Страница 1: ...e air conditioner unit MANUEL D iNSTALLATION Avant d installer le climatiseur lire attentivement ce manuel ainsi que le manuel d installation de I appareil exterieur pour une utilisation sore et correct MANUAL DE INSTALACION Para un uso correcto y seguro lea detalladamente este manual y el manual de instalaci6n de la unidad exterior antes de instalar la unidad de aire acondicionado m m ...

Страница 2: ... where combustible gases may leak be produced flow or accumulate If combustible gas accumulates around the unit fire or explosion may result Do not keep food plants caged pets artwork or precision instruments in the direct airflow of the indoor unit or too close to the unit as these items can be damaged by temperature changes or dripping water When the room humidity exceeds 80 or when the drainpip...

Страница 3: ...holder 1 ZI Alkali batteries size AAA 2 _i Tapping screw 3 5 x 16 2 Block of cushion 1 c_ Wired remote controller ili Remote controller cable QUANTITY PKA A HAL PKA A HA 1 12 3 3 1 1 1 LOCATION OF SETTING Fix at the back of the unit 3 2 Installing the wall mounting fixture Fig 3 2 3 2 1 Setting the wall mounting fixture and piping positions I_ Using the wail mounting fixture determine the unit s i...

Страница 4: ...uding pipes etc may have to be bent and have their length modified to suit the unit Use marking on the mount board as a reference when adjusting the length of the embedded cooling pipe During construction give the length of the extruding pipes etc some leeway Mount board B Reference marking for flare connection Through hole On site piping 3 4 Preparing the indoor unit Check beforehand because the ...

Страница 5: ...r unit to the left and right and verify that the indoor unit is hung securely 5 Fasten by pushing the bottom part of the indoor unit onto the mount board i Fig 3 10 Check that the knobs on the bottom of the indoor unit are securely hooked into the mount board i 6 After installation be sure to check that the indoor unit is installed level Mount board B Indoor unit Hook b square hole Left and left r...

Страница 6: ... joint seating surface before tightening flare nut Use two wrenches to tighten piping connections Use refrigerant piping insulation provided to insulate indoor unit connections Insulate carefully _ Flare cutting dimensions Copper pipe O D mm inch _6 35 1 4 e12 7 112 iB Flare nut tightening torque Copper pipe O D mm inch _6 35 1 4 e12 7 112 Flare dimensions eA dimensions mm inch 8 7 9 1 11 32 23 64...

Страница 7: ...avy The end of drain pipe is under water H Drainage ditch 5 cm 1 31 32 inch or less between the end of drain pipe and the ground J Drain hose k Soft PVC hose Inside diameter 15 mm 19 32 inch or Hard PVC pipe VP 16 Bond with PVC type adhesive Fig 5 2 Fig 5 3 Preparing left and left rear piping Fig 5 2 Remove the drain cap Remove the drain cap by holding the bit that sticks out at the end of the pip...

Страница 8: ...polarity F Lead _ Terminal screw H Earth wire Connect earth wire in the direction illustrated in the diagram i Wired remote control cord onIy for PKA A HA J Indoor outdoor connection cord k Hook L Conduit plate M Bush purchased locally N Lock nut purchased locally Connector purchased locally P Conduit purchased locally Fig 6 1 6 1 1 indoor unit power supplied from outdoor unit A control applicatio...

Страница 9: ... remote controller cord in order to run the remote controller cord from the back then seal the hole with putty Run the remote controller cord through the cut out upper case then seal the cut out notch with putty similarly as above B4 To lead the remote controller cord from the back of the controller B 2 To run the remote controller cord through the upper portion 3 For direct installation on the wa...

Страница 10: ...ly voltage 230V setting number 1 208 V setting number 2 _ Press the MODE button E and mode and the setting number I and _ will change to being on constantly and the contents of the setting can be confirmed _ Press the FILTER A and TEST RUN B buttons simultaneously for at least two seconds The function selection screen will disappear momentarily and the air conditioner OFF display will appear __L i...

Страница 11: ...maining time display _ Set temperature button H Mode selection button i Fan speed button M TEST button 7 2 Test run The following 3 methods are available 7 2 1 Using wired remote controller Fig 7 1 i Turn on the power at least 12 hours before the test run _i Press the TEST button twice TEST RUN liquid crystal display _i Press the Mode selection button Make sure that wind is blown out _i Press the ...

Страница 12: ...c 0 5 sec 0 5 sec Approx 2 5 sec 0 5 sec 0 5 sec starts y _ Star signal received Number of flashes beeps in pattern indicates the check Number of flashes beeps in pattern indicates code in the following table i e n 5 for P5 the check code in the following table Output pattern B Beeper sounds Beep Beep Beep Beep Beep O E A O I LF LFq_q __ra I INDICATOR _ _ _ _ 4 lamp flash Off On On On On On Off On...

Страница 13: ... operated properly after the above test run has been performed refer to the following table to remove the cause Symptom Wired remote controller For about 2 PLEASE WAIT minutes following power on PLEASE WAIT _ Error code After about 2 minutes has expired following Display messages do not appear even power on when operation switch is turned ON operation lamp does not light up On the wireless remote ...

Страница 14: ...Cumulative ON OFF Operation inf tion _ number _ curie2 q boMON Heat excbanger Outdoor unit information Indoor room Indoor unit information The filter operation time displayed is the number of hours the filter has been used since the filter reset was performed 4 Press the button 5 The data is in _ AirElow temperature display example displayed Flashing Display _ Waiting for 147 F Approx 10 sec __ re...