
PLH-P3AAH.UK
PLH-P3AAH
1
.UK
PLH-P4AAH.UK
PLH-P4AAH
1
.UK
PLH-P5AAH.UK
PLH-P5AAH
1
.UK
PLH-P6AAH.UK
PLH-P6AAH
1
.UK
PUH-P3VGAA.UK
PUH-P3YGAA.UK
PUH-P4VGAA.UK
PUH-P4YGAA.UK
The unit of pressure has been changed to Mpa based on international SI system.
The conversion factor is : 1(Mpa)=10.2(kgf/
f
f
)
PLH-P3AAH.UK
PLH-P3AAH
1
.UK
28
4.9
7.4
30
6.6
8.9
30
5.2
7.9
Air flow
Air speed
Coverage range
m
3
/min
m/sec.
m
20
4.0
5.7
Service Ref.
PLH-P6AAH.UK
PLH-P6AAH
1
.UK
PLH-P5AAH.UK
PLH-P5AAH
1
.UK
PLH-P4AAH.UK
PLH-P4AAH
1
.UK
5. OUTLET AIR SPEED AND COVERAGE RANGE
w
The air coverage range is the value up to the position where the air speed is 0.25m/sec.
When air is blown out horizontally from the unit at the Hi notch position.
The coverage range should be used only as a general guideline since it varies according to the size of the room and the
furniture inside the room.
OC236(181A)---2.qxp 01/9/27 5:31 PM Page 41
All manuals and user guides at all-guides.com
all-guides.com