1. PERFORMANCE DATA
1) COOLING CAPACITY(1)
PKH-P2.5FALH, PKH-P2.5FALH
1
PKA-P2.5FAL,
PKA-P2.5FAL
1
CA : Capacity (W) SHC(W) :Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
Outdoor intake air D.B.(
°
C)
20
25
30
Indoor
Intake air
D.B.(
°
C)
Indoor
Intake air
W.B.(
°
C)
20
20
20
22
22
22
24
24
24
24
26
26
26
26
28
28
28
28
30
30
30
30
32
32
32
32
34
34
34
34
16
18
20
16
18
20
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
CA
6,435
6,890
7,410
6,435
6,890
7,410
6,435
6,890
7,410
7,898
6,435
6,890
7,410
7,898
6,435
6,890
7,410
7,898
6,435
6,890
7,410
7,898
6,435
6,890
7,410
7,898
6,435
6,890
7,410
7,898
SHC(W)
4,505
3,996
3,409
5,019
4,547
4,001
5,534
5,099
4,594
3,949
6,049
5,650
5,187
4,581
6,435
6,201
5,780
5,212
6,435
6,752
6,373
5,844
6,435
6,890
6,965
6,476
6,,435
6,890
7,410
7,108
SHF
0.70
0.58
0.46
0.78
0.66
0.54
0.86
0.74
0.62
0.50
0.94
0.82
0.70
0.58
1.00
0.90
0.78
0.66
1.00
0.98
0.86
0.74
1.00
1.00
0.94
0.82
1.00
1.00
1.00
0.90
SHF
0.70
0.58
0.46
0.78
0.66
0.54
0.86
0.74
0.62
0.50
0.94
0.82
0.70
0.58
1.00
0.90
0.78
0.66
1.00
0.98
0.86
0.74
1.00
1.00
0.94
0.82
1.00
1.00
1.00
0.90
SHF
0.70
0.58
0.46
0.78
0.66
0.54
0.86
0.74
0.62
0.50
0.94
0.82
0.70
0.58
1.00
0.90
0.78
0.66
1.00
0.98
0.86
0.74
1.00
1.00
0.94
0.82
1.00
1.00
1.00
0.90
P.C.
2.18
2.22
2.28
2.18
2.22
2.28
2.18
2.22
2.28
2.34
2.18
2.22
2.28
2.34
2.18
2.22
2.28
2.34
2.18
2.22
2.28
2.34
2.18
2.22
2.28
2.34
2.18
2.22
2.28
2.34
CA
6,240
6,695
7,248
6,240
6,695
7,248
6,240
6,695
7,248
7,735
6,240
6,695
7,248
7,735
6,240
6,695
7,248
7,735
6,240
6,695
7,248
7,735
6,240
6,695
7,248
7,735
6,240
6,695
7,248
7,735
SHC(W)
4,368
3,883
3,334
4,867
4,419
3,914
5,366
4,954
4,493
3,868
5,866
5,490
5,073
4,486
6,240
6,026
5,653
5,105
6,240
6,561
6,233
5,724
6,240
6,695
6,813
6,343
6,240
6,695
7,248
6,962
P.C.
2.30
2.34
2.39
2.30
2.34
2.39
2.30
2.34
2.39
2.48
2.30
2.34
2.39
2.48
2.30
2.34
2.39
2.48
2.30
2.34
2.39
2.48
2.30
2.34
2.39
2.48
2.30
2.34
2.39
2.48
CA
6,045
6,468
7,053
6,045
6,468
7,053
6,045
6,468
7,053
7,540
6,045
6,468
7,053
7,540
6,045
6,468
7,053
7,540
6,045
6,468
7,053
7,540
6,045
6,468
7,053
7,540
6,045
6,468
7,053
7,540
SHC(W)
4,232
3,751
3,244
4,715
4,269
3,808
5,199
4,786
4,373
3,770
5,682
5,303
4,937
4,373
6,045
5,821
5,501
4,976
6,045
6,338
6,065
5,580
6,045
6,468
6,629
6,183
6,045
6,468
7,053
6,786
P.C.
2.43
2.50
2.56
2.43
2.50
2.56
2.43
2.50
2.56
2.64
2.43
2.50
2.56
2.64
2.43
2.50
2.56
2.64
2.43
2.50
2.56
2.64
2.43
2.50
2.56
2.64
2.43
2.50
2.56
2.64