12
Service Ref.
Item
Function
Capacity
w
1
Btu/h
W
Total input
w
1
k W
Service Ref.
Power supply (phase, cycle,voltage)
Input
w
2
kW
Running current
w
2
A
Starting current
w
2
A
External finish
Heat exchanger
Fan
Fan (drive)
o
No.
Fan motor output
kW
Airflow (Lo-Mi2-Mi1-Hi)
K
/ min (CFM)
External static pressure
Pa (mmAq)
Booster heater
kW
Operation control & Thermostat
Sound level (Lo-Mi2-Mi1-Hi)
dB
Unit drain pipe I.D.
mm (in.)
Dimensions
Indoor unit
W
mm (in.)
D
mm (in.)
H
mm (in.)
Weight
kg (lbs.)
Service Ref.
Power supply (phase, cycle, voltage)
Running current
A
Starting current
A
External finish
Refrigerant control
Compressor
Model
Motor output
kW
Starter type
Protection devices
Heat exchanger
Fan (drive)
o
No.
Fan
Fan motor output
kW
Airflow
K
/ min (CFM)
Crankcase heater
W
Defrost method
Sound level
Dimensions
Cooling
dB
Heating
dB
W
mm (in.)
D
mm (in.)
H
mm (in.)
Outdoor unit
Refrigerant piping
Weight
kg (lbs.)
Refrigerant
Charge
kg (lbs.)
Oil (Model)
L
Pipe size O.D.
PLH-P5AAH.UK
Cooling
Heating
43,700
54,600 [64,800]
12,800
16,000 [19,000]
5.55
5.93 [8.93]
PLH-P5AAH.UK
Single phase, 50Hz, 220–230–240V
0.30
0.30 <3.00>
1.43
1.43 <12.50>
2.0
2.0 <12.50>
Munsell 0.70Y 8.59/0.97
Plate fin coil
Turbo fan (direct)
o
1
0.120
22-25-28-30 (775-880-990-1,060)
0 (direct blow)
<3.0>
Remote controller & built-in
35-38-41-43
32 (1-1/4)
UNIT : 840 (33-1/16) PANEL : 950 (37-3/8)
UNIT : 840 (33-1/16) PANEL : 950 (37-3/8)
UNIT : 298 (11-3/4)
PANEL : 30 (1-3/16)
UNIT : 32 (71)
PANEL : 5 (11)
PUH-P5YGA
3 phases, 50Hz, 380–400–415V (4wires)
8.39
8.74
79
Munsell 5Y 8/1
Linear expansion valve
Hermetic
HE86YAA
4.3
Line start
Internal thermostat, Anti-phase protector, Thermal relay, HP switch, LP switch, Discharge thermo.
Plate fin coil
Propeller (direct)
o
2
0.075+0.075
95 (3,360)
38
Reverse cycle
53
55
1,050 (41-5/16)
330+20 (13+3/4)
1,260 (49-5/8)
122 (269)
R407C
5.8 (12.8)
2.0 (MEL32)
9.52 (3/8)
19.05 (3/4)
Flared
Flared
Max. 50m
Max. 50m
Liquid
mm (in.)
Gas
mm (in.)
Connection method
Indoor side
Outdoor side
Between the indoor &
outdoor units
Height difference
Piping length
NOTE:
1. Rating conditions (ISO T1)
Cooling : Indoor
: D.B. 27
:
(80˚F), W.B. 19
:
(66˚F)
Outdoor
: D.B. 35
:
(95˚F) W.B. 24
:
(75˚F)
Heating : Indoor
: D.B. 20
:
(68˚F)
Outdoor
: D.B. 7
:
(45˚F)
W. B. 6
:
(43˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor
Outdoor
Cooling
Upper limit D.B. 35
:
, W.B. 22.5
:
D.B. 46
:
Lower limit D.B. 19
:
, W.B. 15
:
D.B. -5
:
Heating
Upper limit
D.B. 28
:
D.B. 24
:
, W.B. 18
:
Lower limit
D.B. 17
:
D.B. -11
:
, W.B. -12
:
w
1 : [ ] Shows the total rating.
w
2 : < > Shows the only booster heater rating.
3. Above data based on indicated voltage
Indoor unit
Single phase 240V 50Hz
Outdoor unit
3 phases 415V 50Hz
OC236(181A)---1.qxp 01/9/27 5:30 PM Page 12
All manuals and user guides at all-guides.com